Industrial
Electronic Devices
ADFweb.com S.r.l.
User Manual
BACnet Master / MQTT
Document code: MN67937_ENG Revision 1.000 Page 19 of 36
Figure 3c: “Set Communication
BACnet MS/TP
Master” window
BAC
NET
M
ASTER
(
FOR
BAC
NET
MS/TP):
This section is used to define the main parameters of BACnet MS/TP line. The
means of the fields are:
In the field “
Baudrate
” it is possible to select the baudrate of the BACnet;
In the field “
Parity
” it is possible to select the parity of the line;
In the field “
BACnet Device Name
” is possible to insert the name to give to
the BACnet node;
In the field “
MAC Address
” it is possible to define the MAC of BACnet node
(from 0 to 254);
The field “
Max Masters
” specifies the highest allowable address for master
nodes. The value shall be less than or equal to 127;
The field “
Max Info Frames
” specifies the maximum number of information
frames the node may send before it must pass the token;
In the field “
Device Istance
” it is possible to assign a number to the BACnet
node (Used for the Device Istance).