Installation Notes
• Always remember to factory default the controller before you start programming.
• Always remember to place the supplied Varistor across the terminals of the lock terminals to protect
the relay contacts.
• Never use the onboard relay to switch AC mains voltage. An external relay isolated electrically from
the ACT 10 should be used for this purpose.
• Don’t forget to change the programming code to something known only to yourself.
Important
: As with any Access Control system, always ensure there is an alternate means
of escape in the event of the unit failing to operate due to power loss or in the event of fire.
ACT 10 Digital Keypad Operating & Installation Instructions
2
ACT 10 Digital Keypad
ACT 10
ACT 10 Flush Kit
ACT 10 FK
ACT 10 Weather Shield
ACT 10 WS
Ordering Information
Product Specification
Number of Users
10 PIN Codes
Supply Voltage
12 – 24 Volts AC or DC
Current Consumption
40mA (nominal), 120mA (maximum)
Operating Temperature
-10 to +50 degrees C
Door Open Time
0 - 255 seconds
Relay Contact Rating
5A / 250Vac
Controller Size
(H x W x D):
138 x 87 x 37 (mm)
Controller Weight
700 grams
Installation
Indoor or Outdoor (IP54)
Mounting
Surface or Flush
Output Rating
100mA