background image

TXV REPLACEMENT - PACKAGE UNIT

 

 

6

Tri-Capacity Package - TXV Replacement  

Doc. 9590-2014-19B  Ver. 3  211105

 TXV Supplier Default Setting and Specifications

SH

TXV Supplier Default Superheat Setting (SS):

   TGE 10 (2 Full Turns

*

):  SS = 4K (-13.8°C) 

           TR 6 (3 1/3 Turns

*

):  SS = 2K (-15.8°C) 

*

 No. of Turns required from spring stop point 

   = 19mm (3/4”)

T = 10Nm (7 ft-lbf)

Superheat Adjustment Parameter

+

-

Change in Superheat per 360° ≈ 2°C

Undo TXV

Protective Cap

TXV

Remove
Protective Cap

Superheat 
Adjustment 
Spindle

 

Stop

1.  Remove Protective Cap from the TXV Valve Body.

2. Turn Superheat Adjustment Spindle until it reach the stop 

point, as shown above.  

Change in Superheat / Turn :

  TGE 10: ∆SH / 360° ≈ 2°C

          TR 6: ∆SH / 360° ≈ 0.6°C

Replace TXV

Protective Cap

TXV

Replace
Protective Cap

3. To get into TXV supplier default setting, turn Superheat 

Adjustment Spindle in the direction as shown. Refer to 
TXV specifications above for the number of turns required 
for particular TXV model. 

4. Replace TXV Protective Cap onto Valve Body.   

NOTES

Using the above set point as reference, further adjust the TXV as per instructions in the TXV.
Replacement section of this manual in order to finally set the TXV into ActronAir default settings.  