12
–
Zone Type Definitions
Type 00
Zone Not Used
Use this zone type if the zone is not used.
Type 01
Entry/Exit Burglary #1
•
Assign to zones that are used for primary entry and exit.
•
Provides entry delay if the control is armed in the Away or Stay modes.
•
No entry delay is provided when the panel is armed in the Instant mode.
•
Entry delay #1 is programmable.
•
Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is
independently programmable.
Type 02
Entry/Exit Burglary #2
•
Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.
•
Provides a secondary entry delay, in same manner as entry delay #1.
•
Entry delay #2 is programmable.
•
Exit delay is same as described for Type 01.
Type 03
Perimeter Burglary
•
Assign to all sensors or contacts on exterior doors and windows.
•
Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, Instant, or
Maximum modes.
Type 04
Interior Follower
•
Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon
entry (to and from the keypad).
•
Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first.
Otherwise this zone type gives an instant alarm.
•
Active when the panel is armed in the Away mode.
•
Bypassed automatically when the panel is armed in the Stay or Instant modes.
Type 05
Trouble by Day/
Alarm by Night
•
Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering a
sensitive area such as a stock room, drug supply room, etc.
•
Can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
•
Provides an instant alarm if faulted when armed in the Away, Stay, Instant or Maximum (night) modes.
•
During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a
central station report, if desired).
Type 06
24-hour Silent Alarm
•
Usually assigned to a zone containing an emergency button.
•
Sends a report to the central station but provides no keypad display or sounding.
Type 07
24-hour Audible Alarm
•
Assign to a zone that has an emergency button.
•
Sends a report to the central station, and provides an alarm sound at the keypad, and an audible external
alarm.
Type 08
24-hour
Auxiliary Alarm
•
Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as water
or temperature sensors.
•
Sends a report to the central station and provides an alarm sound at the keypad.
(No bell output is
provided.)
Type 09
Fire
•
Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a
pulsing bell output.
•
This zone type is always active and cannot be bypassed.
Note:
Hardwired zone 1 should be used with 2-wire smoke detectors; zones 2-8 can be used with 4-wire
smoke detectors; any wireless zone can be used as a fire zone.
Type 10
Interior w/Delay
•
Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away
mode.
•
Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit
delay zone was tripped first.
•
Bypassed when the panel is armed in the Stay or Instant modes.
Type 12
Monitor Zone
•
Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "
ALARM-
24 Hr. Non-Burg. -#XXX
" (where XXX is the zone number) will be sent to the Central Station. The system
keypad will display a “check” message indicating the appropriate zone (but keypad beeping does not
occur). Upon restoral of the zone, the message, "
RESTORE-24 Hr. Non-Burg. -#XXX
" will be sent to the
Central Station.
•
The “check” message will automatically disappear from the keypad dynamically when the zone restores; a
user code + off sequence is not needed to reset the zone.
•
Faults of this zone type are independent of the system, and can exist at the time of arming without
interference.
•
Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.”
Type 14
Carbon Monoxide
•
Assigned to any zone with a carbon monoxide detector.
•
The bell output will pulse when this zone type is alarmed.
•
Always active and cannot be bypassed.
Type 16
Fire w/Verification
•
Provides a fire alarm when zone is shorted, but only after alarm verified.
•
System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit
within 90 seconds triggers fire alarm.
•
Provides a trouble response when zone is open.
Type 20
Arm-Stay
(BR only)
•
Arms the system in Stay mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or disarming.
•
User code for button must be assigned.