_________________________________________________________Battery Charger 

 

All specification are subject to change without notice

 

 

      

INSTRUCTION MANUAL

                                                                                             3 

CB123A_LC_R4 Eng.doc 

 

Battery Type Configurations 

 

Caution:  

Switch off the system before Setting 
the jumper.

 

 
 
Jumpers positions for charging: 

0.

 

Open Lead

: Fast=2.40V/cell 

Trickle=2.23V/cell   

NiCd

: Fast=Imax, 16 hours max  Trickle=20% Imax

 

 

1.

 

Sealed Lead

: Fast=2.40V/cell 

Trickle=2.25V/cell   

NiCd

: Fast=Imax, 12 hours max  Trickle=15% Imax

 

 

 

 
 
 
 
 
 

 
 

 

2.

 

Sealed Lead

: Fast=2.40V/cell 

Trickle=2.27V/cell   

NiCd

: Fast=Imax, 8 hours max Trickle=10% 

Imax

 

 

 

3.

 

Gel Battery

: Fast=2.40V/cell 

Trickle=2.30V/cell   

NiCd

: Fast=Imax, 4 hours max Trickle=5% 

Imax

 

 

 

 

Cable connection 

The following cable cross-sections may be used: 

At the Input:

 0.2÷2.5 mm

rigid / flexible  

At the Output:

 0.2÷2.5 mm

rigid / flexible 

Strip the connection ends: 7mm 

Input: 

The input connection is made by the screw connections L, N, PE

.  

Protection 

On the primary side:

 the device is equipped whit a internally fuse T 4 A/250Vac. If the internal fuse is 

activated, it is most probable that there is a fault in the device. If happen, the 
device must be checked in the factory 

 

On the secondary side Battery and load:

 The device is electrically protected against short circuits and 

overload. 

Inversion polarity:

 the module is protected against inversion of battery polarity. 

Over current and output short circuit:

 the unit limits the output power at max. 36W in normal rating.

 

Battery Test:

 Automatic. Check polarity and battery. Every 4 hours in trickle charge, make the test of the 

battery quality. The fault is signalized with relay commutation and diagnosis led blinking.

 

 
Short circuit and overload 

The output current to the battery is selected with the Charge Level trimmer. The maximum power – load 
of 36W limits the current to the battery.  
 

Thermal behavior 

The device supplies the nominal output current at ambient temperature of up 50°C. For ambient 
temperature of over 50°C, the output current must be reduced by 1% per °C increase in temperature. Max 
60°C. 

 

Standards and Certification 

Electrical safety 

The device must be installed in according with EN60950. The device must have a suitable isolating facility 
outside the power supply unit, via which can be switched to idle. 

 General Standard 

Immunity in according with EN50082-2, level 3, class B 
Radio interference suppression in according with EN 55011 class A (industrial areas) 

1 2 3 

Battery 
 Type 

1 2 3 

Battery 
 Type 

1 2 3

Battery
 Type 

1 2 3

Battery
 Type 