a row collectors, for systems with more than one row. 
Use one (1) for each additional row after the first. 

 

(5) 

Row  Spacer  Kit,  Part  no.  18004-1

  contains 

additional hold-down hardware and connecting parts 
and adapters needed if collectors must be separated 
bya  space due to roof obstructions, such as a chimney 
or  roof  vent.  Use  one  (1)  for  each  gap  between 
collectors. 
 
 

 

(6) 

Hold-Down Strap, Part No. 16007-1, -3 

Polypropylene fabric strap, 5/8” wide, 100, or 300 ft. 
long. 

 

(7) 

Header  Inserts  Part  No.  50055-1 

are  used  in 

special  situations  where  unusually  high  stagnation 
temperatures are expected, such as in desert climate, 
or  where  abnormally  high  system  pressures  may 
occur. Use four (4) inserts per panel. 

 

SECTION 2: INSTALLATION GUIDE 
 
Step 1: Check Water Flow 

 
Under normal conditions the existing filtration pump 
has adequate flow and head pressure to circulate the 
pool water through the POLY PRO system without 
significant reduction in flow. However, verifying the 
flow rates ensures satisfactory system operation. 

 
 
 
 
 
 
 
 
 

Содержание 16004-10

Страница 1: ...oyment First you should thoroughly plan the proposed system before installation Section One of this manual explains and illustrates the required kits and components Section Two provides detailed instr...

Страница 2: ...ordered separately Use one 1 kit for each collector 2 System Kit Part No 18002 1 Contains additional hold down hardware and connecting parts and adapters needed to complete water connection from the...

Страница 3: ...Polypropylene fabric strap 5 8 wide 100 or 300 ft long 7 Header Inserts Part No 50055 1 are used in special situations where unusually high stagnation temperatures are expected such as in desert clima...

Страница 4: ...installed in some cases Select appropriate pipe size for the system supplyand return lines The headers of the POLY PRO collectors are 2 and the pipe adapters included in the kits connect to 2 PVC Sch...

Страница 5: ...sharp utility knife cut through the weld while pulling the two plates apart Lay the collector over the vent pipe keeping the vent pipe at least 12 inches away from a header It will be easier to compl...

Страница 6: ...not install the hold down brackets until the collectors are in place 5 bring the first collector to the roof and slip the proper hoses over both end of the inlet and outlet headers on the last return...

Страница 7: ...the vacuum relief valve in the outlet header of each row This will be located at the opposite end of the row that is connected to the collector outlet pipe Refer to Figures 4 and 12 12 Install an end...

Страница 8: ...manufacturer s instructions included with the automatic equipment you use Other Equipment Some pools employ an automatic pool cleaner This should be plumbed before the control valve to assure positive...

Страница 9: ...d one 1 Referring to the figure below locate the tube to be isolated End tube has been shown for clarity Using a sharp utility knife very carefully cut away approximately 1 of the tube at both headers...

Отзывы: