background image

0160_IOM_1.2_Mar21_6

6

FIRE – 0160 MULTI-SECTION ADJUSTABLE FRAME SYSTEM FOR FLEXIBLE SUPPORTING CONSTRUCTION

Patented Adjustable Frame System

(AFS) incorporating bracket, bracket

slot, and Z-piece

(Patent No: GB2557865)

0160 Series fire damper

AFS bracket, bracket slot,

and Z-piece

M10 drop rods

AFS rails

Access door for

inspection / damper reset

15mm thick gypsum boards

Two hour rated flexible supporting

construction to BS EN 1363-1:2020

Steel stud depth – 71 to 100mm

0160 Series fire damper

Spigot infills

Fire batt

Installation sequence

 The drywall will consist of two layers of 15mm plasterboard each side of steel studwork with an 

optional mineral wool insulation. The opening will be a letterbox construction with overlapping layers 

of plasterboard with an opening clearance around the damper casing in line with the above table.

 Two M10 drop rods per fire damper shall be fitted on both sides of the drywall. These should be 

securely installed in line with the manufacturer’s fixing instructions in a position to match the AFS rail.

 The drop rods should have a nut screwed on for clamping the rail from above. These rods will be 

secured to the two top AFS rails.

 Slide the AFS rails in all the brackets and insert the “Z” piece into the bracket slot pushing it up against 

the underside of the rail. Insert the 8mm bolt from above into the slot through the “Z” piece fitting the 

nut until tight to secure the rail.

Additional drop rods should then be passed through the top and bottom rails and fully tightened.

 The damper should be mounted centrally in the opening flush with the wall on one side. The anchored 

drop rods are to slide through the top rails and nuts are screwed on to take the support. The damper must 

then be levelled and when in the correct position the nut above the rail should be tightened against the rail.

10 

 The galvanised mild steel ductwork connecting to the damper spigots must overlap by up to 40mm, 

leaving a minimum 10mm clearance for any duct expansion in a fire situation. 

11 

 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild 

steel ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at 

high temperature allowing the duct to break away without effecting the integrity of the installation.

12 

 The connecting galvanised mild steel ductwork must be independently supported within one metre of 

the connections and have been installed in accordance with DW144.

13 

 The gap between the damper and the wall opening will need filling with two layers of 50mm thick 

140kg/m3 fire batt cut to an interference fit and pushed in to place. All cut edges must be sealed with 

a firebatt sealant to BS EN 13501-2. A fire rated intumescent mastic (to BS EN 13501-2) shall be applied 

to each joint.

14 

 An access door should be fitted on the access side of the damper to enable the resetting of the 

damper blades.

15 

 When the damper installation has been completed checks should be made to ensure the AFS rails are 

secured to the damper and there is no movement, operation of the damper should be checked.

16 

 Complete DW145 Fire Damper Certificate.

Preparation

 Ensure that the damper is kept 

in a clean dry environment and 

that there is no damage to the 

damper.

 Remove all the packaging and 

transit ties before installation.

 Work out the opening size to be 

cut using the adjacent table.

Nom. duct width

Opening width min.

Opening width max.

1001-2,000mm

Nom. duct +194mm

Nom. duct +350mm

Nom. duct height Opening height min. Opening height max.

1001-1146mm

Nom. duct +150mm

Nom. duct +400mm

1147-1521mm

Nom. duct +175mm

Nom. duct +425mm

1552-1996mm

Nom. duct +200mm

Nom. duct +450mm

1997-2000mm

Nom. duct +225mm

Nom. duct +475mm

PRODUCT  

0160 MULTISECTION W/AFS

APPLICATION  

FLEXIBLE SUPPORTING CONSTRUCTION

CLASSIFICATION REPORT NO.  

TBA

CLASSIFICATION  

E120 (VE I 



 O)

TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING. 

While we have tested a damper 2,000 x 2,000mm, larger sizes can be supplied but the installation will need to be checked by a 

competent structural engineer as stated in the Extended Fields of Application BS EN 15882-2:2015. With all larger sizes there should 

be a risk assessment carried out and a full method statement documented to ensure the correct lifting gear and safety precautions 

are put in place prior to the installation being carried out.

Содержание 0160 Series

Страница 1: ...0160_IOM_1 2_Mar21_1 1 MODEL 0160 FIRE DAMPER AIR CONTROL INSTALLATION OPERATION AND MAINTENANCE MANUAL...

Страница 2: ...all AFS with drop rods in wall 5 Two hour flexible wall multi section AFS with drop rods two sides 6 Two hour rigid wall AFS with drop rods one side 7 Two hour rigid wall HEVAC 8 Two hour flexible wal...

Страница 3: ...luded within this manual an example of the Fire Damper Certificate DW145 Inspection and Handover Check Sheet which is to be completed by the installer A separate certificate is required per damper The...

Страница 4: ...for any duct expansion in a fire situation 10 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild steel ductwork sealer and fixed with low resistance fixings...

Страница 5: ...to the slot through the Z piece fitting the nut until tight to secure the rail 8 The damper should be mounted centrally in the opening as detailed in the drawing The drop rods are to slide through the...

Страница 6: ...ork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at high temperature allowing the duct to break away without effecting the integrity of the installation 12 The...

Страница 7: ...et slot pushing it up against the underside of the rail Insert the 8mm bolt from above into the slot through the Z piece fitting the nut until tight to secure the rail 7 The damper should be centrally...

Страница 8: ...ture allowing the duct to break away with affecting the integrity of the installation 11 The connecting galvanised mild steel ductwork must be independently supported within one metre of the connectio...

Страница 9: ...l ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at high temperature allowing the duct to break away without effecting the integrity of the installation...

Страница 10: ...tend past the opening on each side by 100mm 5 Position the dampers evenly in the centre of the opening 6 Secure the angles to the floor Mark the hole positions on the angle at least 50mm away from the...

Страница 11: ...nised mild steel ductwork connecting to the damper spigots must overlap by up to 40mm leaving minimum 10mm clearance for any duct expansion in a fire situation 12 The galvanised mild steel ductwork co...

Страница 12: ...the blades and spring system 0160 OPERATION AND MAINTENANCE Visually inspect the damper blades to ensure that they are all interlocked that the springs are straight and that the bottom damper is lock...

Страница 13: ...o damper also through ceiling void and adjacent services 7 Confirm the space around the damper has not been used for the passage of other services The presence of other services will invalidate the in...

Отзывы: