C A U T I O N
C A U T I O N !
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
Warranty
: ADTRAN will replace or repair this product within the warranty period if it does not
meet its published specifications or fails while in service. Warranty information can
be found online at
©2008 ADTRAN, Inc. All Rights Reserved.
PRICING AND AVAILABILITY 800.827.0807
TECHNICAL SUPPORT 800.726.8663
RETURN FOR REPAIR 256.963.8722
*61442820G1-22B*
The SFP is a Class 1 Laser Product and complies with the
Laser Safety requirements of FDA 21CFR 1040.10 and
1040.11, and EN60825-1 and -2. The SFP is NRTL Listed
and CB Certified to all applicable American and European
safety standards.
♦
Per GR-1089-CORE the ADTRAN system that the SFP is
being deployed in is designed and intended for
installation as part of a Common Bonding Network
(CBN). The ADTRAN system that the SFP is being
deployed in is not designed nor intended for installation
as part of an Isolated Bonding Network (IBN).
♦
Per GR-1089-CORE Section 9, the SFP does not have an
internal DC connection between battery return and
frame ground. The SFP can be installed in a DC-I
( i s o l a t e d ) o r D C - C ( c o m m o n ) i n s t a l l a t i o n . F o r
installations where other cards or the host system have
internal connections between battery return and frame
ground, the system would be intended for deployment
only in a DC-C installation.
♦
The ADTRAN system chassis frame ground terminal
must be connected to a reliable earth ground to ensure
that the metal enclosure of the SFP is properly grounded
via the backplane connector.
NOTE
3.125 Gigabit Ethernet port(s) are optical and therefore are
not classified as any type of port as defined in Appendix B
of GR-1089-CORE Issue 4.
ETSI EN
The SFP is designed to meet the following environmental
classes:
♦
ETSI EN 300 019-1-1 “Classification of environmental
conditions; Storage,” Class 1.2
♦
ETSI EN 300 019-1-2 “Classification of environmental
conditions, Transportation,” Class 2.3
♦
ETSI EN 300 019-1-3 “Classification of environmental
conditions, Stationary use at weather-protected
locations,” Class 3.3
The equipment is designed to function without degradation