background image

2.2.2.2

ACV circulation kit

ACV offers an optional pre-assembled circulation kit comprising:
- a circulator.
- a 3-way manual motorisable valve.
- connecting pipes including a second optional circuit.
- two isolating valves.
- adapters for mounting safety valve and filling valve to right or

left of expansion tank.

2.2.2.3

Discharge

The drain cock and safety valve must be connected to the waste
water system in accordance with current regulations.

2.2.3

DOMESTIC HOT WATER CONNECTION

2.2.3.1

Pressure reducer

If the water mains pressure is greater than 6 bar, a pressure

reducer calibrated to 4.5

bar must be fitted.

2.2.3.2

Safety unit

The tank safety unit must be ACV approved and calibrated to 7
bar.
The valve discharge must be connected to the sewer drain.

2.2.3.3

Hot water expansion tank

Installing a hot water expansion tank avoids any risk of pressure
surges due to water-hammer.

2.2.3.4

Hot water circulation

If the tank is situated a long way from the point of use, then
installing a closed return circuit can provide a faster supply of
hot water always available.

2.2.3.5

Description

1.

Safety unit

2. Pressure reducer
3. Thermostatic mixing valve
4. Hot water circulator
5. Non-return valve
6. Hot water expansion tank
7. Inlet valve
8. Draw-off valve
9. Emptying valve

IMPORTANT
As a safety measure against burns, we strongly advise
installing a thermostatic mixing valve (recommended
temperature: 60° C).

Optional fittings available

2

INSTALLATION

Fig. 5a: Configuration without thermostatic mixing valve

1

2

4

6

5

7

9

8

1

2

3

4

6

5

7

9

8

Fig. 5b: Configuration with thermostatic mixing valve

4

Fig. 4: ACV circulation kit assembly

Safety unit

Ø 3/4”

Pressure reducer

Ø 3/4”

Thermostatic mixer

Ø 3/4”

Hot water expansion tank

5 litres

Содержание Delta G20

Страница 1: ...G AND SERVICING INSTRUCTIONS DELTA Classic Combination boiler with atmospheric burner ACV reserves the right to modality the technical specifications and components of its products without prior notic...

Страница 2: ...oting 6 4 SERVICING 6 4 1 Recommendation 6 4 2 Servicing the gas boiler 6 4 3 Servicing the safety devices 6 4 4 Servicing the burner 7 4 5 Emptying the boiler 7 4 6 Spare parts 7 5 DESCRIPTION 8 5 1...

Страница 3: ...egulations 2 2 2 CENTRAL HEATING CONNECTION 2 2 2 1 Examples of basic circuit configurations The drain valve and safety valve must be connected to the sewer drain 1 3 way manual motorisable mixer valv...

Страница 4: ...3 Hot water expansion tank Installing a hot water expansion tank avoids any risk of pressure surges due to water hammer 2 2 3 4 Hot water circulation If the tank is situated a long way from the point...

Страница 5: ...range N Black B Blue R Red T Green yellow 1 2 C L1 L1 N T1 T2 N T1 T2 S3 S3 N L1 230V 50 Hz 6A M R B B O B B O M M T N N 1O 11 9 2 8 7 3 6 1 12 2 4 1 3 5 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3...

Страница 6: ...n the boiler room by the electrician 2 1 3 3 2 5 4 7 1 8 6 4 1 RECOMMENDATION ACV advises that boilers should be serviced at least once a year The burner must be serviced and tested by a competent eng...

Страница 7: ...When the boiler is empty return the isolating and safety valves to their initial positions 4 5 2 EMPTYING THE HOT WATER TANK 1 Switch off the mains power to the boiler at the external switch installed...

Отзывы: