background image

   

Industrial

 

Electronic Devices 

 

 

 ADFweb.com Srl – IT31010 – Mareno – Treviso                                                      INFO:  

www.adfweb.com

      Phone +39.0438.30.91.31            

 

User Manual   

PROFINET / J1939 - Converter 

 

Document code: MN67446_ENG     Revision 1.002    Page 26 of 31 

 

 

2)

 

Press the “

Devices and networks

” button 

(1)

, from the right drop-down menu, under “Other field devices

PROFINET 

IO

Gateway

ADFWEB.com

HD67446” double click on “MBmaster” module 

(2)

 

Note: 

If you have installed more than one GSD file, go to the Information section and in the “Version” field select the correct gsd file 

(3)

before double clicking on “CAN” module 

 

 

 

Содержание HD67446

Страница 1: ...05 C 40 F 221 F For other Gateways Bridges CAN from to Modbus See also the following links www adfweb com product HD67012 Modbus RTU Slave www adfweb com product HD67514 Modbus TCP Master www adfweb c...

Страница 2: ...POLICY 31 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To obtain t...

Страница 3: ...cks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation ass...

Страница 4: ...lectronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET J1939 Converter Document code MN67446_ENG Revision 1 002 Page 4 of 31 EXAMPLE OF...

Страница 5: ...web com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET J1939 Converter Document code MN67446_ENG Revision 1 002 Page 5 of 31 CONNECTION SCHEME Figure 1a Con...

Страница 6: ...vices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET J1939 Converter Document code MN67446_ENG Revision 1 002 Page 6 of 31 Figure 1b Connection s...

Страница 7: ...s or AMP SuperSeal 1 5 connectors If is resined the enclosure like the AMP SuperSeal 1 5 connectors is waterproof IP63 The device have these characteristics Triple 4kV isolation between Power Supply E...

Страница 8: ...8 of 31 POWER SUPPLY The devices can be powered between a wide range of tensions For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax HD67446 Exx xx 8V 26V 10V 40V Consumption at 24V...

Страница 9: ...ous meanings of the LEDs are described in the table below LED Normal Mode Boot Mode 1 Device state green Blinks slowly 1Hz Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 CAN C...

Страница 10: ...the HD67446 E7x xx device must be made with a AMP SuperSeal 1 5 Male connector The pinout of Female connector of the board is at right side of the page The termination of J1939 line with a 120 resisto...

Страница 11: ...norms relative to connections in cat 5 up to 100 Mbps To connect the device to an Hub Switch is recommended the use of a straight cable to connect the device to a PC PLC other is recommended the use o...

Страница 12: ...use the available software that runs with Windows called SW67446 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last ve...

Страница 13: ...ich contains the entire device s configuration A device s configuration can also be imported or exported To clone the configurations of a programmable PROFINET J1939 Converter in order to configure an...

Страница 14: ...re is the possibility to change the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Con...

Страница 15: ...teway that you want to use This feature can be enabled or disabled pressing the Check Box field This feature is used for going out of the net In the field Port the port used for PROFINET communication...

Страница 16: ...to read from PROFINET to J1939 it is an identifier In the field Source Address insert the address of the device that sends the frame If the field Transport Protocol is checked the frame use transport...

Страница 17: ...is 0 or 1 usually is 0 In the field PGN insert the PGN of the data you would like to write from PROFINET to J1939 in J1939 protocol the PGN is an identifier In the field Source Address insert the addr...

Страница 18: ...2 205 Turn on the device Press the Ping button must appear Device Found Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When...

Страница 19: ...epeat the operations for the updating Try with another PC Try to restart the PC Check the LAN settings If you are using the program inside a Virtual Machine try to use in the main Operating System If...

Страница 20: ...lectronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET J1939 Converter Document code MN67446_ENG Revision 1 002 Page 20 of 31 MECHANICA...

Страница 21: ...trial Electronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET J1939 Converter Document code MN67446_ENG Revision 1 002 Page 21 of 31 Ty...

Страница 22: ...trial Electronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET J1939 Converter Document code MN67446_ENG Revision 1 002 Page 22 of 31 Ty...

Страница 23: ...trial Electronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET J1939 Converter Document code MN67446_ENG Revision 1 002 Page 23 of 31 Ty...

Страница 24: ...E y z s f Fixing lugs A Type A B Type B C Type C D without fixing lugs J1939 Termination Y Terminated with 120 N Not terminated Varnished Resinated V Varnished R Resined Connectors Type 4 MiniFit 7 S...

Страница 25: ...2 Page 25 of 31 PLC CONFIGURATION The configuration and commissioning of the PROFINET Converter as described on the following pages was accomplished with the help of the TIA Portal V11 software by Sie...

Страница 26: ...vision 1 002 Page 26 of 31 2 Press the Devices and networks button 1 from the right drop down menu under Other field devices PROFINET IO Gateway ADFWEB com HD67446 double click on MBmaster module 2 No...

Страница 27: ...31 User Manual PROFINET J1939 Converter Document code MN67446_ENG Revision 1 002 Page 27 of 31 3 Connect the PLC to the HD67446 module by drawing the Ethernet wire between the two Ethernet ports Then...

Страница 28: ...e MN67446_ENG Revision 1 002 Page 28 of 31 4 Then doubleclivk on the DNSLAVE label 1 and in the field name change it accordingly to the name defined in the Compositor_SW67446 2 Then add the main modul...

Страница 29: ...c Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET J1939 Converter Document code MN67446_ENG Revision 1 002 Page 29 of 31 5 Load the config...

Страница 30: ...n countries with separate collection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applica...

Страница 31: ...to exchange or repair it please do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about...

Отзывы: