PLEASE READ ALL 4 STEPS BEFORE PROGRAMMING

1.

 

Enter B-Level programming mode by holding down button until status LED flashes rapidly, release, hold 

down until rapid flash again, release, then immediately enter programming function as described in 

step 2. 

2.

 

Enter a programming function by pressing button the number of times as the desired function number 

from the 

B-Level Detailed Function Tables 

below (e.g., press twice for function 2, 

Semi-

Auto Grace Period

).

3.

 

Staus LED will flash back the selected function’s current setting (e.g., 3 flashes for 15 sec). To change 

setting, proceed to step 3 before flash back sequence repeats 3 times. To exit the current function or to 

change to a different function, wait for sequence to repeat 3 times and return to step 1.

4.

 

Press button the number of times indicated in the particular function’s detailed table for the new 

desired setting (e.g., press 1 time for 0 sec). As confirmation of setting change, status LED flashes back 

the new setting 3 times before exiting.  

INSTALLATION INSTRUCTIONS

NOTE:

 

For information on additional advanced settings, including resetting unit to factory 

defaults, contact:

Technical Support: 1.800.535.2465

nPS 80 EZ 

B-LEVEL PROGRAMMING INSTRUCTIONS  ______________________________

B-LEVEL DETAILED FUNCTION TABLES  ___________________________

*

Indicates factory default unless dependent on model number.

**

 Setting precision of 0.1V is available via SensorView. Device status LED blinks out current value 

rounded to nearest selection above. 

1 = Name Unit w/ Number

 

1

 1 

3

 3 

5

 5 

7

 7 

9

  9 

 

2

 2 

4

  4  

6

 6 

8

  8  

10

 Unassigned*

2 = Manual On (Semi-Auto) Grace Period

 

1

  0 sec 

3

  15 sec*

3 = Predictive Exit Time

 

1

  5 sec 

3

  7 sec 

5

  9 sec 

7

  15 sec 

9

  30 sec

 

2

  6 sec 

4

  8 sec  

6

  10 sec* 

8

  20 sec 

4 = Predictive Grace Time

 

1

  0 sec 

3

  10 sec 

5

  30 sec 

7

  50 sec

 

2

  5 sec* 

20 sec 

6

  40 sec 

8

  60 sec

11

 

=  Occupancy Tracking

 

1

 Disable 

2

 Enable*

12

 

=  Occupancy Tracking Channel

 

1 - 16

 (e.g., 

1

 = Channel 1*;   

2

 = Channel 2;  etc.)

13

 

= Photocell Tracking

 

1

 Disable 

2

 Enable*

14

 

= Photocell Tracking Channel

 

1 - 16

 (e.g., 

1

 = Channel 1*;   

2

 = Channel 2;  etc.)

15

 

= Switch Tracking

 

1

 Disable 

2

 Enable*

17

 

= Forced Override

 

 

1

  Disabled (not forced)* 

2

 

Override On 

 

3

  Override Off

18

 

= Special Operating Mode

 

1

 Normal* 

   

5

  Predictive Off 

 

2

  Manual On 

 

 

6  

Manual to Override On 

 

Auto to Override On

 

 

7  

Manual to Normal

 

4

  Manual to Full Auto

22 = Maintain Dim Level When Vacant

 

No* 

2

 Yes 

23 = Special Switch Tracking Mode

 

1   

Disable* 

2

   Ignore Offs 

Ignore Ons 

4  Ignore Ons & Offs

29

 

=  Occupancy Expiration of Manual Off

 

1

    Disabled* 

2    

Enabled

30  = Timed Expiration of Manual Off

  

1

    Disabled* 

2    

Enabled

31

 

= High End Trim**

 

1

   0.7V 

3

   2V        

5

   4V       

7

   6V      

9

   8V 

11

   10V 

 

2

   1V 

4

   3V        

6   

5V       

8

   7V    

10

   9V

32

 

= Low End Trim**

 

1

   0.7V 

3

   2V        

5

   4V       

7

   6V      

9

   8V 

11

   10V 

 

2

   1V 

4

   3V        

6   

5V       

8

   7V    

10

   9V

• Mount through a ½” knockout in any junction box or luminaire. Secure with lock nut.
• Following above wiring diagram, connect wires to line voltage feed(s), neutral(s), 

and load.

• Connect low voltage violet and gray dimming wires to 0-10 VDC driver leads and 

green wire to an approved ground connection. Note wires have 600V rated insula-
tion.

• Interconnect unit (via RJ-45 ports) with other nLight devices in lighting zone using 

CAT-5e cables.

BUTTON

LED

RJ-45 PORTS

*

Indicates Factory Default

A-LEVEL DETAILED FUNCTION TABLES  ___________________________________________

2 = Lumen Compensation

 

 

Disabled (n100)  

Enabled (n80)

3

 

= Idle Time Until Dim

 

1

  30 sec 

3

  5 min  

5

  10 min  

7

  15 min   

9

 

20 min 

 

2

  2.5 min 

4

  7.5* min  

6

  12.5 min  

8

  17.5 min   

5

 

= Switch Tracking Channel

 

1 - 16

 (e.g., 

1

 = Channel 1*;  

2

 = Channel 2;  etc.)

6

 

= Follow Photocell Mode

 1

 Disable* 

Enabled (Neg) 

3    

Enabled (Pos/Neg)

7

 

= Secondary Zone Dimming Offset

 

1

  -100%     

5

    -60%  

 

-20%     

13

    20%  

   

17

   60%         

21

   100% 

 

2

  -90%  

  

6    

-50%  

 

10

  -10%     

14

    30%  

   

18

   70% 

 

3

 -80% 

 

  7    

-40%  

 

11

     0% *      

15

    40%  

   

19

   80% 

 

4

  -70%  

 

  8

    -30%  

 

12

   10%  

  

16

   50%  

   

20

   90%  

8

 

= WallPod Dimming Adjustments

 

1

 Permanent*   

Temporary  

Photocell Temp. Override

9

 

= Restore Factory Defaults

 

1

    Maintain Current* 

Restore Defaults

19

 

= Dimming Rate

 

1

  5 min 

  

2    

15 sec  

5 sec* 

4    

2 sec  

Instant

23

 

= Occupied Bright Level

 

1

  1%          

3

 20%       

5

     40%  

7

    60%   

9

  80%  

11

 100%* 

 

2

  10%        

4

 30%       

6

     50%  

8

    70%   

10

 90% 

24

 

= Unoccupied Dim Level

 

1

  1%*          

3

 

20%       

5

     40%  

7

    60%   

9

 

80%  

11

 100% 

 

2

  10%         

4

 

30%       

6

     50%  

8

    70%   

10

 90% 