– 40 –
02 START: ACS PT
(00-31) 00
If the start zone type selected was 27 (access point), this prompt
will be displayed. Enter the access point (00-31) which will
start the relay action.
02 START PART
If the starting event will be limited to occurring on a specific
partition, enter the partition number (1-8) in which the start
event will occur. Enter 0 for any partition.
Press [
∗
] to continue.
02 STOP: ZN LIST
NO LIST
If a zone list is being used to stop this relay action, enter the
zone list number 1-8. The restore of a zone on the zone list
will stop the relay. If a zone list is not being used, enter 0.
Press [
∗
] to continue.
02 STOP: ZN TYP
If a Zone Type/System Operation is being used to stop the relay
action, enter the 2-digit code as listed in the “Choices for
Start/Stop Zone Type/System Operation” table.
Press [
∗
] to continue.
02 STOP: ACS PT
(00-31) 00
If the stop zone type selected was 27, (access point), this prompt
will be displayed. Enter the access point (00-31), which will
stop the relay action.
02 STOP PART
This is the partition to which the stop condition will be limited.
Enter 0 for any partition. Enter 1-8 for specific partition
number.
Press [
∗
] to continue.
RELAY GROUP
Relays may be grouped for common activation by time-driven
events (commands 06-10). Enter 0 (no group) or 1-8 for a
specific group number.
Press [
∗
] to continue.
01 FIRE BELL?
1 = YES 0 = NO
If this relay is on a supervised 4204CF Module, it may be used
as an additional fire bell. Enter 1 (Y) if it is; enter 0 if it is not.
This tells the system which relays are to be activated during a
fire drill or Fire Walk-Test.
Press [
∗
] to continue.
RESTRICTION
1=YES 0=NO
The system may have some devices, which are not intended to
be under end user control, such as relays activating fire doors
or machinery. Enter 1 if the end user will be restricted from
accessing this relay group. If this is a fire bell, it will be
restricted automatically.
Press [
∗
] to continue.
RELAY TYPE
Enter 0 for V-Plex (polling loop) devices. Enter 1 for relay
modules (4204/4204CF). Enter 2 for Powerline Carrier devices.
V-PLEX ZONE #
For polling loop trigger outputs (4101SN), enter the protection
zone number (001-128) linked to each output, if used. If not
using a protection zone on these modules, enter the relay zone
number (601-632). Be sure to enroll the module’s serial
number (see Zone Programming prompt earlier in this section).
Press [
∗
] to continue.