Industrial
Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO:
www.adfweb.com
Phone +39.0438.30.91.31
User Manual
Modbus / CAN - Datalogger
Document code: MN67324_ENG Revision 1.200 Page 14 of 44
CAN:
For terminating the CAN line with a 120Ω resistor it is necessary to put Dip1 of ‘Dip-Switch C’ at ON position.
Cable characteristics:
DC parameter:
Impedance
70 Ohm/m
AC parameters:
Impedance
120 Ohm/m
Delay
5 ns/m
Length
Baud
Rate
[bps]
Length MAX [m]
10 K
5000
20 K
2500
50 K
1000
100 K
650
125 K
500
250 K
250
500 K
100
800 K
50
1000 K
25