IG 1.05
© ADS 2015
2
4640 TRUEMAN BLVD. HILLIARD, OH 43026 (800) 821-6710 www.ads-pipe.com
I nst ruc t ions For I nst a lling Wa t e rSt op Ga sk e t t o H DPE/H P Pipe
1.
Thoroughly clean 2 feet of pipe section at the insertion end of the pipe.
2.
Position the WaterStop Gasket so the center lobe is in the valley of the corrugation.
3.
Place the stainless steel take-up clamps in the grooves on each side of the center lobe.
Insure that both clamps lie on the crest of the pipe corrugations.
4.
Position the take-up clamp screws 180˚ from each other. Using a torque ratchet or torque
wrench, gradually tighten both screws of each clamp to 60lbs./inch torque. Do not
overtighten. A screwdriver will not tighten clamps adequately.
5.
Apply a good quality concrete bonding agent to the structure opening.
6.
Insert pipe into the structure opening. Make sure that the WaterStop is fully within the
plane of the structure's wall.
If mortaring in place, apply and compact non-shrink grout around the WaterStop and
between the pipe and the opening, taking care to fill the voids. Make sure that the
WaterStop Gasket does not contact the bare structure walls.
If pouring in place, use concrete of sufficient slump to permit complete flow around the
pipe and WaterStop. Thoroughly vibrate all around the pipe and WaterStop Gasket to
complete compaction and to release any trapped
air.
7.
Allow concrete or mortar to fully cure before testing or backfilling. If the system is to be tested, testing should be
completed prior to backfilling around the structure, following all recommendations and requirements of the test
system manufacturer. Plug any vent holes in the pipe prior to testing.
8.
Backfill the pipe following the manufacturer’s recommendations.