Engineering Mode
ECN-Lx InstallationGuide
-
5
-
ACT POWER TAIWAN CO., Ltd.
2017 ACT POWER All right reserved
1
E
2 3 4
ID Tx 485
1 2 3 4
1 2 3
N T Rx 232
S1
BR
SF
S2
Freq.
S3
1
E
2 3 4
ID Tx 485
1 2 3 4
1 2 3
N T Rx 232
S1
BR
SF
S2
Freq.
S3
Using this mode to test the transmission data accuracy and the signal strength.
< Dipswitch Setting >
Transmitting
S1-1
0 (E)
S1-3
0 (Tx)
0
1
< Dipswitch Setting >
Receiving
S1-1
0 (E)
S1-3
1 (Rx)
0
1
1. Remove the power from both transmitting and receiving ECN-Lx devices
2. Switching S1-1 to “E”, and switching S1-3 to “Tx” on the transmitting terminal
3. Switching S1-1 to “E”, and switching S1-3 to “Rx” on the receiving terminal
4. Make sure that S2-BR
、
S2-SF and S3-Freq.are at the same position on both transmitting and
receiving terminal
5. Plug the power connector into both transmitting and receiving ECN-Lx devices
6. Check front LED indicator on transmitting terminal, it will blink every 0.5 second to indicate
transmitting the data. If not, please check Step-2
7. Check front LED indicator on receiving terminal, it will blink every 0.5 second to indicate
receiving the data from transmitting terminal. If not, please check Step-3, Step-4 and Step-6
8. Connect transmitting terminal and computer with RS-232 cable, and using serial monitor tool
to monitor the data transmission. Sometimes you will need to use NULL Modem (It isn’t
included in the shipment) to connect ECN-Lx and equipment
9. Data Format XX XX XX XX XX XX XX XX
1 2 3 4 5 6 7 8
1~4
Device ID
5
Firmware Version
6
00~FF hexadecimal continuous number to
check if there any data lost during transmission
7~8
Signal strength (RSSI 17~-125 )*