ADT-CHG-120 Instruction  05/01/98  PN 50938:A

17

Table 7 shows the conditions that cause the charger LEDs to come on:

1RUPDO2SHUDWLRQ

The ADT-CHG-120 charges batteries at 4.5 A. When batteries are fully charged, the 
charger maintains a float charge of 27.6 VDC at a trickle charge rate of less than 400 mA. 
While charging the batteries, the HI and LO Charge LEDs switch on and off approximately 
every 20 seconds. Also, one of the 23 V, 25 V, 27 V, or Low Battery LEDs also comes on, 
depending on the battery voltage.

LED

No

rm

al

 Ope

rat

io

n

AC

 T

ro

u

b

le

Disc

on

n

e

cted

 

Ba

ttery

Gr

o

u

n

d

 F

a

ul

t

Sho

rt

 C

ir

cuit

F

a

u

lty

 Ba

ttery

(o

r less th

e

 2

1

 V)

Tr

o

u

b

le

 (

w

it

h

 A

C

 Tr

o

u

b

le

De

lay u

sed

)

T

rou

bl

e

 (

M

ast

e

r T

rou

b

le In

J

P

6 con

n

ected

)

AC On

+

+

+

+

+

+

Trouble

+

+

+

+

+

+

+

Ground Fault

+

HI Charge

,

,

,

,

,

LO Charge
(Loss of AC)

,

+

+

,

,

+

,

27 V

,

,

+

,

,

,

25 V

,

,

,

,

,

23 V

,

,

,

,

,

Low Battery

,

,

,

+

+

,

,

/HJHQG
+

LED on.

,

 LED on or off, depending on battery voltage. Refer to “Normal Operation.”

Table 7 LED Status Indicators 

Содержание ADT-CHG-120

Страница 1: ... 7 DWWHU KDUJHU QVWUXFWLRQ 0DQXDO ADT Security Services Inc 1750 Clint Moore Road Boca Raton FL 33431 561 988 3600 RFXPHQW 5HYLVLRQ A 31 1 ...

Страница 2: ...rger 6 Mounting the Charger 8 Mounting the Charger into a CAB 3 Series Cabinet 8 Mounting the Charger into a BB 55 Battery Box 9 Connecting the Charger to a Load 10 Connecting the Charger to a Multiple Load 10 Connecting the Charger for Additional Current 11 Configuring the Charger 12 Delay loss of AC Reporting 12 Disable Ground Fault Detection 12 Trouble and Form C Relay Connections Optional 13 I...

Страница 3: ...iv ADT CHG 120 Instruction 05 01 98 PN 50938 A 1RWHV ...

Страница 4: ...e available with the charger You can configure the charger to disable the charger s ground fault detection to delay AC loss reporting 8 or 16 hours and to operate with 120 VAC or 240 VAC How long does it take the charger to charge batteries Typically it takes 9 hours to charge 25 AH batteries 20 hours to charge 55 AH batteries and 38 hours to charge 120 AH batteries Refer to Specifications on page...

Страница 5: ... Fuses F1 F2 and F3 15 A PN 12057 provide overload and reverse polarity protection Replace a blown fuse with a fuse with the same rating and type 3HULRGLF QVSHFWLRQ Periodically inspect the batteries for corrosion and make sure that corrosive effects to the batteries do not affect the charger or cabinet 7URXEOHVKRRWLQJ Most problems with a charger are due to faulty batteries or loose connections I...

Страница 6: ...er Connections Jumpers and Switches Location and references to connections jumpers and switches used to configure maintain and operate the charger 4 Connecting AC Power to the Charger How to connect AC power to the charger 5 Connecting Batteries to the Charger How to connect batteries to the charger in two configurations using two batteries and using four batteries 6 Mounting the Charger How to mo...

Страница 7: ...Q UHIHU WR LVDEOH URXQG DXOW HWHFWLRQµ RQ SDJH 6WDWXV QGLFDWRUV 1LQH V WR LQGLFDWH VWDWXV RI WKH FKDUJHU VHH 8QGHUVWDQGLQJ WKH 6WDWXV QGLFDWRUVµ RQ SDJH 5HVLVWRU 5 8VHG ZLWK 3 WR GHOD ORVV RI UHSRUWLQJ UHIHU WR HOD ORVV RI 5HSRUWLQJµ RQ SDJH 3 2SHQ ROOHFWRU 7URXEOH 2XW DQG 3 2SHQ ROOHFWRU 7URXEOH Q VHH 7URXEOH DQG RUP 5HOD RQQHFWLRQV 2SWLRQDO µ RQ SDJH 3 0DVWHU 7URXEOH Q VHH 7URXEOH DQG RUP 5HOD R...

Страница 8: ...ng the charger to the main AC power source Figure 4 Connecting AC Power to the Charger 6 VHW WR 9 RSHUDWLRQ 6 VHW WR 9 RSHUDWLRQ 1RWH 7KH FKDUJHU LV UDWHG IRU 9 RU 9 RSHUDWLRQ 7KHUHIRUH 9 RQ 6 LQGLFDWHV 9 RSHUDWLRQ DQG 9 LQGLFDWHV 9 RSHUDWLRQ Step 1 Remove the plastic insulating cover from TB1 Step 2 Connect the Earth ground line to TB1 Step 3 Connect the Primary Neutral line to TB1 Step 4 Connect...

Страница 9: ...able 3 contains instructions for connecting batteries to the charger Warning Do not connect the Battery Interconnect Cable at this time Refer to Starting the Charger on page 16 036 7 7 7 Step Action 1 Remove all power sources to the charger 2 Connect the battery negative cable to the TB2 terminal on the charger labeled Battery as shown in Figure 5 3 Connect the battery positive cable to the TB2 te...

Страница 10: ...ger on page 16 036 7 7 7 Step Action 1 Remove all power sources to the charger 2 Tie the batteries in pairs by connecting the battery negative terminals and the battery positive terminals as shown in Figure 6 3 Connect the battery negative cable to the TB2 terminal on the charger labeled Battery as shown in Figure 6 4 Connect the battery positive cable to the TB2 terminal on the charger labeled Ba...

Страница 11: ...sition 2 Figure 7 shows the two mounting positions of a charger into a CAB 3 Figure 7 Mounting a Charger into a CAB 3 Series Cabinet CAB C3 shown To mount a charger into a CAB 3 Series Cabinet follow these instructions Position 1 Lower right corner Position 2 Lower left corner Step Action 1 Place the charger chassis mounting slots in line with the mounting holes in the cabinet If mounting in posit...

Страница 12: ...in the BB 55 Figure 8 shows the mounting position of a charger in a BB 55 Figure 8 Mounting a Charger into a BB 55 To mount a charger into a BB 55 battery box follow these instructions 2SWLRQDO EUDFNHW IRU PRXQWLQJ DQ RSWLRQDO 0 RU 90 6HOI WDSSLQJ VFUHZV Step Action 1 Place the charger chassis mounting slots in line with the mounting holes in the BB 55 2 Insert the self tapping screws through the ...

Страница 13: ...shown in Figure 9 Figure 9 Typical Wiring for a Charger to a Multiple Load To connect a charger as shown in Figure 9 follow these steps Step Action 1 Connect the battery and battery terminals of the power supply to the charger output circuit TB2 Out 1 and Out 1 as shown in Figure 9 2 Connect the battery and battery terminals of the amplifier to the charger output circuit TB2 Out 2 and Out 2 as sho...

Страница 14: ...e Battery and Battery terminals of the power supply to the charger Battery output TB2 Batt 1 and Batt 1 as shown in Figure 10 2 Connect the Battery and Battery terminals of the first AA 120 to the charger output circuit TB2 Out 2 and Out 2 as shown Figure 10 3 Connect the Battery and Battery terminals of the first AA 30 to the charger output circuit TB2 Out 1 and Out 1 as shown in Figure 10 4 Conn...

Страница 15: ...ble bus and Form C trouble contacts when AC fails You can configure the charger for an 8 hour or a 16 hour delay as follows 8 hour delay Cut and remove jumper JP8 on the charger Figure 11 16 hour delay Cut jumper JP8 then cut and remove resistor R100 Figure 11 LVDEOH URXQG DXOW HWHFWLRQ To disable local charger earth fault detection cut and remove resistor R104 Figure 11 Figure 12 contains a simpl...

Страница 16: ... connections Figure 13 Connections for Optional Devices Function Connector Use open collector input and output to daisy chain a trouble signal through the charger without affecting charger operation JP5 Open Collector Trouble In JP4 Open Collector Trouble Out Receive trouble signals from another device such as a M500CH JP6 Master Trouble In Transmit a charger trouble signal to another device TB3 F...

Страница 17: ...JP9 on the charger Figure 13 2 Connect the AM 1 harness to JP3 on the charger Figure 11 making sure to observe proper polarity 3 Mount the AM 1 into a mounting slot on the front of the BB 55 Figure 14 Figure 14 Mounting an AM 1 or VM 1 to a BB 55 Battery Box Item Part Number Description Ammeter AM 1 0 10 A ammeter with a 3 ft cable for connection to the charger JP3 Mounts into a BB 55 battery box ...

Страница 18: ...TB2 Out 1 See Figure 13 2 Connect the negative lead to TB2 Out 1 SeeFigure 13 3 Mount the VM 1 into a mounting slot on the front of the BB 55 battery box QVWDOOLQJ DQ 030 To install an MPM 3 follow these steps 1 Connect the AM 1 Figure 13 2 Connect the VM 1 Figure 13 3 Mount the MPM 3 onto a power supply connected to your system such as an MPS 400 or MPS 24A Figure 15 Figure 15 Mounting an MPM 3 3...

Страница 19: ...nnected To start the charger follow these steps 1 Connect AC power to the charger The AC On LED and Trouble LED go on 2 Connect the batteries to the charger 3 Connect the Battery Interconnect Cable The Trouble LED goes off 4 Connect the charger to the load such as a power supply an amplifier and so on 8QGHUVWDQGLQJ WKH 6WDWXV QGLFDWRUV The charger provides nine LED Status Indicators which are iden...

Страница 20: ...O Charge LEDs switch on and off approximately every 20 seconds Also one of the 23 V 25 V 27 V or Low Battery LEDs also comes on depending on the battery voltage LED Normal Operation AC Trouble Disconnected Battery Ground Fault Short Circuit Faulty Battery or less the 21 V Trouble with AC Trouble Delay used Trouble Master Trouble In JP6 connected AC On Trouble Ground Fault HI Charge LO Charge Loss ...

Страница 21: ...18 ADT CHG 120 Instruction 05 01 98 PN 50938 A 1RWHV ...

Отзывы: