Add a suitable cleaner, such as 

MC5

®

to the system via the 

RapidFlush

 Filter 

canisters.
If this has already been added, skip this 

step.

Turn ON isolation valves on the 

RapidFlush

 Filter.  Re-fill and pressurise 

the central heating system ensuring the 

radiators are half-full. Check for leaks.

Turn on central heating system. Make 

sure all radiator valves are fully open.  

The radiators should be hot at the 

bottom, cold at the top. Allow system to 

reach temperature (over 70°C).

Turn off any bypass valves and all the 

radiators, ensuring they are FULLY 

closed. Leave the furthest radiator 

open. With the system running, use 

ADEY 

Vibraclean

 tool attached to an 

SDS drill, set to hammer only mode with 

no rotary action, agitate open radiator 

for 15-20 seconds, along the bottom of 

the radiator. Repeat process on each 

radiator, moving from furthest away 

radiator to radiator closest to the boiler.

5

6

7

8

Step-by-step

Remember to monitor the MagnaCleanse throughout operation.

ON 

Содержание MagnaCleanse

Страница 1: ...Advanced Central Heating System Flushing User Guide for Combination and Sealed Systems ...

Страница 2: ...e with care A MagnaCleanse RapidFlush filter MUST be used when carrying out a system flush with a MagnaCleanse Installation of MagnaClean filters and carrying out a system flush with a MagnaCleanse should only be undertaken by competent installers If in any doubt consult a qualified heating engineer Monitor the MagnaCleanse system throughout operation Check jubilee clips are secure before and duri...

Страница 3: ...lter To achieve the best protection for the boiler it is important that the flushing process is carried out with the MagnaCleanse hose to valve connector attached to the return pipe of the system For maximum effect it is recommended that cleaner is added for a minimum of 1 hour MC3 Leave for up to 28 days MC5 Leave for up to 7 days The following instructions are designed to assist engineers in the...

Страница 4: ...or Attach MagnaCleanse HTV connector to the isolation valve on the pipework using the appropriate adaptor Ensure drain valve is in lower hose N B The flow through MagnaCleanse RapidFlush filter should enter the bottom right and exit top left Turn OFF isolation valves on the RapidFlush filter Loosen and remove the lid assembly from one of the RapidFlush filter canisters Removal of black iron oxide ...

Страница 5: ...should be hot at the bottom cold at the top Allow system to reach temperature over 70 C Turn off any bypass valves and all the radiators ensuring they are FULLY closed Leave the furthest radiator open With the system running use ADEY Vibraclean tool attached to an SDS drill set to hammer only mode with no rotary action agitate open radiator for 15 20 seconds along the bottom of the radiator Repeat...

Страница 6: ...s are clean Sludge removal tool available at adeyspares co uk Set the boiler control to OFF Attach a drain hose to the MagnaCleanse drain valve and secure with jubilee clip Turn OFF the HTV connector isolation valve 2 on the return pipe to the boiler leaving the HTV isolation valve 1 open 10 11 12 Check jubilee clips are secure before and during operation Step by step Continue the VibraClean radia...

Страница 7: ...utside until clear When complete fill and vent the radiator and allow to circulate Always open up the next radiator before turning off the cleansed radiator Repeat this process on each radiator until system flushing is complete 13 Turn off the filling loop and HTV connector isolation valve 1 drain and remove MagnaCleanse assembly All the radiators should now be full Reinstall Install the MagnaClea...

Страница 8: ...terial A carbon neutral company For the most up to date version of installation and serving instructions visit www adey com All ADEY marks are trademarks of Adey Holdings 2008 Limited Please visit adey com trademarks for a list of ADEY marks Copyright Adey Holdings 2008 Limited 2019 All rights reserved ...

Отзывы: