Industrial

 

Electronic Devices 

 

 

 ADFweb.com S.r.l. 

 

User Manual   

Modbus Slave / HART Master

 

 

Document code: MN67908_ENG     Revision 1.001   Page 24 of 32

 

 

 

Insert the IP Address configured in the converter; 

 

Start the Scan by clicking on “Start Scan” button. The window will appear like below: 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

When  the  Scan  is  complete,  the  software  will  show  the  results.  You  can  import  the  data  by  clicking  on  “OK”  button  after  having 

selected the required variables. The results will be displayed as below: 

Figure 7b: “HART Scan” window

 

Figure 7c: “HART Scan” window

 

Содержание HD67908-5-A1

Страница 1: ...ART Master to www adfweb com Product HD67900 Serial www adfweb com Product HD67901 BACnet Slave www adfweb com Product HD67902 CAN www adfweb com Product HD67903 CANopen www adfweb com Product HD67904...

Страница 2: ...RETURN POLICY 32 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To o...

Страница 3: ...device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operatio...

Страница 4: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus Slave HART Master Document code MN67908_ENG Revision 1 001 Page 4 of 32 EXAMPLES OF CONNECTION...

Страница 5: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus Slave HART Master Document code MN67908_ENG Revision 1 001 Page 5 of 32 CONNECTION SCHEME Figure 1a Connection scheme for HD67908 5 A1...

Страница 6: ...tion between Serial Power Supply Serial HART HART Power Supply Two directional information between Serial bus and HART bus Mountable on 35mm Rail DIN Wide power supply input range 8 24V AC or 12 35V D...

Страница 7: ...08_ENG Revision 1 001 Page 7 of 32 POWER SUPPLY The devices can be powered at 8 24V AC and 12 35V DC For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 8V 24V 12V 35V Consumption at...

Страница 8: ...with Dip2 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip2 of Dip Switch A at ON position is used for uploading the Project and or Firmware For the op...

Страница 9: ...T communication green It blinks when HART communication is running Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 Ethernet link green ON Ethernet cable connected OFF Ethernet...

Страница 10: ...gnals at a low level on top of the 4 20mA This enables two way field communication to take place and makes it possible for additional information beyond just the normal process variable to be communic...

Страница 11: ...dip 1 like in figure The maximum length of the cable should be 1200m 4000 feet Here some codes of cables Belden p n 8132 2x 28AWG stranded twisted pairs conductor foil shield braid shield Belden p n...

Страница 12: ...e made using Connector4 of the HD67908 X A1 with at least a Category 5E cable The maximum length of the cable should not exceed 100m The cable has to conform to the T568 norms relative to connections...

Страница 13: ...runs with Windows called SW67908 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last version of the software present on...

Страница 14: ...configuration A device s configuration can also be imported or exported To clone the configurations of a programmable Modbus Slave HART Master in order to configure another device in the same manner...

Страница 15: ...the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is possible t...

Страница 16: ...bus Slave HART Master Document code MN67908_ENG Revision 1 001 Page 16 of 32 In the section Software Settings it is possible to enable disable some keyboard s commands for an easier navigation inside...

Страница 17: ...fined The means of the fields for the Modbus Slave section are In the field Baudrate the baudrate for the serial line is defined In the field Parity the parity of the serial line is defined In the fie...

Страница 18: ...ned In the field SubNet Mask the Subnet Mask of the converter is defined In the field Gateway the default gateway of the net is defined This feature can be enabled or disabled pressing the Check Box f...

Страница 19: ...es to read write with the Modbus Master The means of the fields are If the field Enable is checked the HART variable is enabled In the field Device Address the address of HART device is defined In the...

Страница 20: ...the HART data is defined In the field Swap the bytes order is reversed In the field Conv Int the data from HART device is converted in Integer format In the field Operations a post operation on the da...

Страница 21: ...rnet cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Device Put Dip1 o...

Страница 22: ...program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8 or 10 make sure that you have the administrator privileges In case you have to program...

Страница 23: ...riables section It has the following characteristics Possibility to scan HART network Automatic decode of HART messages Easy connection directly through the Ethernet port of the converter In order to...

Страница 24: ...s configured in the converter Start the Scan by clicking on Start Scan button The window will appear like below When the Scan is complete the software will show the results You can import the data by...

Страница 25: ...like Internet Explorer Google Chrome Mozilla Firefox by editing the IP Address of the converter in the address bar of the browser WELCOME As soon as the connection to the Webserver interface of the Da...

Страница 26: ...ave HART Master Document code MN67908_ENG Revision 1 001 Page 26 of 32 When one of the buttons of the Welcome page are pressed it is necessary to do the login using the Admin and Password defined in t...

Страница 27: ...an button is pressed the HART Scan window appears Fig 10 It has the following fields NUMBER OF DEVICES TO SEARCH FOR Maximum 16 field number of Hart devices connected Scan Start button it is possible...

Страница 28: ...discovered HART node from HART Scan section is selected the HART Control window appears Fig 11 It has the following fields UNIQUE ID button it is possible to insert the unique ID of the HART device t...

Страница 29: ...al Electronic Devices ADFweb com S r l User Manual Modbus Slave HART Master Document code MN67908_ENG Revision 1 001 Page 29 of 32 MECHANICAL DIMENSIONS Figure 12 Mechanical dimensions scheme for HD67...

Страница 30: ...g HD67908 x xx Connectors Type 1 Removable 5mm Screw Terminal Enclosure Type A 1M 35mm DIN Rail mounting Modbus port 2 RS232 4 RS422 5 RS485 Device Family HD67908 Modbus Slave HART Master Converter Or...

Страница 31: ...tion systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the rec...

Страница 32: ...do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to...

Отзывы: