1-4
• Electrical supply and installation is to conform to local authority's (e.g. National Electrical Board) codes and regulations.
• Voltage supply fluctuation must not exceed ±10% of rated voltage. Electricity supply lines must be independent of welding
transformers which can cause high supply fluctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
• The indoor unit must be installed in such a way that is free from any obstacles in the path of cool air discharge and warm air
return, and must allow spreading of air throughout the room (near the center of the room).
CC Model
• Use the hanger supplied with the unit.
• Make sure that the wall is sufficiently strong to withstand
the weight.
Provide clearance for servicing ease and optimal air flow as
shown in the diagram.
INSTALLATION OF INDOOR UNIT
10 mm
10 mm
140 mm
CK Model
• The installation place must be strong enough to support a load 4 times weight of the indoor unit to avoid noise amplification
and vibration.
• The installation place (handing ceiling surface) must be assuring levelness and the height in the ceiling is 350mm or more.
• The indoor unit must be placed away from heat and steam sources (avoid installing it near an entrance).
• Must be provide clearance for the indoor unit from the wall and obstacles as shown in the figure.
Max. 0.3 m
Min. 0.5 m
Min. 0.5 m
Min. 0.5 m
Min. 1.0 m
Max. 3.0 m
Obstacle
Beam
Floor
Center distance of axle (see drawing below)
Unit Installation
• Measure and mark the position for the hanging rod. Drill
the hole for the angle nut on the ceiling and fix the hanging
rod.
• The installation template is extended according to
temperature and humidity. Check on dimensions in use.
• The dimensions of the installation template are the same as
those of the ceiling opening dimensions.
• Before ceiling laminating work is not completed, be sure
to fit the installation template to the indoor unit.
NOTE:
Be sure to discuss the ceiling drilling work with the installers
concerned.
Piping Direction
Unit Hanging
• Confirm that the pitch of the hanging rod is 790mm x
620.5mm sharp.
• Hold the unit and hang it on the hanging rod with the nut
and washer.
• Adjust the unit height to 35.0mm between the indoor unit
bottom surface and the ceiling surface.
• Confirm with a level gauge that the unit is installed hori-
zontally and tighten the nut and bolt to prevent unit from
falling and vibrating.
• Open the ceiling board along the outer edge of the paper
installation template.
All manuals and user guides at all-guides.com
Содержание IM-FCU-0501-ACSON
Страница 2: ...All manuals and user guides at all guides com...
Страница 46: ...6 2 CC 0 i CK 0 i CE 0ii 02 03 04 7 8 8 8 All manuals and user guides at all guides com a l l g u i d e s c o m...
Страница 47: ...6 3 CE CK CC All manuals and user guides at all guides com...
Страница 49: ...6 5 20 8 0 4 All manuals and user guides at all guides com...
Страница 52: ...6 8 3 4 1 3 2 3 4 5 6 1 40 2 3 1 40 2 2 2 1 2 3 All manuals and user guides at all guides com...
Страница 53: ...All manuals and user guides at all guides com...
Страница 55: ...d IM FCU 0501 ACSON d U d U nK W d b VO d VO CC CE CK All manuals and user guides at all guides com...
Страница 56: ...All manuals and user guides at all guides com a l l g u i d e s c o m...
Страница 67: ...All manuals and user guides at all guides com...