BACnet Slave / PROFINET Master 

 

Document code: MN67B81_ENG     Revision 1.000    Page 1 of 32

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 

 

User Manual 

Revision 1.000 
English 

 

BACnet Slave / PROFINET Master - 
Converter

 

 

(Order Code: HD67B81-IP-A1, HD67B81-MSTP-A1, 

HD67B81-MSTP-B2) 

 

for Website information:  

www.adfweb.com/?Product=HD67B81

    

 

for Price information: 

www.adfweb.com/?Price=HD67B81-IP-A1

 

www.adfweb.com/?Price=HD67B81-MSTP-A1

 

www.adfweb.com/?Price=HD67B81-MSTP-B2

  

 
 

Benefits and Main Features: 

 

Triple electrical isolation 

 

Power Supply 18…35V DC and 8…24 V AC 

 

Temperature range: -40°C/+85°C (-40°F/+185°F) 

For others PROFINET Master devices, see also the following links:  

 
PROFINET Master from/to … 

www.adfweb.com?Product=HD67B45

  

(

OPC UA Server

www.adfweb.com?Product=HD67B70

  

(

Serial

www.adfweb.com?Product=HD67B71

  

(

Modbus Slave

www.adfweb.com?Product=HD67B72

  

(

PROFIBUS Slave

www.adfweb.com?Product=HD67B73

  

(

CAN

www.adfweb.com?Product=HD67B74

  

(

CANopen

www.adfweb.com?Product=HD67B75

  

(

DeviceNet Slave

www.adfweb.com?Product=HD67B76

  

(

Modbus TCP Slave

www.adfweb.com?Product=HD67B77

  

(

SNMP Agent

www.adfweb.com?Product=HD67B78

  

(

EtherNet/IP Slave

www.adfweb.com?Product=HD67B79

  

(

KNX

www.adfweb.com?Product=HD67B80

    

(

MQTT

)  

www.adfweb.com?Product=HD67B82

    

(

IEC 61850 Server

www.adfweb.com?Product=HD67B84

    

(

Ethernet

 
Do you have an your customer protocol? 

See the following links: 

www.adfweb.com?Product=HD67003

 

 
Do you need to choose a device? do you want help? 

Ask it to the following link: 

www.adfweb.com?Cmd=helpme

 

 

User Manual 

Содержание HD67B81-IP-A1

Страница 1: ...ET Master devices see also the following links PROFINET Master from to www adfweb com Product HD67B45 OPC UA Server www adfweb com Product HD67B70 Serial www adfweb com Product HD67B71 Modbus Slave ww...

Страница 2: ...S 31 WARRANTIES AND TECHNICAL SUPPORT 32 RETURN POLICY 32 Pagina 2 di 32 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following...

Страница 3: ...locks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation a...

Страница 4: ...ctronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual BACnet Slave PROFINET Master Document code MN67B81_ENG Revision 1 000 Page 4 of 32 EXAMPLE...

Страница 5: ...b com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual BACnet Slave PROFINET Master Document code MN67B81_ENG Revision 1 000 Page 5 of 32 Figure 1a Connection scheme f...

Страница 6: ...es ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual BACnet Slave PROFINET Master Document code MN67B81_ENG Revision 1 000 Page 6 of 32 Figure 1b Connection...

Страница 7: ...es ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual BACnet Slave PROFINET Master Document code MN67B81_ENG Revision 1 000 Page 7 of 32 Figure 1c Connection...

Страница 8: ...t Power Supply Up to 1500 bytes in reading and 1500 bytes in writing Two directional information between PROFINET and BACnet Mountable on 35mm Rail DIN Wide power supply input range 8 24V AC or 12 35V...

Страница 9: ...code MN67B81_ENG Revision 1 000 Page 9 of 32 POWER SUPPLY The devices can be powered between a wide range of tensions For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax HD67B81 xxx...

Страница 10: ...e device has got two functions mode depending of the position of the Dip1 of Dip Switch A The first with Dip1 in Off position factory setting is used for the normal working of the device The second wi...

Страница 11: ...inks very slowly 0 5Hz update in progress 3 BF bus fault red ON The Ethernet connection is defective the IP address exists several times in the network the own NameOfStation exists several times in th...

Страница 12: ...below LED Normal Mode Boot Mode 1 Device State Blinks slowly 1Hz ON Device powered OFF Device not powered 2 Ethernet Link ON Ethernet cable connected OFF Ethernet cable disconnected Blinks quickly Bo...

Страница 13: ...The Ethernet connection must be made using Connector3 of HD67B81 xxx A1 B2 with at least a Category 5E cable The maximum length of the cable should not exceed 100m The cable has to conform to the T568...

Страница 14: ...th a 120 resistor it is necessary to put ON dip 1 like in figure The maximum length of the cable should be 1200m 4000 feet Here some codes of cables Belden p n 8132 2x 28AWG stranded twisted pairs con...

Страница 15: ...er use the available software that runs with Windows called SW67B81 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last...

Страница 16: ...ontains the entire device s configuration A device s configuration can also be imported or exported To clone the configurations of a programmable BACnet Slave PROFINET Master Converter in order to con...

Страница 17: ...there is the possibility to change the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section...

Страница 18: ...0438 30 91 31 User Manual BACnet Slave PROFINET Master Document code MN67B81_ENG Revision 1 000 Page 18 of 32 In the section Software Settings it is possible to enable disable some keyboard s command...

Страница 19: ...pressing the Check Box field This feature is used for going out of the net In the field Name of Station the name of the PROFINET node is defined If selected BACnet IP the means of the fields for BACn...

Страница 20: ...the converter is defined In the field MAC Address the MAC of BACnet side of the converter is defined from 0 to 254 In the field Max Master the highest allowable address for master nodes is defined Th...

Страница 21: ...ces Present in Network window PROFINET ACCESS By Pressing the PROFINET Access button from the main window for SW67B81 Fig 2 the window Definition of PROFINET Devices Present in Network appears Fig 4 T...

Страница 22: ...s the IP Address of the PROFINET slave is defined If the field Automatic new session when StationProblemIndicator is Active is checked the converter opens a new communication session when an error is...

Страница 23: ...es of PROFINET Device appears Fig 5 In the main table it is possible to import the Modules of the PROFINET device in use In the properties below it is possible to set the parameters of the slave These...

Страница 24: ...ins the BACnet objects writeable by a BACnet Master the PROFINET data associated to these objects are written to PROFINET slaves The meaning of the fields in the window are the follows In the field Da...

Страница 25: ...r by compiling the Selected BACnet Engineering Unit field or by selecting with the fields Select the Type and Select unit the Type Unit desired If the second way is used is necessary to press the Sele...

Страница 26: ...urn ON the device Connect the Ethernet cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are...

Страница 27: ...LAN settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8 or 10 make sure that you have the administrator privi...

Страница 28: ...l IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual BACnet Slave PROFINET Master Document code MN67B81_ENG Revision 1 000 Page 28 of 32 MECHANICAL DIMENSIONS Figure 10a Mec...

Страница 29: ...iso INFO www adfweb com Phone 39 0438 30 91 31 User Manual BACnet Slave PROFINET Master Document code MN67B81_ENG Revision 1 000 Page 29 of 32 Figure 10b Mechanical dimensions scheme for HD676B81 MSTP...

Страница 30: ...ixed 5mm Screw Terminal Enclosure Type A 1M 35mm DIN Rail mounting B 4M 35mm DIN Rail mounting BACnet type IP BACnet IP MSTP BACnet MS TP Device Family HD67B81 BACnet Slave PROFINET Master Converter O...

Страница 31: ...ean countries with separate collection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an appli...

Страница 32: ...h to exchange or repair it please do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information abo...

Отзывы: