Issue 4, August 2004

    3

Figure 2.  NIU3 Circuit Diagram

Figure 3.  NIU3 3-Slot Shelf Rear Panel

Power

Fully populated, the NIU3 3-Slot Shelf operates on 
local –48 VDC at 0.375 amps maximum, or ±24 VDC 
at .750 amps maximum. The shelf backplane has spade 
lug terminal connections (

TB1

) for both an “A-side” 

and “B-side” independent DC source, plus Frame 
Ground (see 

Figure 4

). 

Figure 4.  Local DC Power Connection

WARNING

Ensure power is off and tagged out-of-service
before making power wiring connections.

Use one of the following requirements for powering the 
unit locally:

1. Connect to a grounded 

48 VDC source, electri-

cally isolated from the AC source. Provide branch 
circuit overcurrent protection with a fuse or circuit 
breaker, minimum 48 VDC, maximum 15 amps. 
Provide an easily accessed approved and rated 
disconnect device in the field wiring.

2. Connect to an approved Class 2 Type (LPS) power 

supply rated 48 VDC, maximum 240 VA.

For those slots not populated with an NIU3 circuit card, 
blank covers (P/N 1212076L1) must be installed.

The following terminal connections are made:

1. Connect –48 V or ±24 V local supply to 

PWR A

.

2. Connect the associated return wire to 

RET A

.

3. If redundant power is intended, make similar 

connections to 

PWR B

 and 

RET B

.

CAUTION

Terminate grounds to an approved ground
location. Check metal-to-metal contact on all
ground connections. Verify ground circuit
continuity.

4. Connect the common frame ground terminal or 

ground lug (6 AWG max.) to an approved ground 
location.

CAUTION

Per GR-1089-CORE, October 2002, Section 9,
this system is designed and intended for
installation in a DC-C (common) bonding and
grounding system only. It is not intended or
designed for installation in a DC-I (isolated)
bonding and grounding system.

Independent Power Supply

An optional independent power supply unit is available. 
The Power Supply/Rectifier (PS/R), P/N 1212080L1, 
provides –54V at 2 A. The PS/R plugs into a standard 

SLOT 2

SLOT 3

P7

P8

P4

P3

COM NC NO

DC POWER

SLOT 1

PWR

B

RET

B

RET

A

PWR

A

P2

P1

48V

, 375MA / 24V

, 750MA

USE COPPER CONDUCTORS ONLY.

 

 

 

 

 

 

CERT.TO CAN/CSA STD.

C22.E NO.225-950

CONF TO ANSI/UL

STD 1950

IN

NIU3

1212073L2

OUT

CUST

NTWK

3

IN

OUT

CUST

NTWK

2

IN

OUT

CUST

NTWK

1

THIS UNIT MAY BE POWERED

BY MULTIPLE SOURCES.

DISCONNECT ALL SOURCES

PRIOR TO SERVICING.

REFER TO INSTALLATION

INSTRUCTIONS BEFORE

CONNECTING POWER.

PWR

B

RET

B

RET

A

PWR

A

B

Supply

B

Return

Frame

Ground

A

Return

A

Supply

TB1

Содержание DS3 NIU3

Страница 1: ...he backplane circuitry is protected by a metal cover that has openings for BNC data jacks pass through relays power terminal connections and alarm pins Removable covers provide security for power and alarm connections and pass through and alarm relays All connections are clearly labeled Features The NIU3 3 Slot Shelf provides the following features and functions Field replaceable pass through rela...

Страница 2: ...212078L1WM accommo dates a stack of two 3 Slot Chassis Six x inch bladed hex head screws and flat washers are provided with the 1212078L1WM wallmount bracket for attaching to the wall In this configuration the original flanges are removed and the wallmount flanges are installed using the countersink screws from the originals If using P N 1212073L1WM install the chassis so the circuit cards front p...

Страница 3: ... local supply to PWR A 2 Connect the associated return wire to RET A 3 If redundant power is intended make similar connections to PWR B and RET B CAUTION Terminate grounds to an approved ground location Check metal to metal contact on all ground connections Verify ground circuit continuity 4 Connect the common frame ground terminal or ground lug 6 AWG max to an approved ground location CAUTION Per...

Страница 4: ... standards 2 Install all protective shields and panels that were removed for wiring installation 3 Provide power to the backplane 5 TURNUP When an NIU3 is inserted into a shelf with power on the backplane the STATUS LED turns on red while the NIU3 performs a self test If the test passes the STATUS LED turns on green and the other LEDs go through an on off sequence indicating the NIU3 is online If ...

Страница 5: ...cent to the alarm wire wrap pins on the backplane The alarm relay output responds to the card malfunction status on individual NIU3 cards If an alarm condition occurs but an alarm signal is not present then a failed alarm relay is indicated Follow this procedure to replace a failed alarm relay 1 Using an appropriately sized IC extractor tool lift the relay off its socket 2 Align and insert the rep...

Страница 6: ...es support CAPS requests or further information ADTRAN Sales Pricing Availability 800 827 0807 ADTRAN Technical Support Pre Sales Applications Post Sales Technical Assistance 800 726 8663 Standard hours Monday Friday 7 a m 7 p m CST Emergency hours 7 days week 24 hours day ADTRAN Repair CAPS Return for Repair Upgrade 256 963 8722 Repair and Return Address Contact Customer and Product Service CAPS ...

Отзывы: