5
Minimum
Flow
Reserved for future use.
SCPTminFlow
0
Do not change from
factory default setting.
Minimum
Flow
Standby
Reserved for future use.
SCPTminFlowStby
0
Do not change from
factory default setting.
Duct Area
Reserved for future use.
SCPTductArea
0
Do not change from
factory default setting.
CO2 Set
point
Reserved for future use.
nciCO2Threshold
5000
Do not change from
factory default setting.
Input Network Variables
Function
Description
Symbol On Screen
(SCPTs, SNVTs)
Default value
Range Available
Space
Temperature
Allows the EL to connect to a
space temperature sensor
other than the one installed in
the EL.
nviSpaceTemp
327.67
°
C
(621.806
°
F)
0 –327.67
°
C
(0 – 621.806
°
F)
Temperature
Setpoint
Allows the temperature
setpoint for the occupied and
standby modes to be changed
via the network. It is used to
reset the temperature rather
than change them.
nviSetPoint
327.67
°
C
(621.806
°
F)
10 – 35
°
C
(50 – 95
°
F)
Setpoint
Offset
Shifts the temperature control
point via the network. It is
typically bound to a
supervisory node providing
outside air temperature
compensation or to an
external wall diffuser having a
relevant setpoint knob.
Operates only on occupied
and standby setpoints.
nviSetPtOffset
No offset =
32
°
F/0
°
C
-10
°
C to 10
°
C
(14
°
F to 50
°
F)
Occupancy
Commands the EL diffuser
into different occupancy
modes. It is typically set by a
supervisory node.
nviOccCmd
OC_NUL
OC_OCCUPIED,
OC_UNOCCUPIED,
OC_BYPASS,
OC_STANDBY,
OC_NUL
Duct Inlet
Temperature
Allows the EL to be used with
another mfgr’s inlet
temperature sensor
nviDuctInTemp
327.67
°
C
(621.806
°
F)
10 – 49
°
C
(50 – 120
°
F)
VAV Manual
Override
Commands the controller into
a manual mode
nviManOverride
HVO_OFF, 0.000, 0
2
See below
Emergency
Command
Commands the EL into
different emergency modes.
It is typically set up by a
supervisory node.
nviEmergCmd
EMERG_NORMAL
EMERG_NORMAL,
EMERG_PRESSURIZE,
EMERG_DEPRESSURIZE,
EMERG_PURGE,
EMERG_SHUTDOWN,
EMERG_NUL
Flow
Allows the EL to be used with
another manufacturers flow
sensor located on the
network.
nviBoxFlow
65535 l/s
(138862 cfm)
0 – 65535 l/s
(0 – 138862 cfm)