Document code: MN67833_ENG Revision 1.100 Pagina 19 di 53
SET COMMUNICATION:
This section define the fundamental communication parameters of BACnet and DALI bus.
By Pressing the “
Set Communication
” button from the main window for SW67833 (Fig. 2) the window
“Set Communication” appears (Fig. 3).
In the section “BACnet Type” is possible to select the type of BACnet to use from:
BACnet/IP (uses Ethernet);
BACnet MS/TP (uses RS485).
If selected “BACnet/IP” the means of the fields for “BACnet” are:
In the fields “
IP ADDRESS
” the IP address of BACnet/IP side of the converter is defined;
In the fields “
SUBNET
Mask
” the SubNet Mask of BACnet/IP side of the converter is defined;
In the fields “
GATEWAY
” the default gateway of the network is defined. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “
Port
” the port used for BACnet communication is defined. The default port used for
BACnet communication is 47808, but is possible to insert any value;
In the field "
BACnet Device Name
" the name of BACnet/IP side of the converter is defined;
In the field “
Device Identifier
” the ID of BACnet/IP side of the converter is defined.
The means of the fields for the “DALI” section are:
In the field “
DALI Console Port
” the port for the Ethernet communication with the DALI
Console software is defined;
If the field “
Enable DALI 2
” is checked, DALI 2 protocol is enabled.
Figure 3a: “Set Communication” window