background image

 

 

4.2.  Selecting Installation Position 

 

Chapter 4.  Installation and Operation 

 

It is necessary to select a proper environment to install the unit, in order to 
minimize the possibility of damage to the UPS and extend the life of the UPS. 
Please follow the instructions below: 
 

 

12 

Note: The packing condition and the external outlook of the unit should be 
inspected carefully before installation. Retain the packing material for future use. 

 

1. Keep at least 20cm(8 inches) 

clearance from the rear panel of the 
UPS from the wall or other 
obstructions. 

 
 

 

4.1. Unpacking 
 

1. Take the UPS out of the PE foam. 
2. Remove the packing materials. 

Note: The UPS module is approx. 12.5~39 kgs, be cautious when unpacking 
and lifting the unit to avoid injury. 

2. Do not block the air-flow to the 

ventilation openings of the unit. 

 
 

3. Standard Package includes: 

a. User's Manual 
b.  AC Input Power Cord ( Not available for hard wiring connection models) 
c.  IEC output cables ( for the UPS with IEC sockets only) 
d.  RJ11 Phone Jack Cable 
e.  UPS communication kit (optional) 

4. Accessories for Tower and Rack Mount 
 
 
 
 
 
 
 

 

13

3. Please ensure the installation site 

environmental conditions are in 
accordance with the UPS working 
specifications to avoid overheat and 
excessive moisture. 

 
 
 
 
4. Do not place the UPS in a dusty or 

corrosive environment or near any 
flammable objects. 

 
5. This UPS is not designed for outdoor 

use. 

 
 

Optional 

Optional 

 

Содержание Mini-J RT series

Страница 1: ...stallation 14 4 3 2 Rack Mount installation 16 4 4 Operation Test 18 4 5 Storage Instruction 19 4 6 SNMP Slot 19 4 7 Replacing the Battery 20 Chapter 5 UPS Working Principle 22 5 1 When Utility is Normal 22 5 2 When Utility is Abnormal 22 5 3 Overload Condition 23 5 4 Inverter Failure 24 5 4 1 Output short circuit under inverter mode 24 5 4 2 Output Short circuit under bypass Mode 24 5 5 Inverter ...

Страница 2: ...uit Current The Following Precaution Should be Observed When Working on Batteries Make sure that the AC Utility outlet is correctly grounded Do not try to repair the unit yourself contact your local supplier or your warranty will be void A Remove watches rings or other metal objects B Use tools with insulated handles Please make sure that the input voltage of the UPS matches the supply voltage C W...

Страница 3: ...utomatically switch to bypass mode when the connected loads exceeds 120 of rating It will automatically switch back to inverter mode once overload condition ceases z Guarantees an exclusive protection against DC damage for inductive load Such as motor based devices allowing wide range of different applications Should the output becomes short circuited the UPS holds the system with current limits a...

Страница 4: ...required To press the button over 5 seconds the UPS will be switched to Bypass mode and vice versa c To illustrate the percentage of output load level at AC Mode and the battery energy level at Backup Mode 4 Fault LED Red LED lights up if UPS is faulty 5 Bypass LED Amber LED lights up when UPS is in Bypass mode 6 Utility LED a AC normal Green LED lights up b 100 for load battery level 7 Inverter L...

Страница 5: ...e installation This is to be plugged by the devices to be protected by the UPS Socket type 1Kva 2Kva 3Kva NEMA 5 15R 4pcs 2pcs N A NEMA 5 20R N A 2pcs N A NEMA L5 30 N A N A 1pce AC Outlet For 120Vac System Terminal Block N A N A Yes Socket Type 1Kva 2Kva 3Kva IEC 3pcs 3pcs N A Local Sockets 1pce 2pcs 2pcs 4 For 230Vac System Terminal Block N A N A Yes 5 SNMP Slot It is an optional feature used fo...

Страница 6: ...tware kit The bundled software of the UPS is for Windows environment such as Windows 3 1 Windows 95 98 Windows NT For other applications such as Novell NetWare Unix etc please contact your local distributor for appropriate solution 3 3 1 RS232 interface settings The RS232 interface is to be configured as follows Baud Rate 2400 bps Data Length 8 bits Stop Bit 1 bit Parity None 3 3 2 Pin Assignments...

Страница 7: ...m 2 Remove the packing materials Note The UPS module is approx 12 5 39 kgs be cautious when unpacking and lifting the unit to avoid injury 2 Do not block the air flow to the ventilation openings of the unit 3 Standard Package includes a User s Manual b AC Input Power Cord Not available for hard wiring connection models c IEC output cables for the UPS with IEC sockets only d RJ11 Phone Jack Cable e...

Страница 8: ...Use with extended battery bank 4 3 Installation Instructions Step 1 4 3 1 Tower installation Stand alone unit Step 1 Step 2 15 Step 2 14 ...

Страница 9: ...Step 4 4 3 2 Rack Mount installation Step 1 Step 2 Step 3 Step 5 17 16 ...

Страница 10: ... then the Utility LED and Inverter LED will light up simultaneously 5 Simulate a Mains failure by disconnecting the input power cord of the UPS to see whether the UPS remains operation DC Mode when Utility is absent The Utility LED should extinguish and the alarm will sound continuously till battery cut off The UPS should continue to provide power supply at its output terminals To mute the audible...

Страница 11: ...Step 2 4 7 Replacing the Battery Step 1 Step 3 Step 4 20 21 ...

Страница 12: ... abnormal condition is illustrated as follows O P OUTPUT 4 1 RECTIFIER O P OUTPUT 4 2 23 During a blackout the UPS will work as illustrated in figure 4 2 When Battery is low buzzer will beep continuously till battery is completely cut off The battery low protection of the UPS will cut off battery supply after a preset threshold to avoid the battery from over drain The Inverter LED and Bat Low LED ...

Страница 13: ...Output Voltage Out of tolerance If the UPS inverter delivers over current and out of tolerance voltage to its output the UPS is out of order The UPS will switch to bypass mode when Utility is normal The Utility LED Bypass LED and Fault LED will light up If these two conditions occur when Utility is abnormal the UPS will turn off the Output and the Fault LED will light up O P OUTPUT 4 4 25 2 Troubl...

Страница 14: ...ging capability test 27 Bun ftwa allation allation 1 Connect the male connector of RUPS II cable 2 Connect the female connector of RUPS II cabl rt If there is only a DB25 connector of the RS232 p DB9 DB25 adapter to convert it 7 2 Software Installation tallatio A RUPS II for MS DOS 1 Insert the system diskett sk execute INSTALL EXE u A CD DOS Enter TALL 2 Please select the MS DO t 3 And create the...

Страница 15: ...1 Login the File Server as a SUPERVISOR or a USER with Access Right sub directory SYS SYSTEM F LOGIN SUPERVISOR mv linux z linux Z or mv LINUX Z linux Z chmod 755 install 2 Insert the system diskette into the floppy disk Driver A or you drive 4 Execute the installation program install Select a targ 5 sure no other process using the sam lau UPSilon for Unix daemon p nch the 3 Execute INSTALL EXE in...

Страница 16: ...uit a Inv UPS shut nd Cut the O b ode ks do Mode Bypass M down a AC Input fuse Brea utput wn Overheat a Utility Normal Switch to Bypass sounds continuously cut the output b Utility Abnormal Buzzer t LED lights up then Faul H ode igh Voltage ff Trip O Switch to Backup M Battery Low Alarm continuously till battery cutoff Noise Suppression Comply with EN50091 2 Spike Suppression N6100 Comply with E 0...

Отзывы: