Advanced Energy Thyro-PX 1PX Скачать руководство пользователя страница 91

FIRST TIME OPERATION

On delivery, the device is parameterized to the respective power section, and the 
TAKT operating mode is set. You should review these standard parameters, and, if 
necessary, adjust them for your application.

To Operate the Thyro-PX Unit for the First Time

1. Install the unit according to the installation procedures in this user manual.

The minimum connections are power, load, 

SETPOINT

, and 

PULSE LOCK 

jumper.

Important

By default, the unit is configured to require a customer supplied 

PULSE 

LOCK

 jumper. The unit may be customer configured to not require this 

jumper.

2. Turn on the system circuit breakers and apply AC input to the unit.

When the unit receives AC input, it performs self-diagnostics. If the unit detects 
an error, the unit sets the respective fault bits and lights the 

FAULT

 LED, or the 

light green 

ON / READY

 LED if the fault is severe. You will not be able to 

apply power to the load until you clear the fault.

3. Verify that the light green 

ON / READY

 LED is lit. 

4. Verify that the 

LIMIT

 LED is not lit.

5. Verify that the 

PULSE LOCK

 LED is not lit.

6. Verify that the 

FAULT

 LED is not lit. 

7. Verify that an increase in setpoint applies power to the load.

If the Thyro-PX unit is delivering power and the 

LIMIT

 LED is not lit, the unit is 

functioning properly.

Important

AE recommends that you update the firmware to the latest revision using the 
Thyro-Tool Pro software.

Related Links

• “Operating Modes” on page 5

42

• “Thyro

Touch Display” on page 4

11

• “Software User Interface” on page 4

13

Advanced Energy

®

Thyro-PX

®

 Power Controller

57010148-00G

Installation, Setup, and Operation

5‑41

Содержание Thyro-PX 1PX

Страница 1: ...Thyro PX Power Controller User Manual April 2020 57010148 00G...

Страница 2: ...lt of the reliance on or use of the information contained herein PRODUCT USAGE STATEMENT WARNING Read this entire manual and all other publications pertaining to the work to be performed before you in...

Страница 3: ...ratiques de s curit du propri taire ou de l utilisateur NE JAMAIS METTRE EN CHEC OU CONTOURNER LES DISPOSITIFS DE PROTECTION DE VERROUILLAGE OU DE MISE LA TERRE TRADEMARKS All Advanced Energy trademar...

Страница 4: ...g Conditions 1 7 Chapter 2 Product Overview General Description 2 1 Unit Features 2 1 Chapter 3 Specifications Physical Specifications 3 1 Electrical Specifications 3 4 Cooling Specifications 3 8 Envi...

Страница 5: ...3 First Time Operation 5 41 Normal Operation 5 42 Operating Modes 5 42 Full Wave Switch TAKT 5 42 Phase Angle Firing VAR 5 43 Starting Modes 5 43 RAMP Starting Mode 5 43 MOSI Starting Mode 5 43 Setpoi...

Страница 6: ...No Load Current 6 3 Thyristors Are Set To Full Scale 6 4 Other Malfunctions 6 4 AE Global Services 6 5 Primary Contact Information 6 5 Alternate Contact Information 6 5 Returning Units for Repair 6 5...

Страница 7: ...ations 4 4 Table 4 3 9 pin digital I O connector X51 4 6 Table 4 4 9 pin analog I O connector X52 4 7 Table 4 5 16 pin analog digital I O connector X53 or X54 4 7 Table 4 6 16 pin digital I O connecto...

Страница 8: ...50 HF Thyro PX 1PX 690 300 HF 500 HF 5 3 Figure 5 5 Thyro PX 1PX 500 780 HF 1000 HF 1500 HF Thyro PX 1PX 690 780 HF 1400 HF 5 4 Figure 5 6 Thyro PX 1PX 500 2100 HF Thyro PX 1PX 690 2000 HF 5 4 Figure...

Страница 9: ...Figure 5 32 Shield clamp 5 30 Figure 5 33 1PX power controller connections 5 34 Figure 5 34 2PX power controller connections 5 35 Figure 5 35 3PX power controller connections 5 36 Figure 5 36 2PX pri...

Страница 10: ...DANGER DANGER indicates an imminently hazardous situation that if not avoided will result in death or serious injury DANGER is limited to the most extreme situations DANGER DANGER indique une situatio...

Страница 11: ...install and operate the product Rules for Safe Installation and Operation Please note the following rules Do not attempt to install or operate this equipment without proper training Ensure that this...

Страница 12: ...city Note that other connections might have higher requirements than that of the mains connection On or off or Phase Power on standby Hazardous voltage Hazardous voltage Voltage 30 VRMS 42 4 V peak or...

Страница 13: ...ted to United States safety standards UL Recognized to Canadian and United States safety standards UL Recognized to United States safety standards PRODUCT COMPLIANCE The following sections include inf...

Страница 14: ...s unit in an overvoltage category according to environmental specifications You must install and operate this unit with a circuit breaker on the AC input The circuit breaker must be easily accessible...

Страница 15: ...ge peak of ___ kV as shown in the following table Table 1 1 Transient surge suppression device ratings Supply Voltage Phase to Ground Voltage Phase to Phase Voltage Impulse Withstand Voltage Peak Corn...

Страница 16: ...an 0 1 by weight China RoHS People s Republic of China PRC Ministry of Industry and Information Technology MIIT Order 32 China RoHS 2 Management Methods for the Restriction of the Use of Hazardous Sub...

Страница 17: ...erlocks and limiting conditions Mechanism Detection Method Equipment Condition When Interlock is Open By opening the PULSE LOCK jumper the unit is locked Opening the PULSE LOCK jumper or external inte...

Страница 18: ...rturbations are mainly avoided For applications which have to use phase angle firing due to required high dynamic the voltage sequence control VSC mode offers to significantly minimize harmonics by it...

Страница 19: ...control Operating modes TAKT VAR Optional mains load optimization dASM module for applications with multiple power controllers in operating mode TAKT Starting modes MOSI and RAMP Flexible connectivity...

Страница 20: ...nd cables not included USB X6 USB connector and cable not included Analog I O 1 X51 Included 9 pin plug in screw terminal block 30 AWG 14 AWG Analog and digital I O 2 X52 Included 9 pin plug in screw...

Страница 21: ...340 13 4 15 33 0 Figure 5 4 780 HF 1000 HF 1500 HF 242 9 5 787 31 0 505 19 9 35 77 2 Figure 5 5 2100 HF 522 20 5 577 22 7 445 17 5 50 110 2 Figure 5 6 2900 HF 593 23 3 577 22 7 473 18 6 62 136 7 Figur...

Страница 22: ...gure 5 5 2000 HF 522 20 5 577 22 7 445 17 5 50 110 2 Figure 5 6 2600 HF 593 23 3 577 22 7 473 18 6 62 136 7 Figure 5 7 Thyro PX 2PX 80 H 325 12 8 320 12 6 232 9 1 12 26 5 Figure 5 9 200 HF 325 12 8 41...

Страница 23: ...Semiconductor fuse Ground connection Chassis ground near AC connector suitable for ring lug connection Clamp for grounding the control cable shields Load description Resistive load minimum 100 W Resi...

Страница 24: ...rial AgNi Au Table 3 5 Type voltage 500 volts Model Type Current A Type Power kVA Dissipation W Current Transformer T1 Burden R Fuse F1 A Thyro PX 1PX 16 H 8 71 400 1 27 4 50 37 H 18 105 100 1 2 7 50...

Страница 25: ...20 1000 1 1 00 2x700 1000 HF 866 2865 1000 1 1 00 2x1000 1500 HF 1300 3510 1500 1 1 00 4x900 2000 HF 1732 4800 2000 1 1 00 4x1000 2750 HF 2381 6200 3000 1 1 00 4x1500 Thyro PX 3PX 16 H 14 228 400 1 27...

Страница 26: ...6 1900 1500 1 1 0 4x700 2000 HF 1380 3200 2000 1 1 0 4x900 2600 HF 1794 3450 3000 1 1 2 4x1400 Thyro PX 2PX 80 H 95 225 100 1 1 2 100 200 HF 239 485 200 1 1 0 250 300 HF 358 640 300 1 1 0 350 500 HF 5...

Страница 27: ...fan in HF units require a separate power source at 230 V 50 60 Hz A 115 V fan is available by special order for some units Table 3 7 Current derating Air Temperature I IRATED CURRENT A Self Cooling F...

Страница 28: ...350 HF 495 HF 500 HF 650 HF 0 50 0 38 150 67 780 HF 1000 HF 1400 HF 1500 HF 0 55 0 60 580 75 2000 HF 2100 HF 2600 HF 2900 HF 1 00 1 20 2200 81 2PX 200 HF 280 HF 0 50 0 38 200 67 300 HF 350 HF 495 HF 5...

Страница 29: ...device should be rated at twice the specified continuous current ENVIRONMENTAL SPECIFICATIONS The two following tables describe the environmental specifications for the Thyro PX unit Table 3 9 Enviro...

Страница 30: ...humidity when the unit temperature slowly increases or when the unit temperature directly increases from 25 C to 30 C 13 F to 86 F 4 Maximum absolute humidity when the unit temperature directly decre...

Страница 31: ...ed Type Range Designation Features 500 Up to 500 V 690 Up to 690 V 37 Type current 37 A H Integrated semiconductor fuse F Forced air cooling with integrated fan Advanced Energy Thyro PX Power Controll...

Страница 32: ...Figure 4 1 In the simplest case all the setpoint values are added algebraically The prerequisite for a setpoint to influence the total setpoint value is that it must be enabled by the setpoint configu...

Страница 33: ...and limit relays the Thyro Touch display the Thyro Tool Pro software and the optional bus interface The unit signals faults in the power controller or load circuit via the FAULT LED and fault relay K...

Страница 34: ...Pulse lock active FAULT Red Fault present CONTROL 1 Green Blinks at rate proportional to pulse width modulation of power controller 1 Red Power unit 1 hardware failure CONTROL 2 Green Blinks at rate...

Страница 35: ...configuration Though these functions are fully configurable AE recommends not changing the default configuration Table 4 2 Relay indications Relay Name Description K1 Fault relay This relay is normal...

Страница 36: ...onal 16 pin I O ports may be installed in the unit Each I O port line can be reconfigured to serve any function as needed for the application Important This manual describes the default configuration...

Страница 37: ...n digital I O connector X51 Pin Signal Name Function X51 1 24 V X51 2 24 V X51 3 Digital input 1 1 Pulse lock X51 4 Digital input 1 2 Fault acknowledge X51 5 Digital input 1 3 User configured X51 6 Di...

Страница 38: ...24 V X53 2 24 V X53 3 Digital input 2 1 User configured X53 4 Digital input 2 2 User configured X53 5 Digital input 2 3 User configured X53 6 Digital input 2 4 User configured X53 7 Common X53 8 Digi...

Страница 39: ...gured X54 10 Digital input 3 8 User configured X54 11 Digital input 3 9 User configured X54 12 Common X54 13 Digital output 3 1 User configured X54 14 Digital output 3 2 User configured X54 15 Digital...

Страница 40: ...ry power supply input Figure 4 5 Bottom I O connectors Table 4 7 Relay K1 K2 and K3 connectors X21 X22 X23 Pin Function 1 Common 2 Normally closed 3 Normally open Table 4 8 AC auxiliary power supply i...

Страница 41: ...to the Thyro PX power controller For additional module documentation follow the link in the table below Table 4 10 Module documentation links Anybus Module Link Anybus PROFIBUS DPV1 https www advanced...

Страница 42: ...RO TOUCH DISPLAY The Thyro Touch display is an optional accessory for the parameterization and visualization of measured values such as current voltage power and setpoint Advanced Energy Thyro PX Powe...

Страница 43: ...ireless communication The Thyro PX power controller provides a communications interface through the X10 port This interface allows you to monitor and control the unit through an optional touch display...

Страница 44: ...lay it shows the information determined by the start screen configuration The Thyro Touch display allows you to access menus and to make menu selections When a menu selection causes the display to sho...

Страница 45: ...dowsService and client are installed The server and client start in parallel when the software is started Figure 4 8 Connection to local installed server The left side of the window offers a file expl...

Страница 46: ...message Figure 4 11 Separate status message window You can rearrange the tabs within the window to appear as a Horizontal tab group Vertical tab group Separate window To change to a horizontal or vert...

Страница 47: ...e connected before and after the software is started Important The first time the specific USB port is connected the computer must configure the port and load the device driver This will take up to se...

Страница 48: ...y the current available data and event messages Data Logger to record messages with time stamp Diagrams to show time stamped data as characteristic lines The thyro files include parameters time data l...

Страница 49: ...he save icon to save the changed value Click the save as icon to save parameters to your computer as a thyro file To transfer a local file to the device the device must be connected and the relevant t...

Страница 50: ...r the precise value of each field can be seen without any limitations This is of particular importance to control parameters Figure 4 18 Numeric field parameter With check box parameters a list of pos...

Страница 51: ...bottom of the unit and the bottom of the cabinet or any other object is 100 mm 4 The minimum distance between the top of the unit and the top of the cabinet or any other object is 150 mm 6 The minimum...

Страница 52: ...ure 5 1 Thyro PX 1PX 500 16 H 37 H 75 H 110 H M10 Figure 5 2 Thyro PX 1PX 500 130 H 170 H Thyro PX 1PX 690 80 H Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Operation...

Страница 53: ...yro PX 1PX 500 280 HF Thyro PX 1PX 690 200 HF Figure 5 4 Thyro PX 1PX 500 350 HF 495 HF 650 HF Thyro PX 1PX 690 300 HF 500 HF Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup...

Страница 54: ...X 1PX 500 780 HF 1000 HF 1500 HF Thyro PX 1PX 690 780 HF 1400 HF Figure 5 6 Thyro PX 1PX 500 2100 HF Thyro PX 1PX 690 2000 HF Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup...

Страница 55: ...Figure 5 7 Thyro PX 1PX 500 2900HF Thyro PX 1PX 690 2600 HF Figure 5 8 Thyro PX 2PX 500 16 H 37 H 75 H 110 H Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Operation 5 5...

Страница 56: ...9 Thyro PX 2PX 500 130 H 170 H Thyro PX 2PX 690 80 H M10 Figure 5 10 Thyro PX 2PX 500 280 HF Thyro PX 2PX 690 200 HF Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Opera...

Страница 57: ...350HF 495 HF 650 HF Thyro PX 2PX 690 300 HF 500 HF Figure 5 12 Thyro PX 2PX 500 780 HF 1000 HF 1500 HF Thyro PX 2PX 690 780 HF 1400 HF Advanced Energy Thyro PX Power Controller 57010148 00G Installat...

Страница 58: ...13 Thyro PX 2PX 500 2000 HF Thyro PX 2PX 690 1850 HF Figure 5 14 Thyro PX 2PX 500 2750 HF Thyro PX 2PX 690 2400 HF Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Operat...

Страница 59: ...re 5 15 Thyro PX 3PX 500 16 H 37 H 75 H 110 H M10 Figure 5 16 Thyro PX 3PX 500 130 H 170 H Thyro PX 3PX 690 80 H Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Operation...

Страница 60: ...M10 Figure 5 17 Thyro PX 3PX 500 280 HF Thyro PX 3PX 690 200 HF Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Operation 5 10...

Страница 61: ...Figure 5 18 Thyro PX 3PX 500 350HF 495 HF 650 HF Thyro PX 3PX 690 300 HF 500 HF Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Operation 5 11...

Страница 62: ...Figure 5 19 Thyro PX 3PX 500 780 HF 1000 HF 1500 HF Thyro PX 3PX 690 780 HF 1400 HF Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Operation 5 12...

Страница 63: ...20 Thyro PX 3PX 500 1850 HF Thyro PX 3PX 690 1700 HF Figure 5 21 Thyro PX 3PX 500 2600 HF Thyro PX 3PX 690 2200 HF Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Operat...

Страница 64: ...r installer ou d panner des quipements lectriques haute nergie Des tensions potentiellement l tales peuvent entra ner le d c s des blessures ou des dommages l quipement Assurez vous de prendre toutes...

Страница 65: ...tiqueter toutes les sources de puissance d entr e avant de travailler sur cet appareil ou sur tout l ment qui y est raccord The optional modules may be shipped separately 1 Verify that the unit is di...

Страница 66: ...ei com en anybus_ethercat html Anybus Modbus TCP http www aei com en anybus_modbus_tcp html Anybus Modbus RTU http www aei com en anybus_modbus_rtu html If an Anybus module must be removed from the un...

Страница 67: ...the unit remove the TORX T8 mounting screws insert a connector and pull while moving the module from side to side as shown in the following figure Figure 5 23 I O module removal Advanced Energy Thyro...

Страница 68: ...entiellement l tales peuvent entra ner le d c s des blessures ou des dommages l quipement Assurez vous de prendre toutes les pr cautions de s curit appropri es WARNING These servicing instructions are...

Страница 69: ...ted to another phase For example if the unit is connected to phase 1 then phase 2 phase 3 or neutral are used as the reference phase 10 Connect X51 4 and X51 5 to terminal X51 2 11 Install the covers...

Страница 70: ...uration To convert a 3 phase unit see Figure 5 25 To convert a 2 phase unit see Figure 5 26 The wiring changes are shown as bold lines Advanced Energy Thyro PX Power Controller 57010148 00G Installati...

Страница 71: ...I O control connections Common AO 1 3 output PC 3 AO 1 2 output PC 2 AO 1 1 output PC 1 Common AI 1 3 setpoint PC 3 AI 1 2 setpoint PC 2 AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 u...

Страница 72: ...int PC 2 AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pulse...

Страница 73: ...mmages l quipement Assurez vous de prendre toutes les pr cautions de s curit appropri es WARNING These servicing instructions are for use by qualified personnel only To reduce the risk of electric sho...

Страница 74: ...e de VSC la tension de l alimentation secteur est lev e sur les sorties du contr leur de puissance inactive indiqu par dans l illustration suivante Le transformateur doit tre con u de fa on ce que la...

Страница 75: ...a 3 phase unit to VSC 3 see Figure 5 30 The wiring changes are shown as bold lines 8 For VSC 2 units a Connect A1 X1 5 to A5 X1 3 b Connect A1 X1 6 to A5 X1 2 To convert a 2 phase unit to VSC 2 see Fi...

Страница 76: ...the appropriate VSC configuration from the drop down list 5 Click the save icon Figure 5 29 Software configuration Advanced Energy Thyro PX Power Controller 57010148 00G Installation Setup and Operat...

Страница 77: ...tpoint PC 2 AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pul...

Страница 78: ...tpoint PC 2 AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pul...

Страница 79: ...mensions sont conformes aux exigences applicables Make a suitable chassis ground connection to the location specified on the dimensional drawing See Dimensional Drawings on page 5 1 Connecting I O and...

Страница 80: ...d between 0 14 mm2 and 1 5 mm2 30 AWG and 14 AWG 2 Prepare the end of the control cable a Strip 50 mm 2 of the cable jacket b Expose the cable shield for connection to the shield clamp c Strip 7 mm 0...

Страница 81: ...e can exceed the maximum input voltage damaging the unit In this case an optional 690 V snubber board part number 2000003203 must be connected to each output One snubber board is required for 1 phase...

Страница 82: ...make this connection Follow the torque recommendation for M2 terminal screws 8 Reinstall the plastic cover s removed for step 1 Table 5 2 Terminal screw size Model Connector Screw Protective Earth Scr...

Страница 83: ...SQUE DE MORT OU DE BLESSURES D brancher et verrouiller tiqueter toutes les sources de puissance d entr e avant de travailler sur cet appareil ou sur tout l ment qui y est raccord WARNING More than one...

Страница 84: ...int PC 2 AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pulse...

Страница 85: ...int PC 2 AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pulse...

Страница 86: ...setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pulse lock to 24 V An...

Страница 87: ...2 AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pulse lock to...

Страница 88: ...2 AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pulse lock to...

Страница 89: ...AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pulse lock to...

Страница 90: ...AI 1 1 setpoint PC 1 5 V Common DI 1 6 user configured DI 1 5 user configured DI 1 4 user configured DI 1 3 user configured DI 1 2 fault acknowledge DI 1 1 pulse lock 24 V 24 V Connect pulse lock to...

Страница 91: ...f diagnostics If the unit detects an error the unit sets the respective fault bits and lights the FAULT LED or the light green ON READY LED if the fault is severe You will not be able to apply power t...

Страница 92: ...ative OPERATING MODES Full Wave Switch TAKT In full switch mode whole multiples of the mains periods are always switched and harmonics are minimized The mains are switched on off depending on the pres...

Страница 93: ...rating Modes on page 5 42 MOSI Starting Mode The MOSI starting mode is used for sensitive heating materials with a high Rwarm Rcold ratio such as molybdenum disilicide The power controller limits the...

Страница 94: ...sed by default Switching between the local setpoint and the remote setpoint can be controlled using the Thyro Touch display the Thyro Tool Pro software or the bus communication A digital I O line may...

Страница 95: ...ould be familiar with the application and with the operating characteristics of the load Controlled Value The controlled value effect on the load is proportional to the total setpoint depending on the...

Страница 96: ...maller IRMSmax Pmax I IRMSmax Smaller Smaller Larger Larger URMSm ax Pmax I2 IRMSmax Smaller Smaller Larger Larger URMSm ax Pmax P Pmax Smaller Larger Larger Smaller URMSm ax IRMSmax Without control L...

Страница 97: ...ditions Symbol Description UMainMin Minimum mains voltage UMainMax Maximum mains voltage Ueff_Min Minimum rms voltage Ueff_Max Maximum rms voltage U_min Minimum rectified voltage average of the absolu...

Страница 98: ...tance Monitoring Absolute value monitoring lends itself to one or more load resistances organized in parallel or in series Generally the effective load resistance value measured is continuously compar...

Страница 99: ...cations Simple dASM wiring with shielded RJ 45 patch cables Ethernet CAT 5 8 pole with a cable length between two power controllers of up to 100 m 328 depending on surrounding conditions Simple parame...

Страница 100: ...the same TAKT cycle period for all power controller devices Verify these parameters on the master unit dASM NO OF DEVICES dASM POWER THRESHOLD W Start up each unit in the dASM group dASM Notification...

Страница 101: ...ow operates as a master only for units 1 to 6 and displays that an incorrect number of units are present in the dASM network MAINTENANCE Fan Maintenance The fan is subject to wear Complete the followi...

Страница 102: ...ance d entr e avant de travailler sur cet appareil ou sur tout l ment qui y est raccord DANGER Personnel must receive proper training before installing or troubleshooting high energy electrical equipm...

Страница 103: ...is limited but not shut off 1 Disable the output 2 Verify that the limitation setting is correct 3 Verify that the unit load and load connections are correct Is the FAULT LED lit If yes The unit has d...

Страница 104: ...stomer supplied power supply for the A70 control device is missing Check that the voltage at terminal X1 1 and X1 2 of the A70 control device is within the range 90 VAC to 265 VAC or that X3 1 and X3...

Страница 105: ...analog inputs Verify that parameters Ts Uemin Iemin and Pmin are 0 Controller parameters Ti and Kp are set too small Parameters Iemax Uemax and Pmax are set too large or the load current is too small...

Страница 106: ...o the Advanced Energy website then use one of the following Phone 24 hrs day 7 days week 800 446 9167 or 1 970 221 0108 Email We will respond to email by the next business day mailto technical support...

Страница 107: ...tion call will allow AE Global Services to determine if the unit must actually be returned for the problem to be corrected Such technical consultation is always available at no charge Advanced Energy...

Страница 108: ...nce 5 51 features 2 1 G general description 2 1 Global Services contact information 6 5 grounding 5 29 guidelines safety 1 2 I icons in user manual 1 1 on unit 1 2 industry guidelines compliance with...

Страница 109: ...irectives and standards 1 5 starting modes 5 43 status indicators LEDs 4 2 relays 4 4 symbols in user manual 1 1 on unit 1 2 T touch display accessing the main menu 4 13 features 4 11 menus 4 13 troub...

Отзывы: