6.0  CONFIGURATION 

All  ADTECH  units  are  factory  calibrated  per  P.O.  instructions. 

Usually, a complete recalibration is not required uf'lless you want to 
change input type, output type, or the range of the unit. A calibration 

sticker  located  on  the  unit  identifies  the  model,  calibration  and 
options present. 

NOTE: For recalibration to the existing range proceed to section 6.1; 

for new input or output range proceed as follows. 

A. Remove the right cover to expose the 8 position switch and

Jumper J1 on the input PCB Oust obove the potentiometers).

B. Set output configuration jumpers per table 1 in section 8.0.

C. Set switch 3 position 1 for upscale or downscale burnout.  Set

switch 3 position 2 to Linearized or non-linearized per table 2,

section 8.0.

D. Set switch 3 position 3 to the on position and adjust the output

zero potentiometer for the proper output.

E. Set switch 3 position 3 to off and position 4 to on.  Adjust the

output span potentiometer for full scale output.  Repeat steps

D and E until you reach the desired accuracy.  (Note: you can
check the midscale value by depressing switch 3 positions 3
and 4 simultaneously.)

F. Return  switch 3 positions 3  and  4  to the  off  position,  and

proceed with section 6.1  below to finish the calibration.

6.1  CALIBRATION 

A. Apply the zero input value at the input terminals of the unit.

Depress and hold the Zero input calibration push button switch

until the Zero status led flashes.  You have just set the input

zero, and the output should be at your zero value after a short

time delay.

B. Apply the full scale input value at the input terminals.  Depress

and hold the Span input calibration push button switch until the

Span status led flashes.  You have just set the full scale value

and the output should be at full scale after a short delay.

C. Calibration is complete. Check the calibration with various input

values and verify the output values.

COPPER 

WIRE 

7.0  FIELD TROUBLE SHOOTING GUIDE 

This section offers a simple, first level trouble-shooting aid for an 

apparent instrument malfunction. 

SYMPTOM 

No Output 

CORRECTIVE ACTION 

1. Check the input and output

connections carefully.

2. Check that the power supply polarity

is correct and that the output loop
power is present on the indicated
terminals.

3. Check that the input source(s) is

correct and that it changes magnitude

between zero and full scale values
when so adjusted.

4. Make sure the output loop is

complete and that the correct meter
range is selected.

All external checks are complete.

Problem seems to be internal.

The instrument is made of  small components.  Troubleshooting 

beyond the above may be difficult with out special equipment.  We 

do not recommend attempting repair of he unit in the field.  ADTE CH 

offers a very responsive repair policy. Contact the ADTE CH factory 

for information on repair and return at 716-383-8280 or 716-383-
8386(FAX). 

Typical Test Connection 

01�, 

coo 

POWER 

SUPPLY 

-2-

(8/ 99)  190-A-000097 Rev. A 