Industrial
Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO:
www.adfweb.com
Phone +39.0438.30.91.31
User Manual
IO-Link / BACnet Slave
Document code: MN67865_ENG Revision 1.000 Page 25 of 44
SET COMMUNICATION:
This section defines the fundamental communication parameters of BACnet.
By Pressing the “
Set Communication
” button from the main window for SW67865 (Fig. 2)
the window “Set Communication” appears (Fig. 3).
The means of the fields for “IO-LINK” are:
In the fields “
Select Device
” the type of IO-LINK channels is defined;
In the section “BACnet Slave” is possible to select the type of BACnet to use from:
BACnet/IP (uses Ethernet);
BACnet MS/TP (uses RS485).
If selected “BACnet/IP” the means of the fields for “BACnet” are:
In the fields “
IP ADDRESS
” the IP address of BACnet/IP side of the converter is
defined;
In the fields “
SUBNET
Mask
” the SubNet Mask of BACnet/IP side of the converter is
defined;
In the fields “
GATEWAY
” the default gateway of the network is defined. This feature
can be enabled or disabled pressing the Check Box field. This feature is used for going
out of the net;
In the field “
Port
” the port used for BACnet communication is defined. The default
port used for BACnet communication is 47808, but is possible to insert any value;
In the field "
BACnet Device Name
" the name of BACnet/IP side of the converter is
defined;
In the field “
Device Identifier
” the ID of BACnet/IP side of the converter is defined;
If the field “
BACnet description up to 32 chars
” is checked, the description of the
BACnet objects can be up to 32 chars.
Figure 3a: “Set Communication” window