Installation and Commissioning Guide
Split Ducted Units
PRELIMINARY DATA ONLY
Ver. 3.03 220620
THIS LABEL TO BE REMOVED ON SIGN-OFF
13
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-084
Ver. 3 22xxxx
EFV210S / EFV240S
OVERALL NOMINAL DIMENSION (H X W X D)
= 483 X 1269 X 412
SUPPLY DUCT (H X W) = 305 X 734
RETURN DUCT = 453 X 1095
UNIT MODEL NUMBER
UNIT WEIGHT
(kg)
EFV210S / EFV240S
43
1207
236
337
61
337
236
61
305
117
483 O/A
91
322
70
1269 O/A
1185
(MTG C-C DIST)
1185
(MTG C-C DIST)
57
270
85
56
1095
56
453
357
357
412 O/A
11
11
11
11
15
15
TOP VIEW
FRONT VIEW - SUPPLY AIR
REAR VIEW - RETURN AIR
SIDE VIEW
1207
236
337
61
337
236
61
305
117
483 O/A
91
322
70
1269 O/A
1185
(MTG C-C DIST)
1185
(MTG C-C DIST)
57
270
85
56
1095
56
453
357
357
412 O/A
11
11
11
11
15
15
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
*
Electrical box and/or
pipe connections are
located on the Right
side of the indoor unit.
LEFT
SERVICE
CLEARANCE
890 MM
TOP VIEW
FAN SECTION
DUCT WORK
DUCT WORK
FROM COIL SECTION
(0M MIN - 6M MAX)
*RIGHT
SERVICE
CLEARANCE
890 MM
HEIGHT CLEARANCE = 410mm
NOTES:
1. Do not scale drawing.
All dimensions are in mm unless
specified.
2. Service Clearances given are suggested
minimum based on the condition that
the spaces around the units are free
from any obstructions and a walkway
passage of 1000mm between the units
or between the unit and the outside
perimeter is available.
3. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra
charges incurred due to lack of access.
• Left Service Clearance can be 100mm
minimum if Right Service Clearance is
applicable.
• Right Service Clearance can be
600mm minimum if Left Service
Clearance is applicable.
• Height Service Clearance can be
100mm minimum if Right Service
Clearance is applicable.
THIRD ANGLE
PROJECTION