Read with Input Register / Status Function enabled
Data in reading:
Type
Address
Function
Description
Input Register
0
04
Input Bytes 0-1 of EtherNet/IP side
Input Register
1
04
Input Bytes 2-3 of EtherNet/IP side
Input Register
2
04
Input Bytes 4-5 of EtherNet/IP side
.
.
Input Register
719
04
Input Bytes N – N+1 of EtherNet/IP side
Data in writing:
Type
Address
Function
Description
Holding Register
0
R: 03
W: 06/16
Output Bytes 0-1 of EtherNet/IP side
Holding Register
1
R: 03
W: 06/16
Output Bytes 2-3 of EtherNet/IP side
Holding Register
2
R: 03
W: 06/16
Output Bytes 4-5 of EtherNet/IP side
.
.
Holding Register
719
R: 03
W: 06/16
Output Bytes N – N+1 of EtherNet/IP side
Note:
The data can be read/written as single bits too using Input/Coil Status (Function 02 and Functions 01/05/15).