background image

   

Industrial

 

Electronic Devices 

 

 

 ADFweb.com Srl – IT31010 – Mareno – Treviso                                                      INFO:  

www.adfweb.com

      Phone +39.0438.30.91.31            

 

User Manual   

PROFINET / Modbus Master 

 

Document code: MN674-A006_ENG     Revision 1.000  Page 13 of 47 

    Page 13 of 47 

 
RS485: 

 
The connection of the RS485 in the HD674-A006-4-E4x-xx device must be made with a 3way MiniFit 
Female connector. The pinout of Male MiniFit connector of the board is at right side of the page. 
 
The  connection  of  the  RS485  in  the  HD67-A006-4-E7x-xx  device  must  be  made  with  a  AMP 
SuperSeal  1.5  Male  connector.  The  pinout  of  Female  connector  of  the  board  is  at  right  side  of  the 
page. 

 
 

The termination of RS485 line, with a 120Ω resistor, in the HD674-A006-4-Exx-xx is made internally 
of the device; when the order is performed. If the device have the RS485 terminated the code is the 
follow: HD674-A006-4-Exx-Yx; otherwise is this other: HD674-A006-4-Exx-Nx. 
 
The maximum length of the cable should be 1200m (4000 feet). 
 
Here some codes of cables: 

 

Belden: p/n 8132 - 2x 28AWG stranded twisted pairs con foil  braid shield; 

 

Belden p/n 82842 - 2x 24AWG stranded twisted pairs con foil  braid shield; 

 

Tasker: p/n C521 - 1x 24AWG twisted pair con foil  braid shield;

 

 

 

Tasker: p/n C522 - 2x 24AWG twisted pairs con foil  braid shield. 

 
 
 
 
 
 
 
Link for Mini-Fit® connectors: 

http://www.molex.com/molex/products/group?key=minifit_products&channel=products

 

Link for SuperSeal 1.5 connectors: 

http://www.te.com/catalog/cinf/en/c/10876/956

 

Содержание HD674-A006

Страница 1: ...12 Modbus RTU CANopen to Modbus See also the following links www adfweb com Product HD67001 Modbus RTU Master www adfweb com Product HD67002 Modbus RTU Slave www adfweb com Product HD67004 Modbus TCP...

Страница 2: ...R 46 OTHER REGULATIONS AND STANDARDS 46 WARRANTIES AND TECHNICAL SUPPORT 47 RETURN POLICY 47 Pagina 2 di 47 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that y...

Страница 3: ...interlocks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installat...

Страница 4: ...ic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 4 of 47 Page 4 of 47 EXA...

Страница 5: ...l IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 5 of 47 Page 5 of 47 Figure 1a Connection scheme...

Страница 6: ...eb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 6 of 47 Page 6 of 47 Figure 1b Connecti...

Страница 7: ...eb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 7 of 47 Page 7 of 47 Figure 1c Connecti...

Страница 8: ...eb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 8 of 47 Page 8 of 47 Figure 1d Connecti...

Страница 9: ...nnectors or AMP SuperSeal 1 5 connectors If is resined the enclosure like the AMP SuperSeal 1 5 connectors is waterproof All the four series have these characteristics Triple 4kV isolation between Pow...

Страница 10: ...10 of 47 POWER SUPPLY The devices can be powered between a wide range of tensions For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax HD674 A006 Exx xx 8V 26V 10V 40V Consumption at...

Страница 11: ...in the table below LED Normal Mode Boot Mode 1 Device state green Blinks slowly 1Hz Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 Serial Communication green Blinks when Modb...

Страница 12: ...it Female connector The pinout of Male MiniFit connector of the board is at right side of the page The connection of the RS232 in the HD67 A006 2 E7x xx device must be made with a AMP SuperSeal 1 5 Ma...

Страница 13: ...5 line with a 120 resistor in the HD674 A006 4 Exx xx is made internally of the device when the order is performed If the device have the RS485 terminated the code is the follow HD674 A006 4 Exx Yx ot...

Страница 14: ...568 norms relative to connections in cat 5 up to 100 Mbps To connect the device to an Hub Switch is recommended the use of a straight cable to connect the device to a PC PLC other is recommended the u...

Страница 15: ...erter use the available software that runs with Windows called SW674 A006 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the...

Страница 16: ...which contains the entire device s configuration A device s configuration can also be imported or exported To clone the configurations of a programmable PROFINET Modbus Master Converter in order to c...

Страница 17: ...on there is the possibility to change the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the secti...

Страница 18: ...ser Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 18 of 47 Page 18 of 47 In the section Advanced Functions it is possible to send some advanced commands to the convert...

Страница 19: ...nverter is defined In the field PROFINET Gateway the number of byte from the PROFINET to the converter is defined at maximum it is possible to use 1439 byte In the field PROFINET Gateway the number of...

Страница 20: ...e 20 of 47 Page 20 of 47 In the field TimeOut ms the maximum time that the converter attends for the answer from the Slave interrogated is defined In the field Communication Idle Time ms the delay idl...

Страница 21: ...gister to read is defined The following options are available o Coil Status o Input Status o Holding Register o Input Register In the field Address the starting address of the register to read is defi...

Страница 22: ...ting request only when the data from PROFINET change the value In the field Max Error the number of consecutive errors that the converter waits before suspending the poll until the next reboot is defi...

Страница 23: ...ual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 23 of 47 Page 23 of 47 PROFINET XML By Pressing the PROFINET XML button from the main window for SW674 A006 Fig 2 it is poss...

Страница 24: ...sert the IP 192 168 2 205 Press the Ping button Device Found must appear Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When...

Страница 25: ...istance Try to repeat the operations for the updating Try with another PC Try to restart the PC Check the LAN settings If you are using the program inside a Virtual Machine try to use in the main Oper...

Страница 26: ...llow to check the functioning of the converter and send some Modbus commands directly from Ethernet side These commands can be sent directly from the SW674 A006 software using the section Advanced Fun...

Страница 27: ...31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 27 of 47 Page 27 of 47 ERROR POLL NUMBER B2 These section of the software allows to read number of errors receive...

Страница 28: ...software allows to enable disable the Transparent Mode of the converter This Mode is used to send received some serial messages directly from UDP messages The UDP messages will be addressed from to t...

Страница 29: ...ster Document code MN674 A006_ENG Revision 1 000 Page 29 of 47 Page 29 of 47 OTHER COMMANDS B5 B6 These section of the software allows to enable disable the Modbus polling for a specific slave ID and...

Страница 30: ...odbus side REQ Byte 0 B1 bit7 B1 bit6 B1 bit5 B1 bit4 B1 bit3 B1 bit2 B1 bit1 B1 bit0 Bn bitn 0xB0 Poll 0 Poll 1 Poll 2 Pol 3 Poll 4 Poll 5 Poll 6 Poll 7 Poll x 1 Poll disabled 0 Poll enabled If the m...

Страница 31: ...oll 1 Poll 2 Poll x 1 Poll disabled 0 Poll enabled Note In the UDP message after the command s identifier 0xB1 you can read the status of the Modbus Reading requests and then the status of the Modbus...

Страница 32: ...e after the command s identifier 0xB2 you can read the number of errors for the Modbus Reading requests and then for the Modbus writing requests defined in the section Set Access Example We have defin...

Страница 33: ...parent Byte 0 Byte 1 0xB3 Enabling disabling of Transparent Mode 0x01 Poll disabled 0x00 Poll enabled If the message is received correctly the same message will be sent back by the converter Note When...

Страница 34: ...e the polling to a single Modbus slave REQ Byte 0 Byte 1 Byte 2 0xB5 Slave ID 0x00 0x01 0x01 Disable polling for Modbus slave 0x00 Enable polling for Modbus slave If the message is received correctly...

Страница 35: ...le disable a single poll on Modbus side REQ Byte 0 Byte 1 Byte 2 0xB6 Poll No 0x00 0x01 0x01 Disable poll 0x00 Enable poll If the message is received correctly the same message will be sent back by th...

Страница 36: ...t will represent the status of a Modbus request If for a request the converter receives a correct response the status bit is put to 0 If for a request the converter receives a wrong response or it doe...

Страница 37: ...37 of 47 Page 37 of 47 PLC CONFIGURATION The configuration and commissioning of the PROFINET Converter as described on the following pages was accomplished with the help of the TIA Portal V12 software...

Страница 38: ...FO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 38 of 47 Page 38 of 47 2 Import the module in the network connect the devic...

Страница 39: ...s ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 39 of 47 Page 39 of 47 3 Load the...

Страница 40: ...c Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 40 of 47 Page 40 of 47 ME...

Страница 41: ...lectronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 41 of 47 Page 41...

Страница 42: ...lectronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 42 of 47 Page 42...

Страница 43: ...lectronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual PROFINET Modbus Master Document code MN674 A006_ENG Revision 1 000 Page 43 of 47 Page 43...

Страница 44: ...ordering part number is formed by a valid combination of the following HD674 A006 x E y z s f Fixing lugs A Type A B Type B C Type C D without fixing lugs RS485 Termination not present for RS232 versi...

Страница 45: ...de AC34002 Rail DIN Power Supply 110V AC 50 60Hz 12 V AC Order Code AC67402 Cable Super Seal 1 5 MALE 2 pole 1 0 Meter Order Code AC67402 3 Cable Super Seal 1 5 MALE 2 pole 3 0 Meters Order Code AC674...

Страница 46: ...European countries with separate collection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an...

Страница 47: ...wing Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to the address...

Отзывы: