5. SELECTION PROCESS
WATER PRESSURE DROP VS FLOW RATE
MODEL : A5ACV 30CR - COOLING
Water Flow
m
3
/hr
Pump Head
kPa
System Head
kPa
Available Head Presure
kPa
1.26
109.00
26.56
82.44
1.30
108.40
26.59
81.81
1.32
108.20
28.94
79.26
1.36
108.00
31.54
76.46
1.39
107.20
31.39
75.81
1.43
106.00
31.81
74.19
1.49
105.00
32.30
72.70
MODEL : A5ACV 30CR - HEATING
Water Flow
m
3
/hr
Pump Head
kPa
System Head
kPa
Available Head Presure
kPa
1.89
95.00
38.34
56.66
1.80
96.60
35.40
61.20
1.66
101.00
32.45
68.55
1.44
106.00
28.64
77.36
1.12
111.80
18.51
93.29
MODEL : A5ACV 55CR - COOLING
MODEL : A5ACV 55CR - HEATING
Water Flow
m
3
/hr
Pump Head
kPa
System Head
kPa
Available Head Presure
kPa
2.82
175.47
66.10
109.37
2.79
179.25
68.52
110.73
2.73
182.26
67.30
114.96
2.44
200.00
67.98
132.02
1.89
226.42
67.92
158.50
50
Water Flow
m
3
/hr
Pump Head
kPa
System Head
kPa
Available Head Presure
kPa
1.58
240.00
69.64
170.36
1.97
222.64
67.41
155.23
2.28
207.55
67.18
140.37
2.52
194.34
66.91
127.43
2.68
185.28
67.64
117.64
2.78
180.00
68.11
111.89
2.80
176.98
66.33
110.65
Содержание A5ACV 100 CR
Страница 43: ...INSTALLATION A5ACV 30 55 75CR 41 ...
Страница 44: ...A5ACV 30CR A5ACV 55CR 75CR 42 ...
Страница 78: ...10 WIRING DIAGRAMS PA R T NO 50 13 9 026086 MODEL A5ACV 30CR 76 ...
Страница 79: ...77 MODEL A5ACV 55CR ...
Страница 80: ...MODEL A5ACV 75CR PA R T NO 50 13 4 083602 78 ...
Страница 81: ...MODEL A5ACV 100 135CR 79 ...