PLEASE READ ALL 4 STEPS BEFORE PROGRAMMING
1.
Enter B-Level programming mode by holding down button until status LED flashes rapidly, release, hold
down until rapid flash again, release, then immediately enter programming function as described in
step 2.
2.
Enter a programming function by pressing button the number of times as the desired function number
from the
B-Level Detailed Function Tables
below (e.g., press twice for function 2,
Semi-
Auto Grace Period
).
3.
Staus LED will flash back the selected function’s current setting (e.g., 3 flashes for 15 sec). To change
setting, proceed to step 3 before flash back sequence repeats 3 times. To exit the current function or to
change to a different function, wait for sequence to repeat 3 times and return to step 1.
4.
Press button the number of times indicated in the particular function’s detailed table for the new
desired setting (e.g., press 1 time for 0 sec). As confirmation of setting change, status LED flashes back
the new setting 3 times before exiting.
INSTALLATION INSTRUCTIONS
NOTE:
For information on additional advanced settings, including resetting unit to factory
defaults, contact:
Technical Support: 1.800.535.2465
nPS 80 EZ
B-LEVEL PROGRAMMING INSTRUCTIONS ______________________________
B-LEVEL DETAILED FUNCTION TABLES ___________________________
*
Indicates factory default unless dependent on model number.
**
Setting precision of 0.1V is available via SensorView. Device status LED blinks out current value
rounded to nearest selection above.
1 = Name Unit w/ Number
1
1
3
3
5
5
7
7
9
9
2
2
4
4
6
6
8
8
10
Unassigned*
2 = Manual On (Semi-Auto) Grace Period
1
0 sec
3
15 sec*
3 = Predictive Exit Time
1
5 sec
3
7 sec
5
9 sec
7
15 sec
9
30 sec
2
6 sec
4
8 sec
6
10 sec*
8
20 sec
4 = Predictive Grace Time
1
0 sec
3
10 sec
5
30 sec
7
50 sec
2
5 sec*
4
20 sec
6
40 sec
8
60 sec
11
= Occupancy Tracking
1
Disable
2
Enable*
12
= Occupancy Tracking Channel
1 - 16
(e.g.,
1
= Channel 1*;
2
= Channel 2; etc.)
13
= Photocell Tracking
1
Disable
2
Enable*
14
= Photocell Tracking Channel
1 - 16
(e.g.,
1
= Channel 1*;
2
= Channel 2; etc.)
15
= Switch Tracking
1
Disable
2
Enable*
17
= Forced Override
1
Disabled (not forced)*
2
Override On
3
Override Off
18
= Special Operating Mode
1
Normal*
5
Predictive Off
2
Manual On
6
Manual to Override On
3
Auto to Override On
7
Manual to Normal
4
Manual to Full Auto
22 = Maintain Dim Level When Vacant
1
No*
2
Yes
23 = Special Switch Tracking Mode
1
Disable*
2
Ignore Offs
3
Ignore Ons
4 Ignore Ons & Offs
29
= Occupancy Expiration of Manual Off
1
Disabled*
2
Enabled
30 = Timed Expiration of Manual Off
1
Disabled*
2
Enabled
31
= High End Trim**
1
0.7V
3
2V
5
4V
7
6V
9
8V
11
10V
2
1V
4
3V
6
5V
8
7V
10
9V
32
= Low End Trim**
1
0.7V
3
2V
5
4V
7
6V
9
8V
11
10V
2
1V
4
3V
6
5V
8
7V
10
9V
• Mount through a ½” knockout in any junction box or luminaire. Secure with lock nut.
• Following above wiring diagram, connect wires to line voltage feed(s), neutral(s),
and load.
• Connect low voltage violet and gray dimming wires to 0-10 VDC driver leads and
green wire to an approved ground connection. Note wires have 600V rated insula-
tion.
• Interconnect unit (via RJ-45 ports) with other nLight devices in lighting zone using
CAT-5e cables.
BUTTON
LED
RJ-45 PORTS
*
Indicates Factory Default
A-LEVEL DETAILED FUNCTION TABLES ___________________________________________
2 = Lumen Compensation
1
Disabled (n100)
2
Enabled (n80)
3
= Idle Time Until Dim
1
30 sec
3
5 min
5
10 min
7
15 min
9
20 min
2
2.5 min
4
7.5* min
6
12.5 min
8
17.5 min
5
= Switch Tracking Channel
1 - 16
(e.g.,
1
= Channel 1*;
2
= Channel 2; etc.)
6
= Follow Photocell Mode
1
Disable*
2
Enabled (Neg)
3
Enabled (Pos/Neg)
7
= Secondary Zone Dimming Offset
1
-100%
5
-60%
9
-20%
13
20%
17
60%
21
100%
2
-90%
6
-50%
10
-10%
14
30%
18
70%
3
-80%
7
-40%
11
0% *
15
40%
19
80%
4
-70%
8
-30%
12
10%
16
50%
20
90%
8
= WallPod Dimming Adjustments
1
Permanent*
2
Temporary
3
Photocell Temp. Override
9
= Restore Factory Defaults
1
Maintain Current*
2
Restore Defaults
19
= Dimming Rate
1
5 min
2
15 sec
3
5 sec*
4
2 sec
5
Instant
23
= Occupied Bright Level
1
1%
3
20%
5
40%
7
60%
9
80%
11
100%*
2
10%
4
30%
6
50%
8
70%
10
90%
24
= Unoccupied Dim Level
1
1%*
3
20%
5
40%
7
60%
9
80%
11
100%
2
10%
4
30%
6
50%
8
70%
10
90%