Document code: MN67806_ENG Revision 1.000 Page 19 of 25
In the field “
Position
” insert the address of the internal array where placing the information;
In the field “
Bit Mode
” insert the start bit of the first byte of the field “Position” where start to insert the data read;
In the field “
Lenght
” the dimension of the KNX message is defined;
In the field “
Mnemonic
” the description for the request is defined.
Note:
If the field “On change” is checked and the “Poll Time” is different from 0, the converter sends the KNX command cyclically and also
when the data is changed.
Note:
If the field “OnCMD”, “OnChange” and “OnTimer” are not checked, the converter only sniffs the bus in order to monitor the status of
the KNX message.