High efficiency combination boilers
15
Technical Data
Performance Data
HeatMaster®60
HeatMaster®60
Fuel
Oil (28 sec or 35 sec)
Natural gas/LPG
Burner options
type
Pressure Jet
BG2000-S or forced draught
Input
kW
69.9
69.9
Maximum output
kW
62.5
63.0
Primary capacity
L
82
82
Total capacity
L
162
162
Heating surface area
m
2
2.46
2.46
Primary circuit pressure drop
mbar
54
54
DHW tank pressure drop
mbar
45
45
Flue circuit pressure drop
mbar
0.6
0.6
DHW connection (male BSP)
Ø
3/4
"
3/4
"
Primary connection (female BSP)
Ø
1
1/2
"
1
1/2
"
Flue connection (G)
Ø mm
150
150
Flue connection options
type
B23
B23/C13/C33/C53
BG2000 air intake connection
Ø mm
n/a
80
Weight empty
Kg
220
220
Weight full
Kg
382
382
Minimum working gas pressure
mbar
n/a
20(Nat Gas)/37(LPG)
Gas flow rate
m
3
/h
n/a
7.40(Nat Gas/2.86(LPG)
Maximum operating temperature
°C
90
90
Maximum operating pressure Primary: 3 bar Secondary: 10 bar
Gas connection - BG2000 S/60:
3/4
"
1. Stainless steel inner tank
2. Primary heating circuit
3. Flue pipes with stainless
steel turbulators
4. Rigid polyurethane
foam insulation
5. Primary shunt pump
6. Combustion chamber
7. Oil or gas burner
8. Control panel
9. Primary water flow
connection
10. Primary water return connection
11. Domestic cold water inlet
12. Domestic hot water outlet
HeatMaster®60
Litres in first 10 minutes
40°C
474
Litres in first 10 minutes
45°C
378
Litres in first 10 minutes
60°C
245
Litres in first hour
40°C
1942
Litres in first hour
45°C
1656
Litres in first hour
60°C
1106
Continuous flow 40°C
Ltrs/hr
1835
Continuous flow 45°C
Ltrs/hr
1573
Continuous flow 60°C
Ltrs/hr
1101
Reheat time to 60°C
Min
9
HeatMaster®60 Oil
HeatMaster®60 Gas/LPG
A
1698mm
1698mm
B
1583mm
1583mm
C
538mm
538mm
D
791mm
801mm(BG2000)
E
540mm
540mm
F
390mm
390mm
H
1098mm
1098mm
J
281mm
281mm
Characteristics