![Adesys SVA Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/adesys/sva/sva_manual_2850714012.webp)
Page 12
Manual SVA alarm dialler | Back to
Adesys B.V. | Wateringen
Hardware
4201 4G
4211 4G
Relay output
Relay modes (P/NO/NC)
Imax per output
Switchable voltage level
Life expectancy
0 - 2
1A
SELV 30VDC/1A (resistive)
1 x 10
5
operations at 20°C, 1 Hz
-
Ethernet
Type
10Base-T/ 100Base-TX
Auto MDIX
Yes
GSM/GPRS/EDGE/
LTE Cat-M1
Mobile network
Global-Band FDD-LTE
B1/B2/B3/B4/B5/B8/B12/B13/B17/
B18/B19/B20/B25/B26/B28/B39 (B39
CAT-M1 only)
GSM/GPRS/EDGE 850/900/1800/1900
MHz (Quadband)
Antenna connection
Connector type SMA female
Power supply
Nominal
1-2 Watt (2W whilst the supercap is
charging)
Peak
8.5 Watt / 18 VA (AC)
Imax
0.75A @ Vin= 11.4V
Power supply range
15 ... 35VDC (SELV)
20 ... 30VAC (SELV)
Built-in emergency power supply
Supercap (loaded after a few
minutes) so that a power
failure can still be reported
Expected service life
(Calculated MTBF)
88167 hours (=10 years), according to componentcounting method
Enclosure and operating conditions
Enclosure
DIN rail (TS35) mounting; enclosure fire retardant UL94-V0
Dimmensions (W x H x D)
23 x 95 x 102
(mm)
Weight
125gr
Operating temperature
-20°C ... +50°C
Air humidity
20% - 85% (not condensed)
IP code
IP10
Maximum heigth
Up to 2000 metres
(above 2000 metres the maximum operating
temperature is reduced by 1.5°C per 300 metres up to
a maximum heigth of 4000 metres)
Regulations
EMC
Emission: EN 301 489-01 V1.9.2 & EN 301 489-03 V1.4.1 (Class B)
Immunity: EN 301 489-01 V1.9.2 & EN 301 489-03 V1.4.1(Class A)
Safety (CE)
EN 60950-1 (2006) + A11 (2009) + A1 (2010) + A12 (2011) + AC(2011) + A2
(2013)
Alert functions
Number of dialing
numbers
3 call lists, each containing 8 dialing numbers per call list, maximum of 20
digits per dialing number
Notifications
SMS message or text message over IP IP network