background image

INST

PIPEWORK

ALLATION

The unit must be installed to meet current best practice by a person
competent to do so.

Incoming mains of 22mm with a pressure of 2 bar or above is recommended
for best performance. Lesser pressures/pipe diameters will compromise
performance; this must be taken into account as the decision rests with the
installer/householder.

Incoming pressures of more than 3 bar must be controlled at 3 bar by a
pressure reducing valve (Not supplied).

In hard water areas where concentrations exceed 200ppm a suitable scale
reducer must be installed.  The choice is left to the installer to suit local
conditions. Chlorine levels must be below 200ppm.

If the cold service to the ballcock in the cold section is turned off or 
disconnected it will not be necessary to fit an overflow, make sure that 
the cold section has a 50mm depth of water. Cap the overflow connection
with a 22mm push-fit or compression end stop to prevent evaporation.
For additional protection a float switch can be used connected to a
motorised two port valve on the cold inlet.  This is available as a kit from
Advance - please ask for AA0300.

If the overflow is connected it must be in line with current practice.
A metal overflow should be fitted. Push fit or solvent weld are not
recommended. Discharge must be to a safe point. We also recommend
that the ball valve is isolated even if an overflow is fitted.

Inhibitor must be added via the top of the store to manufacturers’
recommended dosage.

Pipe outside diameter

Maximum heat loss in W/m

In order to comply with Part L Building Regulations it is necessary to
insulate any hot water (primary and secondary) pipework within one metre
of the cylinder. Guidance is given in the Table 5 (Page 20) of the 2013
Domestic Heating Compliance guide. Insulation values for the most popular
pipe sizes are reproduced below.

15
22
28
35

7.89
9.12

10.07
11.08

947219 ADVANCE APPLIANCES 8pp A5_Layout 1  10/11/2015  14:41  Page 4

Содержание ETS 160

Страница 1: ...AND USER GUIDE ADVANCE ELECTRIC THERMAL STORE ETS 160 ADVANCE APPLIANCES LTD PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE ISSUE 4 0214 ISSUE 6 1115 947219 ADVANCE APPLIANCES 8pp A5_La...

Страница 2: ...Section Vent and Water Level Indicator Temperature Gauge BlendingValve ServiceValve 2 L Expansion Vessel Hot Out 3kw Immersion Heater 3kw Immersion Heater Hot Water Coil Cold In Drain 947219 ADVANCE A...

Страница 3: ...ng without a pump and fast bath filling The unit can be fitted and left isolated from the filling point if it is not possible to fit an overflow The blending valve can be orientated to right or left h...

Страница 4: ...nnection with a 22mm push fit or compression end stop to prevent evaporation For additional protection a float switch can be used connected to a motorised two port valve on the cold inlet This is avai...

Страница 5: ...ree life however they should be serviced periodically Advance recommends a service at least every two years It is important that the store temperature is maintained It is critical that the water level...

Страница 6: ...ine with any regulations ruling at the time Conditions apply the unit must be serviced annually and a record of service must be maintained It must be in a frost free environment and must be used for p...

Страница 7: ...947219 ADVANCE APPLIANCES 8pp A5_Layout 1 10 11 2015 14 41 Page 7...

Страница 8: ...ly products that meet or exceed appropriate standards and building and water regulations To provide pre and post sales technical support To provide clear and concise warranty details to customers UNIT...

Отзывы: