If selected “BACnet MS/TP”, the means of the fields for “BACnet” are:
In the field “
Baudrate
” the data rate of the BACnet line is defined;
In the field “
Parity
” the parity of the line is defined;
In the field “
BACnet Device Name
” the name to give to the BACnet node is defined;
In the field “
MAC Address
” the MAC of BACnet node (from 0 to 254) is defined;
The field “
Max Master
” specifies the highest allowable address for master nodes. The value shall
be less than or equal to 127;
The field “
Max Info Frames
” specifies the maximum number of information frames the node may
send before it must pass the token;
In the field “
Device Instance
” the of the BACnet MS/TP side of the converter is defined;
In the field “
Network
” the BACnet MS/TP network number is defined;
If the field “
BACnet description up to 32 chars
” is checked, the description for the BACnet
Objects can be up to 32 chars long.
The means of the fields for the “Ethernet Update” section are:
In the fields “
IP ADDRESS
” the IP address of the converter is defined;
In the fields “
SUBNET
Mask
” the SubNet Mask of the converter is defined;
In the fields “
GATEWAY
” the default gateway of the network is defined. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net.
These information are used for programming the Converter.
Figure 3b: “Set
Communication” window