List of all Parameters and their Valid Adjustment Ranges
parameter
adjustment range
default settings
alarm relay 1
alarm relay 2
alarm relay 3
fault relay
normally opened, normally closed
normally opened, normally closed
normally opened, normally closed
- not parametrizable -
normally opened
normally opened
normally opened
normally closed
time / date
limited to appropriate inputs
current time / date
language
German, English, French
German
limit value 1 (Lt.1)
limit value 2 (Lt.2)
limit value 3 (Lt.3)
10% URV
1
< Lt.1 < Lt.2
Lt.1 < Lt.2 < 90% URV
10% URV < Lt.3 < 90% URV
20% URV*
40% URV
60% URV
monitoring direction Lt.1
monitoring direction Lt.2
monitoring direction Lt.3
overflowing / underflowing
overflowing / underflowing
overflowing / underflowing
overflowing*
overflowing
overflowing
hysteresis
0% URV to 5% URV
0% URV
confirmation Lt.1
confirmation Lt.2
confirmation Lt.3
automatic / manual
- not parametrizable -
automatic / manual
automatic
manual
automatic
relay Lt.1
relay Lt.2
relay Lt.3
- not parametrizable -
- not parametrizable -
horn relay / alarm relay
alarm relay
alarm relay
alarm relay
current 4mA
current 20mA
2000 - 6000
15000 - 25000
works calibration
works calibration
(*)
The default settings of the GTR 210 TOX O
2
(measurement of oxygen) deviate as follows:
limit value 1 (Lt.1)
limit value 2 (Lt.2)
limit value 3 (Lt.3)
90% URV > Lt.1 > Lt.2
Lt.1 > Lt.2 > 10% URV
90% URV > Lt.3 > 10% URV
19% Vol% O
2
17% Vol% O
2
15% Vol% O
2
monitoring direction Lt.1
monitoring direction Lt.2
monitoring direction Lt.3
overflow / underflow
overflow / underflow
overflow / underflow
underflow
underflow