acutherm THERMA-FUSER EL Скачать руководство пользователя страница 1

 

FORM 54.2 REV 0703 

 

 

THERMA-FUSER™ 

 

EL - DDC INTEROPERABLE LINEAR VAV DIFFUSER

 

 

INSTALLATION, BALANCING & MAINTENANCE 

 

 

Table Of Contents 

INSTALLATION INSTRUCTIONS........................................................................................... 2

 

CONNECTING WIRING .......................................................................................................... 2

 

NETWORK CREATION AND COMMISSIONING OF EL DIFFUSERS .................................. 2

 

C

REATE A 

L

ON

M

AKER 

N

ETWORK

....................................................................................................................... 3

 

I

NTRODUCE 

T

HE 

EL

 

T

L

ON

M

AKER 

N

ETWORK

................................................................................................... 3

 

C

REATE 

L

ON

M

AKER 

F

UNCTIONAL 

B

LOCK

.......................................................................................................... 3

 

C

ONFIGURE 

T

HE 

EL........................................................................................................................................... 4

 

P

OWER 

F

AILURE

................................................................................................................................................ 7

 

B

INDING 

N

ETWORK 

V

ARIABLES

.......................................................................................................................... 7

 

P

UTTING 

T

HE 

EL

 

I

O

PERATING 

M

ODE

............................................................................................................... 7

 

AIR DENSITY COMPENSATION............................................................................................ 7

 

SYSTEM AIR BALANCING .................................................................................................... 7

 

TROUBLE SHOOTING ........................................................................................................... 8

 

MAINTENANCE .................................................................................................................... 11

 

CONTROLLING THE SYSTEM............................................................................................. 11

 

MEASURING ENERGY CONSUMPTION............................................................................. 15

 

TWO YEAR WARRANTY ..................................................................................................... 15

 

 

DAMAGED FREIGHT CLAIM PROCEDURE 

When the diffusers are received, inspect for damage, which may have occurred during shipment.  If damage is 
evident, it should be noted on the carrier’s freight bill.  A written request for inspection by the carrier’s agent should 
be made at once. 

 

STORAGE 

Cartons should always be stacked on end.  Do not stack cartons flat on the sides.  Excessive weight may cause 
damage to the diffusers. 
Do not store for prolonged times at temperatures exceeding 130

°

F(56

°

C).  Acceptable humidity level 5-95% relative 

humidity noncondensing. 

 

IDENTIFICATION 

Models are factory shipped one per carton.  The model designation is on the diffuser and on the carton. 

 

INSTALLATION PRECAUTIONS 

When installing diffusers make sure construction debris does not enter the diffuser or duct system. 
Because the EL controls room temperature by sensing the room air induced up from the room, care should be 
taken not to disturb room air induction and entrainment  

 

Содержание THERMA-FUSER EL

Страница 1: ...amage which may have occurred during shipment If damage is evident it should be noted on the carrier s freight bill A written request for inspection by the carrier s agent should be made at once STORA...

Страница 2: ...n site If you are building the network off site these steps are completed after mechanical installation and during network commissioning 1 Connect network cable to the EL Network terminals Two wires a...

Страница 3: ...is the first check the Load XIF option and then select Browse Note The XIF file provides LonMaker For Windows information about the EL 4 Navigate to the directory where the EL XIF file is located then...

Страница 4: ...d for future use SCPTmaxFlow 65535 l s Do not change from factory default setting Occupancy Bypass Time The amount of time in seconds the EL operates in occupied mode when the occupancy input is set t...

Страница 5: ...fts the temperature control point via the network It is typically bound to a supervisory node providing outside air temperature compensation or to an external wall diffuser having a relevant setpoint...

Страница 6: ...bles Example the EL diffuser will use the value of nviSetPoint if this value is valid non default as set point instead of nciSetPnts Output Network Variables Function Description Symbol On Screen SCPT...

Страница 7: ...er network variable you want to connect 4 Repeat steps 1 2 3 for other network connections Putting The EL In Operating Mode 1 If the network was built off site and it is time to put the physical EL in...

Страница 8: ...ds a static pressure no higher than 25 wg 62 Pa but some system designers may accept higher noise levels and opt for a higher static pressure Care should be taken not to exceed the design maximum stat...

Страница 9: ...or trouble shooting to avoid more complicated control algorithms within that band Control is intended to be tighter but will depend on system conditions If any of the set points are changed to achieve...

Страница 10: ...ol to select or highlight the specific EL unit Browse the network variables to locate nvoUnitStatus Go to the end of the fields and look at the last number set which is ALARM The alarm codes are 1 Fau...

Страница 11: ...As with all VAV systems the goals are to achieve a constant supply air temperature may be reset to another constant supply air temperature and to limit the supply air temperature Limits for supply air...

Страница 12: ...S UNOCCUPIED SETPTS FAN ON HEAT ON Y FAN OFF HEAT OFF N N SEE OCCUPIED FLOW CHART N TURN THE FAN ON Y FROM OTHER FLOW CHARTS Flow Chart For AHU Controller Main Page WARM UP IS OPTIONAL OTHERWISE GO TO...

Страница 13: ...G MODE Y Y RESET THE 30 SEC TIMER N CLEAR ALL TIMERS TO MAIN FLOW CHART N COOL ON IS 30 MIN TIMER SET MORE THAN HALF ROOM TEMPS SETPT N N HEAT ON HEAT OFF SET THE 30 MIN TIMER SET THE 30 SEC TIMER Y H...

Страница 14: ...HEAT Y 30 MIN TIMER EXPIRED N Y MORE THAN HALF ROOM TEMPS SETPTS N HEAT OFF SET MONITOR FLAG SET 30 MIN TIMER Y HEAT ON RESET THE 30 SEC TIMER N N CLEAR WARM UP FLAG CLEAR ALL TIMERS TO MAIN FLOWCHAR...

Страница 15: ...ects which would not have occurred had reasonable care been taken provided that such parts have been inspected by Acutherm and found defective and provided the diffusers have been given normal and pro...