Figure 3d: “Set Communication
BACnet Slave”
window
Figure 3e: “Set Communication
NTP (Network
Time Protocol” window
BAC
NET
S
LAVE
(
FOR
BAC
NET
MS/TP):
This section is used to define the main parameters of BACnet MS/TP line. The
means of the fields are:
In the field “
Baudrate
” the data rate of the BACnet line is defined;
In the field “
Parity
” the parity of the line is defined;
In the field “
BACnet Device Name
” the name to give to the BACnet node is
defined;
In the field “
MAC Address
” the MAC of BACnet node (from 0 to 254) is
defined;
The field “
Max Master
” specifies the highest allowable address for master
nodes. The value shall be less than or equal to 127;
The field “
Max Info Frames
” specifies the maximum number of information
frames the node may send before it must pass the token;
In the field “
Device Instance
” the of the BACnet MS/TP side of the
converter is defined;
In the field “
Network
” the BACnet MS/TP network number is defined;
If the field “
BACnet description up to 32 chars
” is checked, the
description of the BACnet objects can be up to 32 chars.
NTP
(N
ETWORK
T
IME
P
ROTOCOL
)
This section is used to define the parameters of NTP protocol. The means of the
fields are:
In the field “
Server URL
” the URL or the IP Address of the NTP Server is
defined;
In the field “
Poll Time (seconds)
” the polling time for the time
synchronization is defined.