5. If connecting bare wire, wrap the bare wire around the contact in a clockwise direction.

6. Tighten the screws to approximately 9 pound-force inches (1 Newton meter) of torque.

7. Terminate the other ends of the wires at the appropriate terminals in the external alarm

system.

Figure 15. Alarm Terminals

4.10 Connecting Output

Output power is supplied to the protected equipment through the output power screw-down
terminal strips located on the rear of the panel. Wire leads should be equipped with crimp-on
spade lugs or ring connectors that have a minimum width of 0.32 inches (81.3 mm). The
terminals also accommodate copper wire without lugs (insulation stripped back). The terminals
can accept a variety of wire sizes up to #12 AWG with crimp-on spade lug or ring connectors or
wires in sizes from #12 AWG to #22 AWG with insulation stripped back. Follow local code. In
selecting wire size, refer to 

Appendix  A

.

.

1. Obtain the required lengths of wire for use as the output power cables.

2. Equip wire leads with spade or ring-type compression lugs (maximum width 0.32 inches)

or prepare a bare wire contact.

Caution: 

Connecting the equipment to the wrong circuit may cause damage to the

equipment or the circuit breaker panel.

SCREW-DOWN TERMINAL

ALARM CONNECTIONS

20641-A

SCREW-DOWN TERMINAL

CONNECTIONS FOR

REMOTE ALARMS

Содержание PowerWorx Circuit Breaker Panel With Reset Switch

Страница 1: ...ADCP 80 570 Issue 2 March 2006 1361499 Rev A PowerWorx Power Distribution Products Circuit Breaker Panel With Reset Switch User Manual 20629 A...

Страница 2: ...further disclaims any and all liability for indirect incidental special consequential or other similar damages This disclaimer of liability applies to all products publications and services during and...

Страница 3: ...dicators 6 1 12 Breaker Alarm Indicators 7 1 13 Alarm Operation 7 1 14 Alarm Connections 7 1 15 Reset Switch 7 1 16 Circuit Breaker Designation Card and Holder 7 1 17 Voltage Designation Label 8 1 18...

Страница 4: ...s 23 5 TESTING 24 5 1 Testing Power Indicators and Connection Polarity 24 5 2 Testing Alarm Contacts Normal State 24 6 OPERATION 25 6 1 Connecting New Equipment 25 6 2 Using the Reset Switch 26 7 MAIN...

Страница 5: ...th or substantial property damage if the hazard is not avoided Warning Warning is used to indicate the presence of a hazard that can cause severe personal injury death or substantial property damage i...

Страница 6: ...mended ambient temperature of 55 C Warning Stability hazard The rack stabilizing mechanism must be in place or the rack must be bolted to the floor before you slide the unit out for servicing Failure...

Страница 7: ...breakers and five 5 Amp circuit breakers Maximum input rating of 45 Amps per bus This corresponds to a maximum input rating of 90 Amps for the total panel One Power On LED green and one Breaker Alarm...

Страница 8: ...OR RED LED BUS B ALARM INDICATOR RED LED BUS A 1 TO 7 CIRCUIT BREAKERS BUS B 1 TO 7 CIRCUIT BREAKERS FRONT VIEW REAR VIEW 20631 A COVER FOR OUTPUT POWER TERMINALS COVER FOR INPUT POWER TERMINALS ALARM...

Страница 9: ...ts to the equipment rack 10 ring terminals 2 for 12 10 AWG wire Can be used to connect the grounding cables to the grounding studs 2 Hole Lugs for 6 AWG wire 4 Used to connect input power cable to inp...

Страница 10: ...is 48 or 24 Vdc 1 4 Power Buses Each circuit breaker panel has two isolated power buses Each bus distributes the input power to the output power circuits In each bus circuit current flows from the inp...

Страница 11: ...m studs with nuts mounted on a plastic terminal block Each pair of studs can accept different size 2 hole compression lugs used with a range of wire sizes up to 6 AWG copper wire Two 2 hole lugs per b...

Страница 12: ...eplaceable 60 Vdc rated circuit breakers with finger guard and amperage markings Each power bus has two 10 Amp breakers and five 5 Amp breakers The maximum capacity per bus is 45 Amps The circuit brea...

Страница 13: ...eturn to a normal operational state The maximum current rating for each set of alarm relay contacts is 1 0 Amp 1 14 Alarm Connections The panel has a screw down barrier terminal strip for the alarm re...

Страница 14: ...l voltage present on the buses and placed on the panel The voltage designation label has a pressure sensitive adhesive backing for attachment Figure 5 Voltage Designation Label 1 18 Material and Finis...

Страница 15: ...101 6 mm from the front of the rack The mounting holes are slotted to permit installation in racks with WECO 1 00 inch 2 54 cm hole spacing or EIA 1 25 inch 3 18 cm hole spacing The following mountin...

Страница 16: ...s 90 Amps max per panel Circuit breaker rating 5 or 10 Amps Positions are labeled Circuit breaker positions 7 per bus 14 per panel Max circuit breaker size 10 Amps rating 45 Amps per bus Input termina...

Страница 17: ...rm contacts 9 pound force inches 1 Newton meter Input power terminal nuts 32 pound force inches max 3 5 Newton meters max Output power terminal screws 12 pound force inches max 1 3 Newton meters max G...

Страница 18: ...ion and Assistance at the back of this manual for repair replacement and warranty information Save all shipping containers for use if the equipment requires return shipment at a future date 4 INSTALLA...

Страница 19: ...mper Multimeter Heat gun 4 2 Materials Required The following materials are required to install the circuit breaker panel Insulated copper wire for input and output power wires see Appendix A Heat shr...

Страница 20: ...the output terminal for circuit 1 connect the negative test probe to the bus A input BATT power terminal and the positive test probe to bus A output BATT power terminal for the circuit being tested Fi...

Страница 21: ...ity exists between the C and NC terminals Figure 10 Figure 10 Test 4 Alarm Contacts 2 Connect the test probes between the C and NO terminals on the first set of alarm terminals Verify that continuity...

Страница 22: ...her a 19 or 23 inch 48 26 or 58 42 cm wide rack using the 1 75 inch high 4 45 cm 19 or 23 inch rack mounting brackets The brackets mounting screws and washers are provided with the panel Note The cabl...

Страница 23: ...the four 3 8 inch 9 525 mm long 12 24 pan head screws and 12 flat washers provided use star washers when required by local practice Tighten the screws to 27 pound force inches 3 1 Newton meters of tor...

Страница 24: ...desired and insert it in the card holder 4 7 Installing Voltage Designation Label Write the voltage used in the circuit breaker panel on the voltage designation label see Figure 5 on page 8 and attach...

Страница 25: ...n accept 16 to 30 AWG solid copper either with crimp on spade lugs or ring connectors or without lugs with insulation stripped back Use the following procedure to connect an external alarm system to t...

Страница 26: ...ring connectors that have a minimum width of 0 32 inches 81 3 mm The terminals also accommodate copper wire without lugs insulation stripped back The terminals can accept a variety of wire sizes up t...

Страница 27: ...nel Each block consists of two pairs of 0 25 inch studs that are used for connecting the negative BATT and positive RTN input power cables The stud pairs are mounted on 0 625 inch centers and accept 2...

Страница 28: ...NEG or and or the voltage value to the connector on the circuit breaker panel labeled BATT battery Connect only the input return wire labeled RTN RETURN POSITIVE POS or BATTERY GROUND to the connecto...

Страница 29: ...nuts to 32 pound force inches 3 6 Newton meters maximum of torque 11 Route the free ends of the input power cables to the office battery source 12 Connect the input power cables to the office battery...

Страница 30: ...d If this appears to be true power down the panel Disconnect the negative BATT and positive RTN input lugs and switch them around Power up the panel and check again to verify that the higher voltage i...

Страница 31: ...accommodate copper wire without lugs insulation stripped back The terminals can accept a variety of wire sizes up to 12 AWG with crimp on spade lug or ring connectors or wires in sizes from 12 AWG to...

Страница 32: ...any circuit breaker is broken or damaged replace the circuit breaker 7 2 Replacing a Circuit Breaker Any existing circuit breaker may be field replaced with an identical circuit breaker or with a brea...

Страница 33: ...ker from snapping back into the panel when the screwdriver is withdrawn from the slot 6 Insert a flat bladed screwdriver into the slot below the circuit breaker 7 Push down and forward on the lower ci...

Страница 34: ...ed as shown the black load wire connects to the top terminal and the white power wire connects to the bottom LINE terminal 11 Connect the two alarm wires to the specified terminals on the rear side of...

Страница 35: ...ension 73475 Wireless Extension 73476 ASIA PACIFIC Sales Administration 65 6294 9948 Technical Assistance 65 6393 0739 ELSEWHERE Sales Administration 1 952 938 8080 Technical Assistance 1 952 917 3475...

Страница 36: ...ADCP 80 570 Issue 2 March 2006 Page 30 2006 ADC Telecommunications Inc...

Страница 37: ...Table 310 16 NEC Allowable Ampacities of Insulated Conductors Rated O Through 2000 Volts 60 to 90 C 140 to 194 F Not More Than Three Current Carrying Conductors in Raceway or Cable or Earth Directly B...

Страница 38: ...50 735 2000 560 665 750 CORRECTION FACTORS For ambient temperatures other than 30C 86F multiply the allowable ampacities shown by the appropriate factor shown below 21 25 1 08 1 05 1 04 26 30 1 00 1 0...

Страница 39: ......

Страница 40: ...i www adc com...

Отзывы: