background image

1 2 3 4

5

6 7

8

9

11

10

12

Horizontal installation

Vertical installation

Cold water

Hot water

CONNECTION

Essential instructions for the safety of persons and the environment
• 

Refer to the safety instructions for the installation. Failure to comply with these 

instructions can result in damages to the system, severe injuries or death.

• 

Hot water can burn! ACV recommends using a pre- set thermostatic mixing 

valve in order to provide hot water at a maximum of 60°C.

Essential instructions for the correct operation of the system
• 

The filling circuit of the DHW tank must be equipped with a safety group, 

comprised at least of a stop valve, a check valve, a safety valve set at 7 bar, and 

possibly, an expansion vessel of the appropriate size. Make sure that the circuit 

between the tank and the safety valve is always open.

• 

The third DHW tank connection, if any, can be used for the auxiliary DHW loop. 

If the connection is not used, replace the protective plug by a brass plug of the 

appropriate size. 

General remarks
• 

In certain countries the domestic kits must be approved.

• 

The circuit illustrations are basic principle diagrams only.

CONNECTION TO THE  DHW CIRCUIT (Typical wall installation)

Key

 1.  Filling valve
 2.  Pressure reducing valve (set at 4.5 bar)
 3.  Check valve
 4.  Stop valve

 5.  DHW expansion vessel
 6.  Pressure gauge

 7.  Safety valve (set at 7 bar)

 8.  Drain valve
 9.  Grounding
 10.  Stop  valve
11. Thermostatic mixing valve
12.  Hot water outlet

Smart Green : A1009652 - 661Y3000 • D

Installation

AVAILABLE KITS AND ACCESSORIES

Domestic hot water kit

 

A. 

Thermostatic mixing valve

 

B. 

Mixed water outlet

 

C. 

Cold water inlet

 

D. 

Drain connection

 

E. 

Expansion vessel connection

 

S. 

Safety unit

 

TH.  Outlet hot water tank

 

TC.  Inlet cold water tank

FLOOR MOUNTING

A

B

E

C

TC

TH

S

D

15

EN

Содержание Smart Green 130

Страница 1: ...Smart Green 130 160 210 Installation Operation Maintenance Instructions for the User and the Installer A1009652 661Y3000 D...

Страница 2: ...RIPTION 7 Models Smart 130 160 210 Green 7 TECHNICAL CHARACTERISTICS 8 Dimensions and Main Characteristics 8 Electrical Characteristics 10 Performance 11 INSTALLATION 12 Safety Instructions 13 Packing...

Страница 3: ...Smart Green A1009652 661Y3000 D Table of Contents MAINTENANCE 21 Periodic Checks by the User 21 Annual Maintenance 21 Draining 22 Bringing back into Service after Maintenance 22 3 EN...

Страница 4: ...y only be replaced by genuine parts Our water heaters are designed and manufactured for the exclusive purpose of heating and storing domestic hot water The domestic hot water heaters must only be heat...

Страница 5: ...Smart Green A1009652 661Y3000 D Product Information ENERGY LABELLING 5 EN...

Страница 6: ...Smart Green A1009652 661Y3000 D Product Information RATING PLATE EN 6...

Страница 7: ...ss and improved energy efficiency 7 EN 1 Polypropylene top lid 2 Stainless steel tank DHW 3 Vacuum insulation panel 4 Dry well 5 Polypropylene shell 6 Polypropylene bottom lid 7 Outer steel tank prima...

Страница 8: ...61Y3000 D Technical Characteristics DIMENSIONS AND MAIN CHARACTERISTICS Tank dimensions Smart Green 130 160 210 A mm 1025 1225 1497 B mm 760 960 1232 C mm 235 235 235 Empty weight Kg 55 65 75 EN 8 A B...

Страница 9: ...10 10 Reheat Performance Primary Hea ting Power Input kW 24 7 32 2 39 2 Primary flow rate to achieve Reheat Performance L sec 0 70 0 70 1 25 Reheat time min 10 10 9 Standing Heat Loss kWh 24h 0 84 0 9...

Страница 10: ...10 Rated voltage V 230 230 230 Rated frequency Hz 50 50 50 Max Amp rating A 6 6 6 ELECTRICAL CHARACTERISTICS Wiring diagram 1 Control thermostat 60 80 C 2 Circulator pump option B Blue Bk Black Br Bro...

Страница 11: ...ak flow at 45 C L 10 275 348 469 Peak flow at 60 C L 10 161 209 272 Peak flow first hour at 45 C L 60 911 1156 1560 Peak flow first hour at 60 C L 60 549 689 913 Constant flow at 45 C L h 763 970 1309...

Страница 12: ...sion connect the stainless steel tank directly to the earth Use an adjustable earth clamp see example below on one of the DHW connections to connect to the earth Advised copper wire section 2 5mm Make...

Страница 13: ...teria exists including Legionella pneumophila if a minimum temperature of 60 C is not maintained in both the DHW tank and the hot water distribution network Essential instructions for the electrical s...

Страница 14: ...Package One Smart Green hot water tank Multilingual Installation Operation and Maintenance Instructions One energy label PACKING CONTENTS All appliances are delivered tested and packaged separately T...

Страница 15: ...tank and the safety valve is always open The third DHW tank connection if any can be used for the auxiliary DHW loop If the connection is not used replace the protective plug by a brass plug of the ap...

Страница 16: ...5 Safety valve set at 7 bar 6 Drain valve 7 Hot water outlet 8 Pressure gauge 9 Grounding 10 Stop valve 11 Thermostatic mixing valve CONNECTION TO THE PRIMARY CIRCUIT Typical floor installation Key 1...

Страница 17: ...to the ratio recommended in the local regulations Consult the manufacturer to determine the compatibility of the antifreeze with the tank s construction materials Essential instructions for the correc...

Страница 18: ...ARY CIRCUIT Figure 2 General remark If the tank is used within a heating system refer to the heating boiler manual 1 Check that the drain valve 3 of your primary circuit is tightly closed 2 Open the s...

Страница 19: ...Figure 1 Figure 2 1 3 3 2 2 4 2 3 1 1 Cold water Hot water Smart Green A1009652 661Y3000 D Starting Up 19 EN...

Страница 20: ...t the tank s upper air bleed valve is tight Check that the water side and heat source side pipes are correctly connected and not leaking STARTING UP To put the installation into service refer to the h...

Страница 21: ...y unit drips periodically it may be due to an expansion problem or clogging of the valve For internal inspections the hand hole can be used If there is none use one of the water connections to insert...

Страница 22: ...rcuit of the hot water heater 1 Stop the charging pump 2 Isolate the primary circuit by closing the stop valves 1 3 Connect the drain valve 2 to the sewer using a flexible hose 4 Open the drain valve...

Страница 23: ...Figure 3 Figure 4 4 1 2 3 Cold water Hot water 1 1 2 3 Smart Green A1009652 661Y3000 D Maintenance 23 EN...