Option “4” 

   

 

 

 

Do not use other configurations for Battery Management 

Note (1):  
In Ni-Cd. The End-of-charge is determined by negative 

V detection of battery voltage (-5mV/cell). If no negative 

V but 

only a “flat” profile is detected fast charge is terminated after 10 min. General end-of-charge timeout set to 16 hours. 
Trickle charge current is regulated at 10% of max current set by the trimmer on the front panel in position N°5. In order 
to detect end-of-charge negative 

V, charging current must be set at least at 30% of nominal battery capacity (0,3 C); 

with lower values of charging current negative 

V detection is not guaranteed. 

 
Jumper Setting always active during all states of the system. 

Functional Setting 

Function 

Battery LIFE TEST 

 

ON position = LIFE TEST enabled 

 

Caution: Switch off the system before Setting the Jumper.  

Functional Setting 

Function 

ENABLE POWER 

SUPPLY 

 

ON position = function POWER SUPPLY  
                       enabled 

 

ENABLE POWER SUPPLY function  

With this feature enabled, there is always voltage on the Output BATTERY even if is the battery is not present, in this 
way you don’t have voltage dips, the Battery Care is guaranteed but the controls on the battery are limited. 
Be careful: don’t reverse the battery polarity. 
  

No. 19: Other Battery Management Configurations 

Jumper Setting always active during all states of the system. 

Functional Setting 

                  Function 

FAST CHARGE 

Enable  

 

Fast charge enabled. Only for Lead or Gel 
battery. 

OPTION 

 

  Future implementation 

 

No. 18: SELECTION OUT VOLTAGE 

Caution: Switch off the system before Setting the Jumper. 

Functional Setting 

                  Function 

Output Voltage 

selection  

 

12V Output Voltage 

Output Voltage 

selection 

 

24V Output Voltage 
Default setting 

 
 
 
 
 

LIFE TEST 

ENABLE POWERSUPPLY 

BATTERY TYPE 

F

AS

T

 C

H

AR

G

E

 

O

PT

IO

N

 

12 Vdc 

24 Vdc 

 

P

a

g

e

 7

 -

 C

h

a

p

te

r:

 D

ia

g

n

o

s

ti

c

 T

y

p

e

 C

h

e

c

k

s

 


 

time by  continuously testing the internal impedance  status, avoids  any possible  risk  of  damages and grants  also a 
permanent,  reliable  and  safe  connection  of  the  battery  to  the  power  supply.  The  system,  through  a  battery 
stimulation circuit with algorithms of evaluation of the detected parameter, is able to recognize sulphated batteries or 
batteries with a short-circuited element. 
Battery Test: Automatic. Every 60 sec. check battery connection. Every 220 minute in trickle charge, make the test of 
the battery efficiency. The fault is signaled with relay BATTERY FAULT commutation and DIAGNOSIS led blinking. 

Diagnostic Type Checks  
Check for accidental disconnection of the battery cables: 

All In One detects accidental disconnection and immediately switched off the output BATTERY. 

Battery not connected: 

If the battery is not connected no output BATTERY. 

Test of quality wire connections: 

During trickle charge the quality (resistance) on the battery connection is checked every 20 sec. This to detect if the 
cable connection has been properly made. 

Battery in Open Circuit or Sulphated: 

Every 220 minute. All In One tests of internal impedance, in trickle charging mode. 

Reverse Polarity check: 

If the battery it is connected with inverted polarity, All In One is automatically protected. 

Test of battery voltage: 

Appropriate voltage check, to prevent connection of wrong battery types, more or less than the nominal voltage. 

End of Charge check:

 

When the battery it is completely full, the device automatically switch in trickle charging mode. 

Check for Battery Cells in short circuit : 

 

Thanks to specific algorithms of evaluation, the CBI recognize batteries with cells in internal short circuit. 
In trickle charge every 2 hours test of element in short circuit. 

Diagnosis of battery and device: 

All  CBI  devices  support  the  user  during  installation  and  operation.  A  Blink  code  of  Led  DIAGNOSIS  allows  to 
discriminate among various possible faults. 
Error  conditions,  “Led  BATTERY  FAULT”  ON  and  “Led  DIAGNOSIS”  blinking  with  sequence;  see  Display  Signal 
section. 

Charging Curve: 

Automatic  multi-stage  operation  and  real  time  diagnostic  allows  fast  recharge  and  recovery  of  deep  discharged 
batteries, adding value and reliability to the system hosting the CBI device. The type of charging is Voltages stabilized 
and Current stabilized IUoUo. 
Four charging modes are identified by a flashing code on a Diagnosis LED. 
To maintain the Output Load in lower Voltage state, don’t put jumper FAST CHARGE, in this case no boost charge but 
only Float charge. 

 

State 

Diagnosis LED 

Battery Fault LED 

Charging Type 

Trickle-Float 

1 Blink/2sec 

OFF 

Absorption 

1 Blink/sec 

OFF 

Boost-Bulk 

2 Blink/sec 

OFF 

Recovery 

5 Blink/sec 

OFF 

 

 

P

a

g

e

 6

 -

 C

h

a

p

te

r:

 B

a

tt

e

ry

 C

a

re

 


 

No. 15: BUS TERMINATION 

Caution: Switch off the system before Setting the Jumper. 
Read the MODBUS/CANBUS instruction manual to learn about the operational functions available. 
 
Jumper Setting always active during alla states of the system. 

Functional Setting 

Bus termination 

 

No. 5: CHARGING LEVEL Current:

 

 
 
It is possible set the max recharging current for the batteries by trimmer (Battery Charging 
Level). The current adjustment goes from 20% ÷ 100% of In. Set the maximum charging 
current between 10% and 20% of the battery capacity. 
 
 

No. 11: Auxiliary Output “AUX 1” 

RJ 11 behind the label, remove the window label to find the connector. 
It is possible connect:  

 

Temperature sensor, for ambient temperature charging   

       compensation.  With this it  is  possible  to  active   the  
       specifications  of  the  EN54-4  firing  norm. 

Compensation Recharges in temperature  

Connecting to RJ11 AUX1 Auxiliary Output the cable RJTEMP11 (supplied separately), the CBI will vary the voltage of 
battery charging depending on the temperature: 

 

Fast Charge 

Trickle charge 

 +/-5mV/°C x n. of Cells  from -8°C to +60°C 

+140mV/Cell ÷ -200mV/Cell compared to the value 
at 20°C 

+/-3mV/°C x n. of Cells from -20°C to +60°C 
+120mV/Cell ÷ -120mV/Cell compared to the value 
at 20°C 

 

If the temperature is less than -20°C or greater than +60°C alarm is signalled with code 7 blink.

 

The sensor place on cable RJTEMP11 must be applied on the battery. 
If the sensor is not connected or if the sensor is defective, the led Low Batt is on and the led Diagnosis continues to 
show the status of the battery: trickle charge, fast charge or recovery charge. 

No. 13: TIME BUFFERING Setting 

Time buffering it is  enabled  when  the  Input main is  switched  OFF. It is  possible  setting by  the position of  the  rotate 
switch TIME BUFFERING. 
The output LOAD time ON depending on position of the Switch. 
Switch positions: 

Switch position 

Time Buffering (min.) 

 

0.5 

10 

15 

20 

30 

45 

60 

If the switch is in 0 position the Time Buffering maintain ON state until the battery it is completed discharged. Anyway 
to prevent risk of damage, the product disconnect the batteries when a minimum voltage level is reached. 

No. 14: Auxiliary Output “AUX 2” 

Connection MODBUS/CANBUS via RJ45 connector. See instruction for MODBUS communication protocol. (CANBUS 
to be implemented) 

No. 15: Auxiliary Output “AUX 3” 

Connection MODBUS/CANBUS via RJ45 connector. See instruction for MODBUS communication protocol. (CANBUS 
to be implemented) 

Battery Care 

The  Battery  Care  philosophy  is  base  on  algorithms  that  implement  rapid  and  automatic  charging,  battery  charge 
optimization  during  time,  flat  batteries  recovery  and  real  time  diagnostic  during  installation  and  operation.  The  Real 
Time Auto-diagnostic  system, monitoring  battery faults  such  as,  elements  in  short circuit,  accidental  reverse  polarity 
connection, disconnection of the battery, they can easily be detected and removed by help of Blink Code of Diagnosis 
Led; during the installation and after sell. Each device is suited for all battery types, by means of jumpers it is possible 
setting predefined curves for Open Lead Acid, Sealed Lead Acid, Gel and Ni-Cd. They guarantees battery reliability in 

 

P

a

g

e

 8

 -

 C

h

a

p

te

r:

 P

ro

te

c

ti

o

n

 F

e

a

tu

re

s

 


 

Protection Features 

On  the  primary  side:  the  device  is  equipped  whit  an  internally  fuse.  If  the  internal  fuse  is  activated,  it  is  most 
probable that there is a fault in the device. If happen, the device must be checked in the factory. 
 
On  the  secondary  side  BATTERY  and  LOAD:  The  device  is  electrically  protected  against  short  circuits  and 
overload. 
Inversion polarity:  the module  it is  automatically  protected  against  inversion  of  battery  polarity  and  connection of 
load inverted. 
Over current and output short circuit:  the unit limits the output current (see the technical data). 
Deep discharge : not possible. The unit disconnects the battery when a minimum voltage level is reached. 

Thermal behaviour 

Surrounding  air  temperature  50°C.  For  ambient  temperature  of  over  50°C,  the  output  current  must  be  reduced  by 
2.5%  per  °C.  Max  70°C  At  the  temperature  of  70°C  the  output  current  will  be  50%  of  In.  The  equipment  does  not 
switch  off  in  case  of  ambient  temperature  above  70°C  or  thermal  overload.  The  devices  are  protected  for  Over 
temperature conditions “worst case”; in this situations the device Shut-down the output and automatic restart when 
temperature inside fall. 

Standards and Certification 

Electrical Safety: 
Assembling device: UL508, IEC/EN 60950 (VDE 0805) and EN 50178 (VDE 0160). 
Installation according: IEC/EN 60950. 
Input / Output separation: SELV EN 60950-1 and PELV EN 60204-1. Double or reinforced insulation. 
EMC Standards Immunity: 
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5. 
EMC Standards Emission: 
EN 61000-6-4, EN 61000-6-3, EN 61000-3-2  
Standards Conformity: 
Safety of Electrical Equipment Machines: EN 60204-1. 

 The CE mark in According to EMC 2004/108/EC and Low voltage directive 2006/95/EEC 

Norms and Certifications 

In  Conformity  to:  IEC/EN  60335-2-29  Battery  chargers;  EN60950  /  UL1950;  Electrical  safety  EN54-4  Fire  Detection 
and  fire  alarm  systems;  89/336/EEC  EMC  Directive;  2006/95/EC  (Low  Voltage);  DIN41773  (Charging  cycle); 
Emission: IEC 61000-6-4; Immunity:  IEC 61000-6-2. CE. 

Rail Mounting: 

 

All modules must have a minimum vertical and horizontal distance of 10 cm to this power supply in order to 
guarantee  sufficient  auto  convection.  Depending  on  the  ambient temperature  and  load  of the  device, the 
temperature of the housing can become very high! 
 

 

 

Содержание CBI-1280 Series

Страница 1: ...the load until the battery voltage reaches 1 5 V per cell This prevents the battery from deep discharge CBI devices provide microprocessor controlled battery charging Using algorithms the battery s co...

Страница 2: ...xtra power to support the load in case one power supply unit fails The simplest way is to put two CBI in parallel In case one power supply unit fails the other one is automatically able to support the...

Страница 3: ...xtra power to support the load in case one power supply unit fails The simplest way is to put two CBI in parallel In case one power supply unit fails the other one is automatically able to support the...

Страница 4: ...xtra power to support the load in case one power supply unit fails The simplest way is to put two CBI in parallel In case one power supply unit fails the other one is automatically able to support the...

Страница 5: ...xtra power to support the load in case one power supply unit fails The simplest way is to put two CBI in parallel In case one power supply unit fails the other one is automatically able to support the...

Страница 6: ...ging current for the batteries by trimmer Battery Charging Level The current adjustment goes from 20 100 of In Set the maximum charging current between 10 and 20 of the battery capacity No 11 Auxiliar...

Страница 7: ...ging current for the batteries by trimmer Battery Charging Level The current adjustment goes from 20 100 of In Set the maximum charging current between 10 and 20 of the battery capacity No 11 Auxiliar...

Страница 8: ...ging current for the batteries by trimmer Battery Charging Level The current adjustment goes from 20 100 of In Set the maximum charging current between 10 and 20 of the battery capacity No 11 Auxiliar...

Страница 9: ...ging current for the batteries by trimmer Battery Charging Level The current adjustment goes from 20 100 of In Set the maximum charging current between 10 and 20 of the battery capacity No 11 Auxiliar...

Страница 10: ...apacitive load Start up con carichi capacitivi Yes Unlimited Residual Ripple Ripple Residuo 60mVpp Charging max Ibatt Corrente max di Carica 15A 5 12Vdc 10A 5 24Vdc T 40 C In Charging current Limiting...