Initial operating check

The 0400MAN damper should only be commissioned once the installation has been completed. 

The damper should be inspected thoroughly to ensure that it is clean and free of any internal debris before 

the damper actuation is tested as per the following instructions;
• 

Remove the access door.

• 

 To operate the damper the thermal fuse must be unscrewed, then turn the handle anticlockwise until 

it is in the open position, as shown on the label.

• 

 The damper blade is under tension from a spring so the handle must be held in position whilst the 

thermal fuse is re-tightened, the blade will hold in the open position.

• 

 To ensure the damper is operating correctly the damper should be tested by first checking that there 

are no obstructions to the handle and that it is free to move. Then unscrew the thermal fuse quickly, 

this will release the blade to its closed position.

• 

 Check that the blade is in the closed position by checking that the handle is in line with the close 

position on the label.

• 

 If everything is satisfactory then reset the damper to its correct position, either fully open or if it is to 

balance air then this can be done so long as the damper remains at least 50% open.

• 

 Re-fit the access door.

• 

 If the damper has not closed, the blade may have been incorrectly positioned, or the damper may be 

faulty. Please contact Advanced Air for advice.

Maintenance

0400MAN dampers are installed as a life safety product and it is essential that they are always maintained in 

good, clean working condition. In accordance with BS9999 Annex W.1 maintenance and inspection should 

be undertaken annually.
Maintain the dampers as follows;
• 

Mark the handle position on the label so that it can be reset to the same position after testing.

• 

Remove the access door.

• 

Visually inspect all damper components for signs of corrosion, obstructions and build-up of dirt/dust.

• 

Remove any obstructions, wipe away all dirt/dust from the damper blades and duct surfaces.

• 

After internal inspections are complete a functional check of the damper should be made.

• 

Test the damper by unscrewing the thermal fuse quickly, check that the reaches its closed position.

• 

Reset the damper to its original position and re-tighten the fusible link.

• 

 If there is a requirement to change the thermal fuse this can be done simply by unscrewing it fully from 

the case and replacing with a new one. The thermal fuse should be replaced if it has been activated, 

damaged or part of a regular service plan.

• 

Refit the access door and complete inspection reports as appropriate.

0400MAN – OPERATION AND MAINTENANCE

The damper is fully closed 

when the handle is rotated 

to the ‘Close’ position.

Thermal fuse

The damper is fully open 

when the handle is rotated 

to the ‘Open’ position.

Содержание AIR CONTROL 0400FME

Страница 1: ...0400_IOM_1 1_Mar21_1 1 AIR CONTROL INSTALLATION OPERATION AND MAINTENANCE MANUAL MODEL 0400 FIRE DAMPER...

Страница 2: ...er Model 0400MAN Two hour flexible wall 4 Two hour rigid wall 5 Circular fire damper Model 0400FME Two hour flexible wall 6 Two hour rigid wall 7 Operation and Maintenance Model 0400MAN 8 Model 0400FM...

Страница 3: ...luded within this manual an example of the Fire Damper Certificate DW145 Inspection and Handover Check Sheet which is to be completed by the installer A separate certificate is required per damper The...

Страница 4: ...it and pushed into place All cut edges must be sealed with a fire batt sealant to BS EN 13501 2 A fire rated intumescent mastic to BS EN 13501 2 shall be applied to each joint 7 The galvanised mild st...

Страница 5: ...l be applied to each joint 6 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm leaving a 10mm clearance for any duct expansion in a fire situation 7 The galvan...

Страница 6: ...cent mastic to BS EN 13501 2 shall be applied to each joint 7 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm leaving a 10mm clearance for any duct expansion...

Страница 7: ...30mm leaving a 10mm clearance for any duct expansion in a fire situation 7 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild steel ductwork sealer and fix...

Страница 8: ...blade may have been incorrectly positioned or the damper may be faulty Please contact Advanced Air for advice Maintenance 0400MAN dampers are installed as a life safety product and it is essential tha...

Страница 9: ...ion For other faults contact Advanced Air Sales Office Complete any relevant reports Maintenance 0400FME dampers are installed as a life safety product and it is essential that they are always maintai...

Страница 10: ...5 6 7 8 G PRODUCTS DMP 0400 Series 02 Drawings D0400 ES Electrical Schematics D0400 ES001 Wiring diagram fire smoke damper actuator D0400 ES001 rev B Wiring diagram 0400 FME dwg Wiring detail for dam...

Страница 11: ...o damper also through ceiling void and adjacent services 7 Confirm the space around the damper has not been used for the passage of other services The presence of other services will invalidate the in...

Отзывы: