Adel CB123A/48 Скачать руководство пользователя страница 3

_________________________________________________________Battery Charger 

 

All specification are subject to change without notice

 

 

      

INSTRUCTION MANUAL

                                                                                             3 

CB123A_48_A24.AAA.015A1_R1_Eng 

 

 

Battery Type Configurations 

 

Caution:  

Switch  off  the  system  before  Setting 
the jumper.

 

 
 
Jumpers positions for charging: 

0.

 

Open Lead

: Fast=2.40V/cell 

Trickle=2.23V/cell   

NiCd

: Fast=Imax, 16 hours max 

Trickle=20% Imax

 

 

1.

 

Sealed Lead

: Fast=2.40V/cell 

Trickle=2.25V/cell   

NiCd

: Fast=Imax, 12 hours max 

Trickle=15% Imax

 

 

 
 
 
 
 
 
 
 
 

 

2.

 

Sealed Lead

: Fast=2.40V/cell 

Trickle=2.27V/cell   

NiCd

: Fast=Imax, 8 hours max 

Trickle=10% Imax

 

 

 

3.

 

Gel Battery

: Fast=2.40V/cell 

Trickle=2.30V/cell   

NiCd

: Fast=Imax, 4 hours max 

Trickle=5% Imax

 

 

 

 

Cable connection 

The following cable cross-sections may be used: 

At the Input:

 0.2÷2.5 mm

rigid / flexible  

At the Output:

 0.2÷2.5 mm

rigid / flexible 

Strip the connection ends: 7mm 

Input: 

The input connection is made by the screw connections -, +, 

.  

Protection 

On the primary side:

 the device is equipped whit a internally fuse T 4 A. If the internal fuse is activated, 

it is  most probable  that there is a fault in the device. If happen, the device must 
be checked in the factory 

 

On the secondary side Battery and load:

 The device is electrically protected against short circuits and 

overload. 

Inversion polarity:

 the module is protected against inversion of battery polarity. 

Over current and output short circuit:

 the unit limits the output power at max. 36W in normal rating.

 

Battery Test:

 Automatic. Check polarity and battery. Every 4 hours in trickle charge, make the test of the 

battery quality. The fault is signalized with relay commutation and diagnosis led blinking.

 

 
Short circuit and overload 

The output current to the battery is selected with the Charge Level trimmer. The maximum power 

– load 

of 36W limits the current to the battery.  
 

Thermal behavior 

The  device  supplies  the  nominal  output  current  at  ambient  temperature  of  up  50°C.  For  ambient 
temperature of over 50°C, the output current must be reduced by 2.5 % per °C increase in temperature. 
Max 70°C. 

 

Standards and Certification 

Electrical safety 

The device must be installed in according with EN60950. The device must have a suitable isolating facility 
outside the power supply unit, via which can be switched to idle. Safety EN IEC 62368-1 

 General Standard 

Emission : EN61000-6-4 
Immunity: EN61000-6-2 

1  2  3 

Battery 
 Type 

1  2  3 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Battery 
 Type 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1  2  3 

Battery 
 Type 

1  2  3 

Battery 
 Type 

Отзывы: