The HeatMaster® boiler controls the gas/air mix as a function of the airflow.   Following table defines the recommended 
CO

2

 level of the boiler: 

 
 

Boiler type  

Type of gas  %CO

2

 (max input) 

%CO2 (min. input) 

HeatMaster® 201 

Nat. gas 

9.1 

±

 0.2 

8.5 

±

 0.5 

HeatMaster® 201 

Propane 

11.0 

±

 0.2 

10.0 

±

 0.5 

HeatMaster® 201 

Butane 

11.2 

±

 0.2 

10.2 

±

 0.5 

 
 

Before starting with Propane: 

Before starting with propane a burner adjusted for natural gas, rotate the gas 
adjustment screw  ¾ turn (270°) clockwise (see picture). 

 
CO2 adjustment at max.input 

 

• 

Switch the boiler in service mode H (Press simultaneously the <mode> 
and <+> buttons during 3 seconds) 

• 

Wait during a few minutes to stabilize the boiler. 

• 

Adjust the CO

2

 level according to the table above. 

• 

With the adjusting screw: Rotate Clockwise to REDUCE CO

2

 (a 90° 

rotation generates an approx 2,5 % variation of CO

2

), or CCW to 

INCREASE CO

2

.  

• 

To return to normal mode, press simultaneously the buttons <+> and <-> 
during 3 seconds. 

 

CO2 adjustment at min.input 

 

• 

Switch the boiler in service mode L (Press simultaneously the <mode> 

and<-> buttons during 3 seconds) 

• 

Wait during a few minutes to stabilize the boiler. 

• 

Check the CO

2

 level according to the table above. 

• 

To return to normal mode, press simultaneously the buttons <+> and <-> during 3 seconds 

 

Blower speeds adjustment: 

 
The HeatMaster boilers are factory set for natural gas.  Use the following procedure to adjust the blower speed for 
propane or butane.  

• 

Key in the installer's code: 05 

• 

Press once the <mode> button, then repeatedly the <step> button to reach parameter 13 (max. speed, heating) 

• 

Set parameter 13 at 4700 for propane or butane 

• 

Press the <step> button to reach parameter 15 (max speed DHW) 

• 

Set parameter 15 at 5350 for propane or butane 

• 

Press the <step> button to reach parameter 19 (power up speed) 

• 

Set parameter 19 at 3200 for both propane and butane 

• 

Press <store> to save the new values. 

 
Check for gas leaks before rejacketting the boiler.

 

 
 
 
 