NOTE: The Gigabit Ethernet port(s) are optical and 

therefore are not classified as any type of port as 

defined in Appendix B of GR-1089-CORE Issue 4.

The SFP is designed to meet the following environmental 

classes:

ETSI EN 300 019-1-1 “Classification of 

environmental conditions; Storage,” Class 1.2

ETSI EN 300 019-1-2 “Classification of 

environmental conditions, Transportation,” Class 2.3

ETSI EN 300 019-1-3 “Classification of 

environmental conditions, Stationary use at weather-

protected locations,” Class 3.3

The equipment is designed to function without degra-

dation during exposure to all test severities per Class 3.3.

COMPLIANCE

CAUTION: Electrostatic Discharge (ESD) can damage 

electronic modules. When handling modules, 

wear an antistatic discharge wrist strap to 

prevent damage to electronic components. Place 

modules in antistatic packing material when 

transporting or storing. When working on 

modules, always place them on an approved 

antistatic mat that is electrically grounded.

The SFP is NRTL Listed to the applicable UL 

standards. The SFP meets or exceeds all the 

applicable requirements of NEBS, Telcordia

GR-63-CORE, and GR-1089-CORE. The SFP is 

intended for deployment in Central Office type 

facilities, EEEs, EECs, and locations where the 

NEC applies (for example, Customer Premises 

and is intended to be installed by trained 

service personnel). Install the SFP in an 

ADTRAN product located in a restricted access 

location.

This device complies with Part 15 of the FCC rules. 

Operation is subject to the following two conditions:

1. This device may not cause harmful interference
2. This device must accept any interference received, 

including interference that may cause undesired 

operation.

Changes or modifications not expressly approved by 

ADTRAN could void the user's authority to operate this 

equipment.

CAUTION: Per GR-1089-CORE the ADTRAN system that 

the SFP is being deployed in is designed and 

intended for installation as part of a Common 

Bonding Network (CBN). The ADTRAN system 

that the SFP is being deployed in is not designed 

nor intended for installation as part of an 

Isolated Bonding Network (IBN).
Per GR-1089-CORE Section 9, the SFP does not 

have an internal DC connection between battery 

return and frame ground. The SFP can be 

installed in a DC-I (isolated) or DC-C (common) 

installation. For installations where other cards 

or the host system have internal connections 

between battery return and frame ground, the 

system would be intended for deployment only 

in a DC-C installation.
The ADTRAN system chassis frame ground 

terminal must be connected to an earth ground to 

ensure that the metal enclosure of the SFP is 

properly grounded via the backplane connector.

Warranty

: ADTRAN will replace or repair this product within the warranty period if it does not meet 

its published specifications or fails while in service. Warranty information can be found 

online at 

www.adtran.com/warranty

.

© 2008 ADTRAN, Inc. All Rights Reserved.

*61442120G1-22A*

C A U T I O N ! 

SUBJECT TO ELECTROSTATIC DAMAGE

OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.

CLEI: VAUIAL8P _ _
Product P/N: 1442120G1

Issue Date: 0802

Document P/N: 61442120G1-22A

PRICING AND AVAILABILITY

800.827.0807

TECHNICAL SUPPORT

800.726.8663

RETURN FOR REPAIR

256.963.8722

Small Form-Factor Pluggable

Gigabit Ethernet, Single-Mode 20 km