Advanced RF Technologies, Inc.
35
7.
PSR-VU-9537-UBWEB-GUI SETUP INTRODUCTION
The Web-GUI allows the user to communicate with the repeater locally. To connect to the repeater locally, you
will need a laptop with an Ethernet port and an RJ-45 crossover cable.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for in-building 2-Way Emergency Radio Communication Enhancement Systems, UL 2524 certain programming
features or options must be limited to specific values or not used at all as indicated below.
Program feature or option
Permitted in UL 2524?
(Y/N)
Possible settings
Settings permitted in
UL 2524
Remote Power Switch
N
Enable/Disable
Disable
Battery Not Charge Check
Y
On/Off
On
Battery Check
Y
Check All/Except
Installed/Check Off
Check All
Donor Antenna Malfunction
Check Time
Y
0sec, 10sec, 45sec, 90sec,
3min, 6min, 15min, 30min,
1hour, 2hour, 4hour, 8hour,
12hour, 24hour, and 48hour
0sec, 10sec, 45sec,
90sec, 3min, 6min,
15min, 30min, 1hour,
2hour, 4hour, 8hour,
12hour, and 24hour
Please note that some selections of the Donor Antenna Malfunction Check Time setting could impact the
compliance of the UL 2524 code. The selections available for this option are 0sec, 10sec, 45sec, 90sec, 3min,
6min, 15min, 30min, 1hour, 2hour, 4hour, 8hour, 12hour, 24hour, and 48hour. Selection of 24 hours or less will
be required to remain compliant with UL 2524.
Figure 7-1
Donor Antenna Malfunction Check Time
Содержание PSR-VU-9537-UA
Страница 27: ...Advanced RF Technologies Inc 27 Figure 5 2 PSR ANN Repeater Mount ...
Страница 37: ...Advanced RF Technologies Inc 37 7 2 Status Tab Figure 7 3 Status Tab ...
Страница 41: ...Advanced RF Technologies Inc 41 7 3 Control Tab Figure 7 9 Control Tab ...
Страница 56: ...Advanced RF Technologies Inc 56 11 MECHANICAL DRAWING Figure 11 1 PSR VU 9537 UBMechanical Drawing ...
Страница 57: ...Advanced RF Technologies Inc 57 Figure 11 2 PSR ANN Annunciator Mechanical Drawing ...
Страница 58: ...Advanced RF Technologies Inc 58 Figure 11 3 ADRF BBL U Mechanical Drawing ...
Страница 59: ...Advanced RF Technologies Inc 59 Figure 11 4 ADRF BBS U Mechanical Drawing ...