ADCP-80-353 • Issue 2 • August 2002 • Section 2: Installation
Page 2-1
©
2002, ADC Telecommunications, Inc.
SECTION 2: INSTALLATION
_________________________________________________________________________________________________________
1
GENERAL
This
section provides complete instructions for installing the DSX-3 (DSX-4U-24) Rear Cross-
Connect
System. It is recommended that the entire section be read and understood before
beginning
installation.
2
OFFICE REQUIREMENTS
2.1
Space and Floor Loading
The
cross-connect system consists of up to 240 circuit modules mounted in a standard 2.13 m
×
48.26
cm (7-foot
×
19-inch) unequal flange equipment bay. Maximum width of the bay is 55.72 cm
(21.94
inches), and maximum depth is 30.47 cm (12 inches). A fully configured unwired/uncabled
cross-connect
system bay weighs approximately 163 kg (360 pounds).
2.2
Environment
2.2.1
Shipping and Storage
The
cross-connect system must be shipped and stored in ambient temperatures and humidities
which
do not exceed the following:
• Temperature:
–55
°
to +85
°
C (–67
°
to +185
°
F).
• Relative
Humidity: 0% to 95% without condensation.