TCT-327-MOD 

Ill..' 

3750 Monroe Avenue 

Pittsford°, New York 14534-1302 

��  (716) 383-8280 •  FAX (716) 383-8386 

Hi-Speed type S TC Isolated Transmitter 

Instruction Manual 

1.0  INTRODUCTION 

These instructions ref er to the above model. Supplementary sheets 

are attached if the unit has special options or features. For detailed 

specifications, see page 4 or refer to the Data Bulletin. All ADTE CH 

instruments are factory calibrated and supplied with a label detailing 

the calibration. Adjustments are normally not necessary. A simple 

check must be performed to verify calibration before installation to 

ensure that it matches the field requirement. 

2.0  GENERAL DESCRIPTION 

The TCT-327-MOD transmitter accepts a type S thermocouple input 
and  provides  a  linearized  and  isolated  output  representing 

temperature  at  a  rate  of  500  samples  per  second  (130  Hz 

bandwidth).  Calibration is extremely easy  with Adtech's Smart 

Touch® 

technology.  Simply input your zero value, touch a button, 

input your span value and  touch another button,  and the unit is 

calibrated. 

The isolated output resolution is 12 bits and provides 0-5 Vdc.Other 

voltage or current output signals are available (see table 1 page 3) 

Isolation is 600 volts ac or 1000 volts de from the input to the output 

/ power supply.  Power requirements are 15 to 42 Vdc at 40 ma 

maximum. 

The primary features are: 

• Wide range - covers the full range of the ISA standard type S

thermocouple.

• Output setup is via plug in jumpers.

• High accuracy, input resolution of 0.6µv for 0.1 °C resolution.

• High speed (500 samples per second) linearized conversion.

• RFI resistant.

• NO INTERACTION of zero and span controls.

• Adtech Smart Touch® calibration.

• Small size - DIN mounting package (1 "w x 3.1 "h x 3.6"d).

• Options for NEMA 4 and NEMA 7 housings, SNAP TRAK and

surface mounting.

3.0  INSTALLATION 
Electrical Connections 

The wire used to connect the instrument to the control system 1/0 

should be a twisted pair(s) and sized according to normal practice. 

Shielded cable is not normally necessary (if used, the shield must 

be grounded at the input negative of the ADTECH instrument and 

left floating at the sensor). 

-1-

Six position compression terminal blocks are provided for 1/0 and 

power connection.  A housing ground terminal is not required due 

to non-metallic housing. 

Controls 

Instrument controls consist of the following: 

• 8  position  switch  for  input  configuration  and  calibration

options.

• Jumper for zero based 

elevated output.

• Output zero and span pots.

• Input zero and span push buttons (Adtech 

Smart Touch®)

4.0  MAINTENANCE 

These  instruments  are  electronic  and  require  no  maintenance 

except periodic cleaning and calibration verification.  If the unit 

appears to be mis-operating it should be checked per sections 6.0 

and  7.0.  MOST  problems  are  traced  to  field  wiring  and 

or 

associated  circuits.  If  the  problem  appears  to  be  with  the 

instrument, proceed to sections 6.0 and 7.0. 

5.0  CONNECTIONS 

Standard connections are shown below and on the instrument face 

plate, Data Bulletin or on attached supplementary sheets. 

(+)------

Type S TC Input 

(-) 

------.1 

!• 

1.�

:

1.•

1

,• 

,..

,

.Jto

_

l.

.,,

'-

l

input 

l

� 

SPAN 

t::.:\ 

INCN. 

� 

ZERO 

® 

SPAN 

&:\ 

STATUS 

�  ZERO 

l

ADTECH 

TCT-327 

SPAN@ 

OUTCN. 

ZERO@ 

- + 

+V

ii

:

,,J, 

•. 

Common 

(-)------

0 to 5Vdc Output 

(+)------

Power 15 to 

42VDC 

...... -----(+) 

(8/ 99)  190-A-000097 Rev. A 