Adp Foa Series Скачать руководство пользователя страница 18

Gas Flow 

Service 

To  check  for  proper  gas  flow  to  the  combustion  chamber, 
determine  the  Btu  input  from  the  appliance  rating  plate. 
Divide this input rating by the Btu per cubic feet of available 
gas.  Result  is  the  required  number  of  cubic  feet  per  hour. 
Determine  the  flow  of  gas  through  the  gas  meter  for  two 
minutes and multiply by 30 to get the hourly flow of gas. 

Gas Pressure Adjustment 

1)

Check  gas  line  pressure  with  unit  firing  at  maximum
rate.  A minimum of 5" (127mm) w.g. for natural gas or
10.4"  (264mm)  w.g.  for  LP/propane  gas    should    be
maintained for proper  unit operation.

2)

After  line  pressure  has  been  checked  and  adjusted,
check  regulator  pressure.  Correct  manifold  pressure  is
shown on the unit rating plate.  See figures 9 and 10 for
gas  pressure  adjustment  screw  location.    A  natural  gas
to LP/propane gas changeover kit is required to convert
the  unit  in  the  field.  Refer  to  installation  instructions
provided with changeover kit for conversion procedure.

Limit Control 

The  limit  control  switch  is  factory-set  and  is  not 
field−adjustable. 

Louver Vane Adjustment 

Rotate  louver  vanes  to  direct  airflow  upward,  downward, 
straight, or any combination of these directions.  When unit is 
installed in an inverted position, louvers may be positioned in 
the same manner. 

Combustion Air Pressure Switch 

This  pressure  switch  checks  for  proper  combustion  air 
inducer  operation  before  allowing  an  ignition  trial.    The 
switch is factory-set.  No field adjustment is necessary. 

Flame Rollout Switch 

The  flame  rollout  switch(es)  are  located  on  the  burner  box 
top, behind the ignition control board.  This normally closed 
switch  opens  on  a  temperature  rise.    Check  for  adequate 
combustion air before manually resetting switch. 

CAUTION 

Turn  off  gas  and  electrical  power  to  unit  before  per- 
forming any  maintenance or service operations on this unit.  
Remember to follow lighting instructions when putting unit  
back into  operation after service or maintenance.

 

The  unit  heater  and  vent  system  shall  be  inspected  once  a 
year  by  a  licensed  professional  service  technician,  or 
equivalent. 

BURNERS 

1)

Periodically examine burner flames for proper
appearance during the heating season.

2)

Before each heating season examine the burners for any
deposits or blockage that may have occurred.

3)

Clean burners as follows:

a.

Turn off both electrical and gas supplies to unit.

b.

Disconnect  gas  supply  piping,  high  tension  and
sensor  leads.  Remove  gas  manifold.    Remove
burner tray.

c.

Clean burners as necessary.  Make sure that burner
heads  line  up  properly  to  ensure  flame  crossover.
Check  spark  gap  on  electrode  and  adjust  if
required.  The  gap  should  be  between  0.110"  and
0.140"  (3mm  to  4mm).  The  gap  may  be  checked
with  appropriately  sized  twist  drills  or  feeler
gauges.

d.

Reinstall  burner  tray,  gas  manifold,  high  tension
and sensor leads.  Reconnect gas supply piping.

e.

Restore  electrical  power  and  gas  supply.    Follow
lighting  instructions  to  light  unit.  Check  burner
flame.

18

Содержание Foa Series

Страница 1: ...and Performance Checklist 19 Warranty 20 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Be sure to read and understand the installation operation and service instructions in this manual Improper installation adjustment alteration service or maintenance can cause seriou...

Страница 2: ...HEAT EXCHANGER B 1 25 18 1 2 470 HANGING BRACKETS 2 GAS INLET 5 3 4 146 TOP VIEW 29 737 1 25 SERVICE ACCESS DOOR FLUE OUTLET C A E BURNER VIEWING PORT ADJUSTABLE THUMB SCREW D COMBUSTION AIR INLET LOUVERS SIDE VIEW ELECTRICAL BOX BACK VIEW DIRECT DRIVE FAN DIMENSION 45 60 75 A 12 305 17 432 B 5 1 2 140 6 1 2 165 C 7 3 4 197 10 1 4 260 D 1 3 4 44 3 1 4 83 E 5 1 4 133 5 3 4 146 F 13 330 14 1 2 368 2...

Страница 3: ... brackets shipped loose with 45 units Check the unit for shipping damage The receiving party should contact the last carrier immediately if any shipping damage is found Optional Accessory Units require a changeover kit when the unit is to be used with LP propane gas The kit is ordered separately CSA Requirements in USA Installation of gas unit heaters must conform with local building codes or in t...

Страница 4: ...MA 02269 9101 CSA Requirements in Canada These instructions are intended only as a general guide and do not supersede local codes in any way Authorities having jurisdiction should be consulted before installation The installation must conform with local building codes or in the absence of local codes with the current edition of CSA B149 installation compliance codes All electrical wiring and groun...

Страница 5: ...ted position a Remove and retain screws securing door and rotate door 180 b Resecure door using existing screws c Rotate louvers to direct airflow as desired 2 Choose location for mounting brackets 3 Remove and retain three screws along top edge bottom edge when rotated of front of unit 4 Align screw holes on mounting bracket with holes along top edge either upright or rotated of unit Use existing...

Страница 6: ...de atmosphere to convey oxygen from the air to the appliance burner NOTE Local codes may supersede any of these provisions GENERAL RECOMMENDATIONS AND REQUIREMENTS Unit heaters must be vented in compliance with the latest edition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 in the USA and with CSA B149 1 codes in Canada as well as applicable provisions of local building codes and the followin...

Страница 7: ... listed clearance thimble is used Clearance to combustible material for type B 1 vent or factory built chimney is per manufacturer s instructions Clearance to combustible material is 1 on vertical sections of the concentric vent adapter cap kit 8 The vent connector shall be supported without any dips or sags Vertical vents shall be supported in accordance with their listing and manufacturers instr...

Страница 8: ...orizontal vent termination directly below roof eaves or above a public walkway or any other area where condensate dripping may be troublesome and may cause some staining Avoid windows where steam may cause fogging or ice buildup 8 Minimum clearance for horizontal vent termination from any door window gravity air inlet gas or electric meter regulators and relief equipment is 4 feet 1m for United St...

Страница 9: ...ITH WATER TRAP TO CONDENSATE DRAIN Category III adaptor must be installed before optional elbow if used NOTE Minimum horizontal vent length is 5 ft This does not include termination tee Refer to table 2 for maximum length and number of elbows GROUND LEVEL SLOPE 1 4 IN PER FOOT RUN MAXIMUM Provided by installer RESIDENTIAL APPLICATIONS Venting must be listed special vent for Category III appliances...

Страница 10: ... Concentric Single wall 3 Single wall 3 Concentric vent kit 4 7 Part 65336800 Double Wall B 1 60 75 Two Pipe Single wall 4 Single wall 4 Any UL approved caps Double Wall B 1 Concentric Single wall 4 Single wall 4 Concentric vent kit 4 7 Part 65336800 Double Wall B 1 100 125 Two Pipe Single wall 5 Single wall 4 Any UL approved caps Double Wall B 1 Concentric Single wall 5 Single wall 4 Concentric v...

Страница 11: ...tial Horizontal Vent Applications FOA ADP Part Number Description 45 60 75 100 125 Category III Horizontal Vent Kits 1 66808901 2 VENT KIT UP SLOPED CAT III 3 X 66808902 2 VENT KIT UP SLOPED CAT III 4 X 66808903 2 VENT KIT UP SLOPED CAT III 5 X 66809001 VENT KIT DOWN SLOPED CAT III 3 X 66809002 VENT KIT DOWN SLOPED CAT III 4 X 66809003 VENT KIT DOWN SLOPED CAT III 5 X Category III Components 3 668...

Страница 12: ...ontal Venting sections The air inlet may be single wall material or U L listed single wall flex vent connector 2 The vent pipe diameter for horizontal commercial installations shall be 3 76 mm on 45 units and 4 100 mm on 60 75 units Refer to Table 3 3 Refer to Table 2 for maximum vent lengths 4 Refer to Figure 5A for concentric kit termination Figure 3 for upward slope with condensate trap Figure ...

Страница 13: ...condition of use 7 If improper venting is observed during any of the above tests the common venting system must be corrected The common venting system should be resized to approach the minimum size as determined by using the appropriate tables in Appendix G in the current editions of the ANSI Z223 1 or the appropriate Category I Natural Gas and Propane appliances venting sizing tables in the curre...

Страница 14: ...TYPICAL FOA 45 60 75 100 125 WIRING SCHEMATIC FIGURE 7 14 ...

Страница 15: ...nished by Installer GROUND JOINT UNION NOTE Compounds used on threaded joints of gas piping must be resistant to the actions of liquefied petroleum gases Leak Check After gas piping is completed carefully check all piping connections field and factory for gas leaks Use a soap solution or other preferred means CAUTION DO NOT use matches candles flame or other sources of ignition to check for gas le...

Страница 16: ...t in a fire or explosion These unit heaters are equipped with an automatic spark ignition system There is no pilot In case of a safety shutdown move thermostat switch to OFF then return the thermostat switch to HEAT position FOA unit heaters are equipped with an automatic spark ignition system There is no pilot In case of a safety shutdown move thermostat switch to OFF then return the thermostat s...

Страница 17: ...tisfied the combustion air inducer is shut off 9 The ignition control will shut off the system fan approximately 120 seconds after the gas valve is de energized Ignition Control LED The ignition control contains a green LED which indicates the following TABLE 6 IGNITION CONTROL LED LED UNIT OPERATION Slow Flash Normal Operation No call for heat Fast Flash Normal Operation Call for heat 2 Flashes S...

Страница 18: ...ration before allowing an ignition trial The switch is factory set No field adjustment is necessary Flame Rollout Switch The flame rollout switch es are located on the burner box top behind the ignition control board This normally closed switch opens on a temperature rise Check for adequate combustion air before manually resetting switch CAUTION Turn off gas and electrical power to unit before per...

Страница 19: ... 3 Is there a breaker tripped or a fuse blown 4 Is gas turned on at meter 5 Is manual shutoff valve open 6 Is unit ignition system in lock out If unit locks out again call service technician to inspect unit 7 Is pressure switch closed Obstructed flue will cause unit to shut off at pressure switch Check flue passage and outlet SAFETY SHUT OFF VALVE TEST The safety shut off valve test procedure is a...

Страница 20: ...mplete warranty terms registering for an extended warranty or obtaining instructions on filing a warranty claim please go to www ADPwarranty com In such states or provinces where registration requirements are prohibited failure to complete registration by the consumer does not diminish his or her warranty rights EQUIPMENT INFORMATION Please complete information below and retain this warranty for r...

Отзывы: