Zone Type Definitions 

 

Type 00 

Zone Not Used

 

Use this zone type if the zone is not used.  

Type 01 

Entry/Exit Burglary #1

 

 

   Assign to zones that are used for primary entry and exit. 

   Provides entry delay if the control is armed in the Away or Stay modes.  

   No entry delay is provided when the panel is armed in the Instant mode.  

   Entry delay #1 is programmable. 

   Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is 

independently programmable. 

Type 02 

Entry/Exit Burglary #2

 

   Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.  

   Provides a secondary entry delay, in same manner as entry delay #1.  

   Entry delay #2 is programmable. 

   Exit delay is same as described for Type 01. 

Type 03 

Perimeter Burglary 

   Assign to all sensors or contacts on exterior doors and windows. 

   Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, Instant, or 

Maximum modes.  

Type 04 

Interior Follower 

   Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon 

entry (to and from the keypad). 

   Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first. 

Otherwise this zone type gives an instant alarm.  

   Active when the panel is armed in the Away mode.  

   Bypassed automatically when the panel is armed in the Stay or Instant modes.  

Type 05 

Trouble by Day/ 

Alarm by Night 

   Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering a 

sensitive area such as a stock room, drug supply room, etc.  

   Can also be used on a sensor or contact in an area where immediate notification of an entry is desired. 

   Provides an instant alarm if faulted when armed in the Away, Stay, Instant or Maximum (night) modes.  

   During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a 

central station report, if desired).  

Type 06 

24-hour Silent Alarm 

   Usually assigned to a zone containing an emergency button. 

   Sends a report to the central station but provides no keypad display or sounding.  

Type 07 

24-hour Audible Alarm 

  Assign to a zone that has an emergency button. 

  Sends a report to the central station, and provides an alarm sound at the keypad, and an audible external 

alarm.  

Type 08 

24-hour  

Auxiliary Alarm 

  Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as water 

or temperature sensors. 

  Sends a report to the central station and provides an alarm sound at the keypad. 

(No bell output is 

provided.)

  

Type 09 

Fire 

 

  Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a 

pulsing bell output.  

  This zone type is always active and cannot be bypassed.

  

Note: 

Hardwired zone 1 should be used with 2-wire smoke detectors; zones 2-8 can be used with 4-wire 
smoke detectors; any wireless zone can be used as a fire zone. 

Type 10 

Interior w/Delay 

  Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away 

mode.  

  Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit 

delay zone was tripped first.  

  Bypassed when the panel is armed in the Stay or Instant modes.  

Type 12 

Monitor Zone 

  Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "

ALARM-

24 Hr. Non-Burg. -#XXX 

" (where XXX is the zone number) will be sent to the Central Station. The system 

keypad will display a “check” message indicating the appropriate zone (but keypad beeping does not 
occur). Upon restoral of the zone, the message, "

RESTORE-24 Hr. Non-Burg. -#XXX 

" will be sent to the 

Central Station.  

  The “check” message will automatically disappear from the keypad dynamically when the zone restores; a 

user code + off sequence is not needed to reset the zone.  

  Faults of this zone type are independent of the system, and can exist at the time of arming without 

interference. 

  Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.” 

Type 14 

Carbon Monoxide 

  Assigned to any zone with a carbon monoxide detector.   

  The bell output will pulse when this zone type is alarmed.  

  Always active and cannot be bypassed. 

Type 16 

Fire w/Verification 

  Provides a fire alarm when zone is shorted, but only after alarm verified.  

  System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit 

within 90 seconds triggers fire alarm. 

  Provides a trouble response when zone is open. 

Type 20 

Arm-Stay 
(BR only) 

  Arms the system in Stay mode when the zone is activated.  

  Pushbutton units send the user number to the central station when arming or disarming. 

  User code for button must be assigned.  

Содержание Counterforce CFV15P

Страница 1: ...ogramming Guide ON OFF 1 OFF 4 MAX 7 INSTANT READY 2 AWAY 5 TEST 8 CODE 0 3 STAY 6BYPASS 9CHIME ARMED READY 1 OFF 4 MAX 7INSTANT READY 2 AWAY 5 TEST 8 CODE 0 3 STAY 6BYPASS 9CHIME ARMED READY K5305 7P...

Страница 2: ...s 57 Function Key Programming Unlabeled keypad keys known as ABCD keys for special functions 58 Zone Programming Same options as 56 mode but with fewer prompts Intended for those familiar with Expert...

Страница 3: ...UNDER BELL TIMEOUT 1 0 none 1 4 min 2 8 min 3 12 min 4 16 min UL For residential fire alarm installation must be set for a minimum of 4 min option 1 for UL Commercial Burglary installations must be mi...

Страница 4: ...nt 1 15 secs 2 30 secs etc UL Grade AA must be 0 Grade A must be 15 max 55 DYNAMIC SIGNALING PRIORITY 0 0 Primary Dialer first 1 Long Range Radio first For UL Commercial Burglary installations that us...

Страница 5: ...s option not for use in UL installations 0 assign cross zones on zone list 4 using 81 Menu mode 0 15 seconds 6 2 1 2 min 12 8 min 1 30 seconds 7 3 min 13 10 min 2 45 seconds 8 4 min 14 12 min 3 60 sec...

Страница 6: ...ANDS These are commands not data fields See page 2 PAGER OPTIONS 160 172 160 PAGER 1 PHONE No Enter up to 20 digits 0 9 11 12 13 2 second pause 161 PAGER 1 CHARACTERS Enter the optional prefix charact...

Страница 7: ...rsor back moves forward Press when done to continue TOUCH SCREEN DEVICE ENABLE 189 AUI DEVICE 1 and 2 ENABLE for Touch Screen Style Keypads 1 1 AUI 1 AUI 2 System supports up to two touch screen style...

Страница 8: ...alarms when armed disarmed 1 don t show alarms when armed show alarms trbles faults when disarmed 3 never show any alarms trbles faults 0 no 4 power reset after fault by code OFF 12 verification see...

Страница 9: ...9 BR 50 BR 51 BR 52 BR 53 BR 54 BR 55 BR 56 BR 95 09 01 00 N A N A N A keypad 1 96 08 01 00 N A N A N A keypad 3 99 07 01 00 N A N A N A keypad NOTES Zone Type see definitions on page 12 Hardwire Type...

Страница 10: ...ER DEVICE X 10 MAPPING Must program before using 80 OUTPUT TYPE Relay X10 Output No Module Addr Pos 1 4 Unit No Description 01 02 03 04 05 06 07 08 17 On Board Trigger 1 norm output 18 On Board Trigge...

Страница 11: ...11 12 13 14 15 16 17 18 19 20 21 22 23 24 ZONE TYPE SYSTEM OPERATION Choices for Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 24 Silent Burglary 01 Entry Exit 1 06 24 Hr...

Страница 12: ...keypad and an audible external alarm Type 08 24 hour Auxiliary Alarm Assign to a zone containing an emergency button or to a zone containing monitoring devices such as water or temperature sensors Se...

Страница 13: ...sounding resumes if bell timeout has not expired and reports that were stopped are sent Types 90 91 Installer Defined These zone types can be programmed for various custom responses See data fields 1...

Страница 14: ...53 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKYLIG...

Страница 15: ...5 1 No Response 23 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22 TEMPLATE 3 1 24 hour audible 7 TEMPLATE 6 1 24 hour audible 7 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21...

Страница 16: ...ND OR RING GRAY TIP GREEN RING RED INCOMING PHONE LINE NOT USED ZONE 1 ZONE 2 HI LO HI LO ZONE 3 ZONE 4 HI LO HI LO ZONE 6 HI LO HI LO MAXIMUM LOOP RESISTANCE EACH ZONE 300 OHMS PLUS EOLR RESPONSE ZON...

Отзывы: